admin 6aabb832fc SAFETY-03: alarm when a computed setpoint exceeds the rating, do not just clip it (#12)
The clamp already existed; the alarm did not, and specs 10.3 records a silently clipped integrator that reached 14,768 W while every dashboard read a legal 5000 W. OUTPUT_CLAMP now alarms on every engagement, with its own reason code, notification_id, status row and counter, distinct from ordinary saturation. Clamp lives in write_setpoint(), the one path every write takes; the alarm runs after it, out of the write path. Not a trip: the clamped value is written and the loop keeps running.

Reviewed over two rounds. Round one held the PR on three findings: clamp_to_rating() returned early from the max_w stage so the device bound was never applied when the first stage engaged (the bigger the overshoot, the less the guard did), and two checks that could not fail - range(CLEAR_CYCLES - 1) issued zero clean cycles at CLEAR_CYCLES=1, and REASSERT_S + 9 passed for any value including an hour of silence. All three fixed in 4e66583 and verified independently: both clamp stages now run on symmetric, asymmetric and wider-device ratings with no escapes; the 492-point sweep was shown to bite where the witness values cannot (a positive-side-only device bound gives 181 escapes with both witnesses passing, and a single-grid-point hole gives 1); and the rewritten checks pin the requirement rather than the constant - CLEAR_CYCLES red at 1 and at 51, REASSERT_S red at <=5 and at >=300.

Author's six mutations all reproduced red, including the cross-suite one where removing the event-log coalescing turns test_freeze red - this guard's log had been evicting SAFETY-18's METER FROZEN? row. Headline claim reproduced: keying the alarm on Decision.reason instead of the i_clamped/clamped booleans takes the 10.3 replay from 2 engagements to 0. AC2 verified with an independent saturation-without-clamping scenario: sat_count 10 at 21.6% of the rating, zero clamp engagements.

Two reviewer mutations survive, both recorded and neither blocking: describe() dropping the bound name (the bound field itself is pinned), and abs() on limit_w (unreachable under the int(100,5000) schema).

First merge in this repository to pass through CI-01's gate rather than around it: 46383c5 merged release/1.0 in so the required context could run at all, and checks / unit (pull_request) reports success in 2m32s.

Note for TEST-06 (#14), which rebases behind this: it conflicts in BOTH app/main.py and test_freeze.py, and its 8 red assertions are its own service-keyed notification counting - keying those four call sites on notification_id turns the whole suite green against this app/ with no change here.
2026-08-30 17:22:30 +02:00

GoodWe RS485 Controller — Home Assistant add-on repository

Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.

repository.yaml            add-on repository metadata
goodwe_controller/         the add-on
  config.yaml              manifest + options schema (the per-site config form)
  app/                     the controller
    control.py             the control law — pure functions, no I/O
    maintenance.py         the monthly cycle state machine
    hass.py                Supervisor/Core API access
    store.py               persistent state in /data
    mqtt.py                optional status entities
    web.py                 ingress UI
    main.py                orchestration, heartbeat, failsafe behaviour
  test_control.py          runnable checks — no framework needed
  test_maintenance.py      runnable checks — walks a full cycle in fake time
  DOCS.md                  the add-on's documentation tab
firmware/goodwe-master.yaml  ESPHome config for the T-CAN485
estop/rs485_log.py           optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf  the guide techs carry (10pp, A4)
docs/build_guide.py          its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md             how to edit and rebuild the guide

Picking this up after a break? Read HANDOVER.md first — current state, what is known broken, and what to do next.

Install

Settings → Add-ons → Add-on store → ⋮ → Repositories → add

https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon

then install GoodWe RS485 Controller.

⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it anonymously; against a private repo the store shows nothing and gives no useful error. If it must stay private, install locally instead: copy goodwe_controller/ into the machine's /addons/ folder, then ha store reload — it appears as a Local add-on.

⚠️ Bump version: in goodwe_controller/config.yaml for every change. Supervisor keys the built image by that version, so without a bump it silently reuses the old image and your fix appears not to work — on your bench and on every client's machine.

Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.

Read this first

The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.

Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:

  1. ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
  2. Wind-down before firmware updates — 0 W written before the update starts.
  3. RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.

Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md §10 signed.

Development

The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:

cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py

Both must pass before shipping any change. They are not unit-test theatre — each assertion corresponds to a rule whose absence produced an observed failure on real hardware, and the comments in control.py say which.

Compatibility

Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:

tag platform verdict
ESU EMU ESA BPS BPU EMJ IJL 105 — ES/EM/BP, AA55-era meter bus supported
SPB SPN 745 — SBP G2 (GW…-SBP-20) no
ESN ESC 745 — ES G2 (GW…-ES-20) no
ETU EHU BTU … 205/745/753 — ET/EH/BT hybrids no
SDT DST MSU NSU … PV-only inverters — no battery to control no

A "-20" or "G2" suffix means a different platform with a different meter protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which is also what Home Assistant's own integration uses to pick a protocol.

  • GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
  • The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.