F1 the on-change case is tested as slow, F2 override and direction checks, F3 the 3.75 s rule in the texts, F4 the quarter figures and the live note. No behaviour change. Co-Authored-By: Claude <noreply@anthropic.com>
82 lines
5.0 KiB
Markdown
82 lines
5.0 KiB
Markdown
# SAFETY-136 - a slow meter gets a gentler loop until the last move shows
|
|
|
|
**Status: for review.** Code: `app/settle.py`, a call in `Controller.cycle()`
|
|
(`app/ctl_cycle.py`). Tests: `test_safety136.py`. No option, no text change.
|
|
|
|
**Problem.** On a 5 s meter, Home Assistant readings 10-15 s late are not
|
|
found (SAFETY-129): they look like a slow battery (R2-1), and a hold does not
|
|
help (a perfect one cut the export of the oven by 7 %, SAFETY-129 review).
|
|
With moving loads the loop answers the same stale error at each cycle and
|
|
overshoots: an oven, a kettle and hob, the owner's day or a step export 3-10
|
|
times what they do with no lag. The fix is a calmer loop, not a detector.
|
|
|
|
**Decision.** After a move of 150 W or more, a loop on a slow meter runs at half
|
|
its gain until the meter has fallen by half of that move, or for 2 cycles.
|
|
Slow is judged from the readings that arrive: the usual gap
|
|
between them, over the last 60 s and at least 5 readings, is over 3.75 s (the
|
|
limit of SAFETY-128's fast meter fit). It counts arrivals, not changes of
|
|
value: on the recorded day at 1-2 s the value-based test (`MeterFit.slow()`)
|
|
called 24 % of the cycles slow, because the recorded house repeats a value
|
|
for 5 s or more, and the commands then differed from base. So there is no
|
|
option. At a meter with a usual gap of 3.75 s or less (1-3 s) it is false, the tuning is never touched and the
|
|
commands are those of the tree before. A meter that Home Assistant passes on
|
|
only when its value changes looks as slow as its changes are far apart, as it
|
|
does to SAFETY-128's fits: a 1-2 s meter with a value that holds for 5 s or
|
|
more is then treated as slow, and the loop is gentler for it (the cost below).
|
|
With no lag the meter shows a move at the next reading, so the wait ends at
|
|
once.
|
|
|
|
**Candidates** (SAFETY-129 sim, real `cycle()`, 5 s meter, sum over oven,
|
|
kettle and hob, owner shape over the oven and over the heat pump, step down,
|
|
step up, flat; export Wh, lag 0 / 10 s / 15 s; base 64 / 340 / 363):
|
|
|
|
| Candidate, only at a slow meter | 0 s | 10 s | 15 s | Import Wh, 0 / 10 / 15 s |
|
|
|---|---|---|---|---|
|
|
| gain 0.4 | 97 | 201 | 299 | 97 / 224 / 301 |
|
|
| gain 0.3 | 128 | 185 | 322 | 132 / 232 / 293 |
|
|
| step limit 500 W | 118 | 285 | 293 | 110 / 325 / 324 |
|
|
| cut fast, raise slowly (0.6 / 0.3) | 55 | 140 | 226 | 140 / 332 / 345 |
|
|
| ignore 1 cycle after a move | 93 | 216 | 325 | 90 / 240 / 291 |
|
|
| ignore 2 cycles after a move, unless the meter showed half | 69 | 206 | 277 | 62 / 240 / 354 |
|
|
| **half gain for 2 cycles after a move, unless the meter showed half** | **67** | **189** | **296** | **62 / 223 / 288** |
|
|
|
|
A lower gain for good, a step limit and a fixed ignore all make a 5 s meter
|
|
with no lag worse (export +30-110 Wh, quarter peak up to 150 W): that is the
|
|
common case. Cutting fast and raising slowly moves export to import and peak.
|
|
Waiting only while the last move has not shown costs nothing with no lag.
|
|
Ignoring the meter (the 2-cycle line) was worse than half gain where the plant
|
|
is slow, not the readings late: a 12 s dead time with one inverter went from
|
|
250 to 841 Wh import and a quarter peak of 206 to 1 509 W, so the loop keeps
|
|
following at half gain.
|
|
|
|
**What it gives** (5 s meter; the pull request and the report have each
|
|
scenario). Export summed over the seven houses: 10 s late 340 -> 189 Wh
|
|
(-44 %, import 363 -> 223), 15 s late 363 -> 296 Wh (-19 %, import 281 ->
|
|
288), together -31 %. At 15 s the oven and the owner's oven are not better
|
|
(92 / 39 Wh against 91 / 37), the kettle and the steps are. No lag: export
|
|
64.4 -> 66.5 Wh (kettle +2), import and peak the same.
|
|
|
|
**What it costs.** The loop follows a real step more slowly: half gain for up
|
|
to two cycles after each move of 150 W or more. Of the 136 sim runs (every
|
|
SAFETY-129 review scenario and its 15 harm runs), 56 at 4-10 s meters differ
|
|
from base. Together their export is 10 363 -> 9 559 Wh (-8 %) and import
|
|
8 389 -> 7 835 Wh (-7 %). Only 5 export more than 1 Wh and 14 import more:
|
|
export by at most 11.5 Wh (a 10 s battery lag, +10 %), import by at most
|
|
17 Wh (a 12 s dead time, one inverter, +7 %), and the quarter average by at
|
|
most 35 W, except two import quarters: +73 W (10 s meter, 10 s dead time,
|
|
export -59 Wh) and +40 W (`dead10_p6`, -6 to 34 W, export -68 Wh). Slow
|
|
batteries with a dead time of 8-10 s export 5-39 % less; a 12 s dead time is
|
|
the same. `READINGS_LATE` holds are the same seconds in every run.
|
|
|
|
**Live, a 1-2 s meter can be judged slow.** Through Home Assistant on change,
|
|
a value that holds for 4-10 s makes a 1 s meter slow. In 20 rig scenarios the
|
|
commands were those of base. On the recorded day (1 s, N=1, 1 day, repeats
|
|
dropped; its values hold about 5 s) it was slow in 33 % of cycles, half gain
|
|
in 83 cycles, 15 422 commands in both trees, 4 016 with another value (at
|
|
most 190 W apart), cost 0.61 EUR in both (review of SAFETY-136).
|
|
|
|
**Does not change.** Meters of 1-2 s: the same commands in all 63 runs (34
|
|
at 1 s, 29 at 2 s), and the recorded-day digests (see the report). The late
|
|
verdict, the hold and the freeze tests. 15 s late is only partly helped, and
|
|
30 s late is the hold's (SAFETY-129).
|