glenn schrooyenandClaude Opus 5 9aed43990b SAFETY-02: a loop can be fresh, tracking and inside its rating and still push the wrong way
The stale-input watchdog asks whether the meter is still talking. The saturation
freeze asks whether the inverter can follow. The output clamp asks whether the
number is too big. A loop can pass all three while charging the battery out of
the grid, because the only thing wrong is the sign.

On 2026-08-20 a commercial controller did exactly that four times in one day,
for up to 77 minutes at a stretch, reaching a commanded -14 768 W against a
±5000 W inverter. app/watchdog.py compares the emitted setpoint against the
authoritative P1 figure and, when they oppose each other with both over 300 W
for 180 s continuously, files a failsafe SET claim at P_SAFETY, commands 0 W and
latches there until an operator starts control again.

Validated against that day rather than against an argument: sim/replay_sign.py
in the infra repo drives this module over the committed captures of both
2026-08-20 and the healthy 2026-08-23 and reaches 18 trips on the fault day -
every one inside a window NOTES.md §4.7 accounts for - and 0 on the healthy day.
The four episodes do share one signature: 0.3 / 0.9 / 10.5 / 0.0 % sign
agreement inside them against 92.9 % healthy.

Three decisions the ticket could not make:

- It is DISARMED whenever the grid-following loop is not what is driving. Sign
  agreement is a property of a loop that follows the meter, and a maintenance
  grid charge opposes the meter by design - 2500 W of charge into a house
  drawing 500 W is +3000 W on the meter against a -2500 W command, for hours.
  The gate tests the emitted number, not the winning claim's name, because a
  limit claim can let the loop "win" and still replace its value.
- The trip LATCHES. Commanding 0 W removes the command side of the comparison,
  so the disagreement always clears the moment the trip works.
- sign_disagree_w at or above max_w is refused at startup. The arbiter never
  lets a command exceed max_w, so such a threshold leaves the watchdog incapable
  of firing while the status page still reports it armed.

What it does not catch, said out loud: an inverter that ACTS opposite to its
command moves the meter further the same way, leaving command and meter in
agreement. That is the saturation freeze's job.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-28 21:51:35 +02:00

200 lines
7.1 KiB
YAML

name: GoodWe RS485 Controller
version: "0.5.0"
slug: goodwe_controller
description: >-
Drives a GoodWe ES/BP battery inverter over RS485 by emulating its smart
meter, holding net grid exchange at zero and running a monthly battery
maintenance cycle.
url: https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
arch:
- aarch64
- amd64
- armv7
init: false
startup: application
boot: auto
# Needed to read the meter and to write the ESPHome setpoint number.
homeassistant_api: true
hassio_api: true
# Own diagnostics/operations UI inside HA. This is what a field tech and a
# remote supporter both look at, so it is not optional.
ingress: true
ingress_port: 8099
panel_icon: mdi:battery-sync
panel_title: GoodWe
# Optional: publish status entities by MQTT discovery. `want` rather than
# `need` - the add-on runs fine with no broker, it just publishes nothing.
services:
- mqtt:want
options:
# --- sources (required) ---------------------------------------------------
meter_entity: sensor.p1_meter_active_power
meter_invert: false
soc_entity: ""
batt_entity: ""
batt_invert: false
setpoint_entity: ""
# --- P1 meter ingestion (specs §5.2 / §14 `meter:`) -------------------------
# `off` keeps the original single meter_entity path above, so an existing
# install is untouched until it opts in. ha_dsmr subscribes to the DSMR
# integration's entities over the HA WebSocket; mqtt_p1 reads the topic below;
# ha_signed reads ONE signed HA entity (+ import / - export), which is what a
# HomeWizard P1 publishes and what ha_dsmr cannot consume.
# homewizard_local skips Home Assistant entirely and polls the meter's own
# local API. ⚠️ It is the ONLY mode whose sensor.p1_sample_age_s measures when
# the meter REPORTED rather than when the value last CHANGED - HA emits
# nothing at all for a repeated reading - so it is the only mode a firmware
# watchdog may threshold. See DOCS.md.
meter_source: "off"
meter_phases: 1
meter_max_age_s: 30
meter_mqtt_topic: ""
# homewizard_local only. The meter's own address, `host` or `host:port`.
p1_host: ""
# homewizard_local only. Seconds between polls. Must be well under
# meter_max_age_s - the age is never fresher than this interval - and there is
# nothing to gain below the meter's own ~5.0 s update rate (NOTES.md:640).
meter_poll_s: 5
# The two UNSIGNED Belgian registers. The EMS derives net power from them
# (import - export); do NOT point these at a signed template sensor.
p1_import_entity: ""
p1_export_entity: ""
# Optional, in L1..L3 order. Required for the capacity-tariff peak on a
# three-phase connection; the list length must equal meter_phases.
p1_phase_import_entities: []
p1_phase_export_entities: []
# ha_signed only. ONE signed net-power sensor: positive = import from the
# grid, negative = export to it. Do NOT split it into two template sensors -
# the split is done in the add-on (p1.split_signed) precisely so the sign
# convention is tested rather than living in unreviewed YAML.
p1_net_entity: ""
# Optional, in L1..L3 order, each one signed the same way. Same role as
# p1_phase_import_entities: the capacity-tariff peak on a three-phase
# connection. The list length must equal meter_phases.
p1_phase_net_entities: []
# --- control ---------------------------------------------------------------
max_w: 2000
gain: 0.6
slew_w: 1000
deadband_w: 15
target_grid_w: -10
step_w: 10
saturation_w: 500
saturation_cycles: 3
integrator_max_w: 0
heartbeat_s: 10
stale_input_s: 15
cycle_floor_s: 15
auto_start: false
# --- SAFETY-02 sign-disagreement watchdog ----------------------------------
# Trips when the emitted setpoint and the P1 net figure point OPPOSITE ways,
# both over sign_disagree_w, continuously for sign_disagree_s. Action: 0 W and
# a failsafe that latches until an operator starts control again.
#
# Both defaults are measured, not chosen. On the captured healthy day
# (2026-08-23) the longest legitimate opposed run - a load step the loop has
# not caught up with - is 30 s, and sign agreement over the gated samples is
# 92.9 %. On the captured fault day (2026-08-20) the four episodes run 0.0-11 %
# agreement with opposed runs up to 1752 s. 300 W / 180 s sits in the middle of
# a very wide gap: at 60 s the healthy day still trips nothing, at 300 s the
# fault day still trips 13 times. There is no reason to move either number
# without a capture that says so. They are options because the AC says
# thresholds are defaults rather than constants - not because they are knobs
# anyone is expected to turn.
#
# ⚠️ sign_disagree_w must stay BELOW max_w or the watchdog can never fire (the
# arbiter bounds the command to +-max_w). validate.py refuses that config.
sign_disagree_w: 300
sign_disagree_s: 180
# --- maintenance -----------------------------------------------------------
maintenance_enabled: false
maintenance_interval_days: 28
maintenance_start_hour: 10
maintenance_discharge_w: 2500
maintenance_charge_w: 2500
maintenance_soc_floor: 11
maintenance_soc_target: 99
maintenance_hold_min: 120
# --- tariff / capacity tariff (all optional) ------------------------------
peak_forecast_entity: ""
peak_cap_w: 3500
price_now_entity: ""
price_avg_entity: ""
# --- site ------------------------------------------------------------------
estop_fitted: false
log_level: info
schema:
meter_entity: str
meter_invert: bool
soc_entity: str
batt_entity: str
batt_invert: bool
setpoint_entity: str
meter_source: list(off|ha_dsmr|mqtt_p1|ha_signed|homewizard_local)
# ⚠️ 2 is accepted by this range but is not a real Belgian connection. A
# telegram whose phase count disagrees is rejected at ingest and logged, so a
# mis-set 2 shows up immediately as "0 telegrams accepted" rather than as a
# quietly wrong number.
meter_phases: int(1,3)
meter_max_age_s: int(5,300)
meter_poll_s: int(1,60)
meter_mqtt_topic: str?
p1_host: str?
p1_import_entity: str?
p1_export_entity: str?
p1_phase_import_entities:
- str
p1_phase_export_entities:
- str
p1_net_entity: str?
p1_phase_net_entities:
- str
max_w: int(100,5000)
gain: float(0.05,1.0)
slew_w: int(50,5000)
deadband_w: int(0,500)
target_grid_w: float(-200,200)
step_w: int(1,100)
saturation_w: int(100,2000)
saturation_cycles: int(1,10)
integrator_max_w: int(0,15000)
heartbeat_s: int(2,25)
stale_input_s: int(5,120)
cycle_floor_s: int(5,60)
auto_start: bool
# No "off" value, deliberately: this is a P0 safety check and the schema is
# not the place to make disarming it a supported configuration.
sign_disagree_w: int(50,5000)
sign_disagree_s: int(30,1800)
maintenance_enabled: bool
maintenance_interval_days: int(1,90)
maintenance_start_hour: int(0,23)
maintenance_discharge_w: int(500,5000)
maintenance_charge_w: int(500,5000)
maintenance_soc_floor: int(5,30)
maintenance_soc_target: int(50,100)
maintenance_hold_min: int(5,480)
peak_forecast_entity: str?
peak_cap_w: int(500,15000)
price_now_entity: str?
price_avg_entity: str?
estop_fitted: bool
log_level: list(trace|debug|info|warning|error)