SAFETY-81 review: 10 s hold, ERROR line per episode, more scenarios
- The alarm must hold for peakguard.ALARM_HOLD_S (10 s) on the projection's
  clock. A load that tops cap + battery for ~5 s every 30 s alarmed at every
  quarter start while the quarter landed under the aim (sine4500_fast).
- A cycle with no battery reading leaves the hold alone.
- Notified once per quarter, but the ERROR line is written per episode.
- New sim scenarios (sine4500_fast, twice7000, step6500_gap) with 5a4cdc2
  digests; control still byte-identical. Unit checks for export and the
  hold across a missing reading. test_peakguard's saturated fixture moves
  the hold start back instead of waiting it out.
- DECISIONS and DOCS updated: costs of the hold, tolerance reasoning, the
  double count in control left to a follow-up.