glenn schrooyenandClaude Opus 5 4e66583a52 SAFETY-03 review fixes: both clamp stages always run, and two checks that could not fail
1. BEHAVIOURAL, and a regression this PR introduced. clamp_to_rating() returned
early from the max_w stage, so the device bound was applied only when the rating
bound had NOT fired - the bigger the overshoot, the less the guard did. At max_w
5000 against a +-4000 device, +9999 emitted +5000 W, outside the device range,
while +4500 was correctly held to +4000. It undid the pre-PR guarantee "never
send a value the device will reject outright" and undercut this module's own
case for max_w-not-min(), which rests on that stage catching a validation that
did not run. Both stages now always run; the result names both bounds when both
bite (max_w+device). Asserted over a 492-point sweep, because the defect was
invisible to any single-value check sitting inside one stage.

2. The hysteresis check issued range(CLEAR_CYCLES - 1) clean cycles, which at
CLEAR_CYCLES = 1 issues zero, passes, and prints "0 clean cycles do NOT clear
it" - green for the chatter setting the constant exists to prevent. Now: ONE
clean cycle must not clear the alarm, a literal that does not move with the
constant, and the de-assert count is measured by looping until it clears.

3. The re-assert check stimulated at REASSERT_S + 9, green for any value
including 3600 - the hour of silence the module promises not to produce. Now
stated in wall-clock terms: a loop pinned across the 900 s capacity-tariff
quarter must speak at least 5 times and on no more than 20% of cycles. Pinned in
both directions.

Red confirmed for each: the restored early return (3 checks), CLEAR_CYCLES = 1
(1), REASSERT_S = 3600 (1) and REASSERT_S = 0 (3).

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC