SAFETY-31: the grid is 42, not 90, and the wrong number was in the failure text
Review reproduced every figure in both PRs except one, and rejected on it.

⚠️ "0 of 90 GAINS x SPLITS combinations produce opposing shares" - the SUBSTANCE
is right and review re-measured it, but the DENOMINATOR is invented. sitesim.py
declares GAINS with 7 entries and SPLITS with 6: the grid is 42. 90 is not even
divisible by 7, so no reading of "GAINS x SPLITS" reaches it. It is almost
certainly TEST-20`s RUN count (84 + 6), which is a different quantity that
happened to be nearby.

⚠️ AND THE WORST COPY OF IT WAS INSIDE THE `PRECONDITION FAILED` TEXT, so the
next engineer to see this scenario go red would have been handed an
unreproducible measurement as their diagnosis - the exact defect class this
campaign exists to correct, in the failure path where it does the most harm.

Corrected in all seven places. At the failure-text site the denominator is now
`len(GAINS) * len(SPLITS)`, computed rather than typed, so it cannot drift from
the grid again - the same fix test_translations.py already took.

Also N3: a missing blank line was going to render the S3 and M19 paragraphs as
one in DECISIONS.

Re-run after the change: `inject.py two_master_circulation` PASS in 35 s, norig,
no rig lock taken. Add-on suite 26 files, all pass.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-07 20:13:01 +02:00

435 lines
26 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# SAFETY-31 — what "acted on" means for circulating power, and what it cannot mean
**Status: DECIDED 2026-09-04.** The trip **stops the site**: a `SET 0 W` claim
at `P_SAFETY` on the **site** actuator, latched, persisted, and re-announced
after a restart. This document records why that is an action rather than
theatre, given that [[HW-01]] established a wedged inverter cannot be commanded
at all — and it records the numbers the threshold and the window were read off,
because "establish the window from the rig, do not pick a round number" is an
acceptance criterion and a number without its measurement is a guess.
Filed with SAFETY-31. Card `6a99e0022b6a6c8ca15dbe3e`.
---
## 0. The two halves, and which one this card built
Half of this card was already shipped, and it is not the half below.
| | **ALLOC-01, AC 7 — the COMMAND half** | **SAFETY-31 — the MEASUREMENT half** |
|---|---|---|
| what it is | `allocator.REFUSE_SIGN` | `circulation.circulating_w()` + `CirculationWatchdog` |
| what it sees | the shares the allocator is about to hand out | each inverter's **own measured power** (`Inverter.batt`, register 0x0518) |
| what it does | **refuses** the allocation, names both units, returns no shares | **stops the site**, latches, alarms durably |
| what it covers | circulating power the allocator would have **commanded** | circulating power **nobody commanded** |
| graded by | `test_alloc.py` part 6 | `test_watchdog.py`, the SAFETY-31 section |
**They are complements, not duplicates.** The gate refuses an allocation before
it is written and cannot see one millisecond past that. This card reads the
hardware and does not care what was written. Neither replaces the other, and
**a sensor built on the allocation record would collapse the second into the
first and detect nothing** — see §2.
## 1. What "acted on" means
> **The trip files `Claim.set("circulation", P_SAFETY, 0.0)` on the SITE
> actuator. Every inverter is commanded 0 W and held there until an operator
> starts control again.**
### The objection, which is correct
[[HW-01]] is on the record: on 2026-09-02 the comms subsystem failed and the
power stage went on executing its last instruction for **6 h 25 m**, through
every command this add-on sent it. If the cause of the circulation is a unit
that has stopped listening, **a command is not a remedy**, and shipping one as
though it were is theatre.
### The answer
**A circulating loop needs two participants.** In every cause on this card's
list — a unit ignoring its share, a unit lagging it, a stale share still being
executed, a maintenance or [[SAFETY-25]] pin holding one unit while the loop
drives the other, or HW-01's wedged power stage — **exactly one participant is
the unit that stopped listening, and the other one is this controller**,
faithfully commanding the sibling to a share computed to sum with a number the
wedged unit is not actually producing.
Stopping the commanding half does two things a notification cannot:
1. **It halves the loop.** The unit that *is* still listening stops being driven
into the one that is not. That is real energy and real cycles off a real
pack, and it needs no cooperation from the wedged unit to take effect.
2. **It makes the residue visible — and this is the more important half.**
Circulating power hides *because it nets to zero at the meter*. With this
controller's contribution removed, whatever the wedged unit is still doing
stops being cancelled and appears at P1 as a plain net flow, where
SAFETY-02's sign watchdog, the peak guard and the capacity tariff can all see
it. **The fault stops being invisible.**
Measured on the [[TEST-19]] rig, and this is the number that makes the case:
in the card's own scenario — A at −3000 W, B at +3000 W, house load 0 W — the
meter reads **+0 W** and the shipped `SignWatchdog`'s predicate is **false on
every one of 30 cycles**, because it gates on `abs(grid_w) > 300` and the gate
never opens.
### What it does not do, said plainly
**It does not stop the wedged inverter. Nothing this add-on can send will.** If
the loop persists at the meter after this trip, the remaining actuator is a
human at the isolator, and the notification says so in those words.
### Why the claim is SITE-scoped
`arbiter.CLAIM_SCOPE` classifies `circulation` as `SCOPE_SITE`, beside `loop`,
`peak`, `arbitrage` and `safety`. The neighbouring `failsafe` entry looks like
it and is not: SAFETY-02 has site-wide *evidence* and a per-unit *conclusion*,
because it compares the meter against the command **this controller put on one
actuator**.
Circulating power has no such conclusion available. It is
`Σ|Bᵢ| − |ΣBᵢ|` — defined over the whole roster, **identically zero for any one
unit** — and there is no fact of the matter about which of two opposing
inverters is the offender: *a unit ignoring its share* and *a sibling faithfully
executing a share computed to sum with it* produce **identical readings**.
Filing this per-unit would require inventing an attribution the measurement
cannot support, and would park one inverter while the other went on feeding the
loop — quite possibly parking the only one still listening.
The same argument is why the latch is **flat** in the store (`circ_tripped`,
`circ_reason`) and not namespaced like SAFETY-02's. One site, one latch.
## 2. Why the sensor is MEASURED, and why the cheap version is worthless
The obvious cheap version computes the same formula over `Allocation.shares`.
It would be simpler, would never be `None`, and would be **worth nothing**, for
two independent reasons:
1. **It cannot fire.** ALLOC-01's sign-coherence gate already refuses any
allocation whose shares carry two signs. A record-derived sensor is therefore
a sensor over a set that is **guaranteed sign-coherent**. It reads zero *by
construction*, forever.
2. **It is [[MUTATION.md]]'s third failure mode.** It could only ever confirm
that the allocator agrees with itself — a check whose data cannot reach the
failure it names.
Verified rather than argued. On the rig, with inverter B wedged on a stale
discharge while PV drives the site to charge:
```
S = -2500 W shares a = -1250 W b = -1250 W <- record: ok, ONE sign, sums to S
MEASURED A = -1250 W B = +1000 W <- hardware
sensor over the RECORD : 0 W
sensor over MEASURED power : 2000 W -> trips at 190 s
```
And the card's own headline scenario, driven on the same rig — A at −3000 W,
B at +3000 W, house load 0 W:
```
METER (P1) : +0 W <- the site looks IDLE
sensor over MEASURED power : 6000 W -> trips at 100 s
SAFETY-02 SignWatchdog : predicate false on 30 of 30 cycles
```
The same pair is asserted in `test_watchdog.py` **with the precondition written
as its own check and printed**, per MUTATION.md's rule, and mutation **M10**
(the property rewritten to read `self.allocation.shares`) takes it **red**.
## 3. The numbers, and where they come from
Both were read off a curve produced on `admin/goodwe`'s `sim/` two-master rig,
used read-only: the add-on's own `compute()`, its own `allocator.plan()` and its
own `circulating_w()`, driving `plantsim.Plant` through the firmware's own
encoder, with the sensor input taken from each unit's holding register 0x0518.
**924 closed-loop runs in which nothing is faulty** — every unit executes the
share it was given — over both families of stimulus that can produce legitimate
opposition (7 reversals × 5 write staggers, and 7 flap periods × 4 amplitudes),
each swept across the **whole range `config.yaml` accepts** for the two settings
that decide how fast the site can turn around: `gain` `float(0.05,1.0)` and
`slew_w` `int(50,5000)`.
### ⚠️ THE HARNESS BEHIND EVERY FIGURE ABOVE IS NOT COMMITTED, AND UNTIL 2026-09-07 THAT MADE THEM UNCHECKABLE
**Read this before quoting any number in this section.** The paragraph below
said the campaign harness "is not committed here" and treated that as a
packaging detail. It is not: a figure produced by a script that exists in
nobody's tree cannot be re-run, cannot be reviewed, and cannot be defended when
it is contradicted. It has now been contradicted twice.
| sweep | worst peak | worst continuous | trips |
|---|---:|---:|---:|
| the 924-run campaign below — **harness uncommitted** | 1700 W | 505.0 s at 100 W; 5.0 s above 700 W | 0 / 924 |
| independent reviewer sweep, 2026-09-07, 48 honest reversals | **2750 W** | **15.0 s above 700 W** | 0 / 48 |
| `admin/goodwe` `two_master_circulation`, 840 runs — **committed** | 1048 W | 10.0 s at 100 W; 5.0 s above 700 W | **0 / 840** |
**This is not proof that anything was fabricated, and it should not be reported
as one.** The three swept different grids. What the third one adds is a
measurement of *why* the spread is that wide — on one grid, changing nothing but
the model:
| plant / stagger | worst legitimate peak |
|---|---:|
| modelled plant (lag 10 s, ramp 800 W/s), staggers up to a whole cycle | 1048 W |
| `INSTANT` (lag 0, unbounded ramp), staggers up to a whole cycle | 2250 W |
| `INSTANT`, staggers strictly under a whole cycle | **0 W** |
A factor of 2.1×, and a factor of infinity, between three defensible
descriptions of the same rig. **The plant model and the write-stagger set are
terms of the number**, and a worst case quoted without them is not a
measurement. That is enough to explain the whole spread above without anybody
having invented anything — and it is exactly what cannot be established when the
instrument is missing.
**What survives, and what does not.**
* **The window argument survives, and is now committed.** The claim that
decides `circulation_hold_s: 75` is *"the worst continuous legitimate episode
above 700 W is about one control cycle"*. All three sweeps agree on the shape
of that (5.0 s, 15.0 s, 5.0 s — one to three cycles against a fifteen-cycle
window), and **all three trip zero times**. `two_master_circulation` re-runs
it on every pull request in `admin/goodwe`.
* **The threshold curve does NOT survive as stated.** `505.0 s at 100 W` is the
number the "knee at 400 W" argument for `circulation_w: 700` rests on, and the
committed sweep measures **10.0 s** at 100 W on its grid — 50× smaller. The
curve still *falls* with the threshold (126 of 840 runs cross 100 W against 1
that crosses 700 W), so the knee is real in direction; its depth is not
established by anything anybody can run. **Do not quote 505.0 s.**
* **Nothing about the guard is compromised.** 0 trips in 924 + 48 + 840
non-faulty runs, from three independent grids.
**What would settle it:** the original harness, committed. Until then the
committed sweep is the only figure in this section anybody can check, and it is
labelled as its own grid's rather than as a reproduction.
### Reproducing it
⚠️ **THE COMMITTED VERSION IS `admin/goodwe`'s `sim/inject.py
two_master_circulation`** (`sim/sitesim.py:circulation_findings`, runnable on its
own as `python3 sim/sitesim.py --circulation`, `norig`, ~36 s, graded by
`checks.yml` on every pull request there). It produces the fault with
`plantsim.Inverter.wedge()` — a unit answering its bus and no longer steering its
power stage, which is HW-01 — and sweeps the legitimate family with the
serialised write path staggered up to a whole control cycle. The paragraph below
describes the ORIGINAL campaign, which is the one that is not committed.
The rig lives in `admin/goodwe` (`sim/`) and was used **read-only**; the harness
is not committed here because it imports that repo's `plantsim`/`frame_check`,
which are not present in this one or in CI. What it does is small enough to
restate: build `Site([Inverter.from_spec("A", INVERTER_A),
Inverter.from_spec("B", INVERTER_B)])`, close the loop with the add-on's own
`compute()` and `allocator.plan()`, put each share on its unit's wire through
`Inverter.command()` (which goes out through the firmware's real encoder), and
read the sensor from `inv.reg(0x0518)` — **the same register the live add-on's
`batt_entity` binds**, so the input is the one the shipped code gets. Point it
at a checkout with `GOODWE_ADDON_REPO`. ⚠️ MUTATION.md's note applies: those
harnesses write `__pycache__` into **both** trees, so purge both by hand before
grading a mutation through one.
Every figure below was re-run against the final shipped `CirculationConfig`
(`min_w=700`, `hold_s=75`) rather than against the draft values they were first
measured at.
### Worst CONTINUOUS legitimate opposition, by threshold
| threshold | worst continuous | runs that ever cross it |
|---:|---:|---:|
| 100 W | **505.0 s** | 281 / 924 |
| 200 W | 445.0 s | 174 / 924 |
| 250 W | 40.0 s | 132 / 924 |
| 300 W | 10.0 s | 115 / 924 |
| **400 W** | **5.0 s** | 74 / 924 |
| 700 W | 5.0 s | 33 / 924 |
| 1000 W | 5.0 s | 16 / 924 |
| 1700 W | 0.0 s | 0 / 924 |
****With the shipped `min_w=700 W` and `hold_s=75 s`, 0 of those 924 runs trip.**
The knee is at 400 W and it is sharp.** Below ~250 W a flapping load holds the
sensor above the threshold for *minutes* at a time, and no window shorter than
the 900 s billing quarter could tell that from a fault. At 400 W and above the
worst legitimate episode collapses to **5.0 s — one control cycle — and stays
there**. The worst peak on any legitimate run is **1700 W**.
That 5.0 s is the serialised write path doing exactly what it should: on a
reversing cycle inverter B's new number lands up to a whole control cycle after
A's, both then slew through zero at 800 W/s behind a 10 s lag, and **between the
two zero crossings they genuinely oppose**. Nothing is wrong. A guard that
tripped on it would be the fourth false-alarm generator of the week, and this
project's doctrine on crying wolf is explicit ([[SAFETY-15]], [[SAFETY-19]]).
### `circulation_w: 700` — schema floor `400`
`700` is **1.75× the measured knee**. The headroom is bought for one named
reason: **inverter B does not physically exist.** Its ramp and lag in the rig
are inverter A's, *copied*, carrying `measured=False`; [[SPIKE-04]] measures the
real ones. A slower or faster second unit moves the transient's shape, and the
margin above the knee is what absorbs that without re-opening this card.
**Revisit when SPIKE-04 lands, not before.**
The **schema floor is the knee itself**, 400 W, so a legally configured install
cannot land in the 445–505 s regime — ⚠️ and those two figures are from the
uncommitted campaign; the committed sweep measures 10.0 s at 100 W on its own
grid. See the disclosure at the head of this section. The floor is still the
right shape (fewer runs cross a higher threshold, measured 126/840 at 100 W
against 1/840 at 700 W); its DEPTH is not established by anything re-runnable. What the threshold costs: a circulating
loop smaller than 350 W per unit is not reported, which is deliberate — at that
scale the round-trip loss is a few watts.
### `circulation_hold_s: 75` — schema range `30..900`
Three bounds, and the value clears all three:
* **lower, from the rig — 5.0 s.** The worst continuous legitimate opposition
above 700 W across all 924 runs.
* **lower, from the firmware — 30 s (`inverter.LINK_STALE_S`).** A unit still
executing a stale share for less than the firmware's own veto window is a
*link* fault, and the add-on already answers it: liveness drops the unit and
the survivors carry its share, with the record saying so. Firing inside that
window would raise a second, louder alarm about a state already being handled.
* **upper, from the bill — 900 s**, the quarter that sets the capacity tariff.
**75 s** is fifteen control cycles: **15× the worst legitimate episode**, **2.5×
the firmware veto**, and **12× inside the quarter**. It is deliberately not 60
or 120 — a round number here would be a guess wearing a measurement's clothes,
and a check in `test_watchdog.py` asserts it is none of the values a guess
lands on.
## 4. Why the window cannot be defeated the way SAFETY-02's was
`allocator.py` records the measurement that makes SAFETY-02 blind to the
broadcast fight: the sign disagreement **flips on alternate ticks**, so
`disagree_since` is cleared between every pair of them and the 180 s hold never
accumulates.
Circulating power cannot do that. It is a **magnitude**, non-negative by
construction, and a sustained loop holds it high on *every* cycle rather than
every other one. An oscillation that genuinely alternated between opposing and
agreeing is not a circulating loop and should not be reported as one — which is
exactly the flapping-load case in §3, and it is why the window clears.
## 5. SAFETY-34: the latch is not the alarm
`persistent_notification` is **in memory**. Home Assistant restarts and the card
is gone while the fault runs on — which is precisely how the 2026-09-02 outage
went unseen for **6 h 25 m with the detector correct throughout**.
So the durable half and the visible half are joined, and the join is
`Controller._circ_announced`: a **per-process** flag, deliberately *not*
persisted. The latch in `/data/state.json` says *"this site is tripped"*; the
flag says *"this process has put that in front of a human"*. A restart clears
the flag and keeps the latch, so **the notification is re-raised on the first
cycle after every start** — which is the first cycle after a Home Assistant
restart, because the add-on restarts with it.
**One code path serves both** the fresh trip and the restart, on purpose: two
paths would be two chances for the restart one to rot unnoticed, and the restart
one is the case nobody exercises by hand. Mutations **M13** (flag initialised
from the latch) and **M18** (the call removed) both take it red.
## 6. Mutation ledger
Every run on a **freshly copied tree with no `__pycache__`, mounted `:ro`** into
the CI image — the structural immunity MUTATION.md records for CI and for
SAFETY-25 — so no stale `.pyc` could exist to be read. Byte deltas recorded;
**three are `+0 B`, the risky delta, and are marked**.
| # | file | mutation | Δ | result |
|---|---|---|---|---|
| M1 | `circulation.py` | `sum(abs(v))` → `sum(v)` in the sensor | −5 B | **RED** — the 6000 W, 2000 W and three-unit checks |
| M2 | `circulation.py` | N≤1 returns `None` instead of `0.0` | +1 B | **RED** — AC 5's nine-reading sweep |
| M3 | `circulation.py` | a missing reading at N≥2 returns `0.0` | −1 B | **RED** — "health from an absence" |
| M4 | `circulation.py` | drop `max(0.0, ...)` | — | **EQUIVALENT, not run as a claim.** For a same-sign roster the two sums accumulate the same magnitudes in the same order and are bit-identical; 700 000 random rosters produced no negative. Argued at the line and in the check's own text. |
| M5 | `circulation.py` | threshold `<=` → `<` | −1 B | **RED** — "exactly 700 W forever does not trip" |
| M6 | `circulation.py` | window `<` → `<=` | +1 B | **RED** — "trips at 75 s, not before" |
| M7 | `circulation.py` | the window removed entirely | −85 B | **RED** — both slew-transient checks |
| M8 | `circulation.py` | `None` no longer clears the window | +34 B | **RED** — the stale-reading gap check |
| M9 | `circulation.py` | the latch removed | −123 B | **RED** — "restored as tripped stays tripped" |
| **M10** | `main.py` | **the sensor derived from `self.allocation.shares`** | +60 B | **RED** — AC 2's headline check. This is the card. |
| M11 | `main.py` | the `circulation` claim never filed | −235 B | **RED** — `test_watchdog.py` **and** `test_peakguard.py` 10f/10g |
| M12 | `main.py` | the latch not persisted to the store | −112 B | **RED** — all three durability checks |
| M13 | `main.py` | `_circ_announced` initialised from the latch | +21 B | **RED** — SAFETY-34's re-raise |
| M14 | `main.py` | the operator clear leaves `_circ_announced` set | −45 B | **RED** — "the next trip would raise nothing" |
| M15 | `arbiter.py` | `circulation` scoped `SCOPE_UNIT` | **+0 B** | **RED** — `test_arbiter.py` ×3 and `test_peakguard.py` ×3 |
| M16 | `config.yaml` | schema floor `400` → `100` | **+0 B** | **RED** — the measured-knee check |
| M17 | `circulation.py` | default `700` → `500` | **+0 B** | **RED** — the CFG-03 pin and the not-a-round-number check |
| M18 | `main.py` | `await self.check_circulating()` removed | −39 B | **RED** — all four notification checks |
| M19 | `main.py` | publish `round(x or 0.0)` instead of `None` | −68 B | **survivor on the first battery — GAP CLOSED**, then RED |
| **M20** | `main.py` | **`pos, neg = opposing(...)` → `([], [])`** — the attribution clause deleted from the alarm | −102 B | **SURVIVED ALL 26 FILES on the shipped battery — GAP CLOSED**, then RED on §6a |
| M21 | `main.py` | `pos` and `neg` exchanged — the alarm names both packs, both the wrong way round | **+0 B** | **RED** — §6a ×3 (the mirrored run, and "only its own sentence") |
| M22 | `main.py` | `opposing(..., min_w=cfg.min_w / 2.0)` → `min_w=0.0` | −25 B | **RED** — §6a's resting-pack check |
**And four in `admin/goodwe`**, graded through `python3 sim/sitesim.py
--circulation` rather than through the injector — deliberately, because
`inject.py` is the file that takes the rig lock, and "run the injector to grade a
mutation" is not a sentence anybody should have to type. Byte deltas over
`plantsim.py` + `sitesim.py` together.
| # | file | mutation | Δ | result |
|---|---|---|---|---|
| S1 | `plantsim.py` | `wedge()` no longer stops the latch reaching the power stage | −20 B | **RED** — the opposing-signs precondition **and** "the watchdog did not trip" |
| S2 | `sitesim.py` | the sensor computed over the **allocation record** instead of register 0x0518 | **+0 B** | **RED** ×3 — this is M10 restated on the rig |
| S3 | `sitesim.py` | the campaign run on `plant=INSTANT` | −51 B | **RED** — the plant is a *term* of the figures; it was a SURVIVOR until that check was added, and finding out why produced §3's 1048/2250/0 W table |
| S4 | `sitesim.py` | the write stagger removed from the legitimate campaign | −19 B | **RED** — "the legitimate campaign produced no opposition at all" |
**S3 is recorded as a survivor because it was one, and it is the most useful
result in this table.** The scenario first shipped with a vacuity check whose
text claimed `plant=INSTANT` would make the sweep measure 0 W. S3 was run and
**passed**: `INSTANT` with a stagger of exactly one control cycle samples the
plant before the second unit has stepped, so it produces opposition anyway — and
a *larger* worst peak (2250 W) than the modelled plant does (1048 W). The claim
in the check's own text was wrong. It was corrected against the measurement, the
plant was pinned as an explicit term, and S3 is red now for a stated reason
rather than by accident. §3's spread table is that measurement.
**M19 is recorded as a survivor because it was one.** The first battery found no
check grading what `publish()` does when a per-unit reading is missing, so
turning *"I do not know"* into *"0 W"* on the one surface an operator actually
watches went unnoticed — the sensor's own `None` rule, defeated one layer out.
A check was added and the mutation re-run; it is red now. The run that found it
was purged, so it is a result and not an artefact.
**M20 IS RECORDED AS A SURVIVOR BECAUSE IT WAS ONE, AND IT IS THE MORE
UNCOMFORTABLE OF THE TWO.** The commit message for this card claimed *"18
mutations, all RED"*, and M1–M19 above have no entry for the notification's
attribution clause. Verification on 2026-09-07 ran it and it **survived the
whole 26-file suite**: the alarm still fires, still stops the site, still says
the meter cannot see it — and no longer says *which two packs* or *which way
round*. `circulation.py`'s own docstring calls that sentence the first thing
somebody woken by this alarm needs and *"impossible to reconstruct from the
number alone"*.
It survived for one reason, and it is not reachability: **M18 (the whole call
removed) is red**, so `check_circulating()` is exercised. The three checks on
that notification asserted `METER CANNOT SEE`, `CONTROL HAS BEEN STOPPED` and
`isolator` — and **never an inverter name**. Nothing graded the attribution.
`test_watchdog.py` §6a closes it, and closes it on a fixture that can tell the
three failures apart. It runs a roster of **`["garage", "shed", "cellar"]`** —
operator names, none of them `UNIT_A`, for test_maintenance.py §11's reason:
on a fixture whose names are the module's own constants a check cannot tell the
roster from the constant. It runs the site **twice, mirrored**, so the sentence
is not symmetric and a swap (M21, `+0 B`) is a different red from a deletion.
And it carries a **third pack resting at 5 W**, so the floor that stops a pack
in standby being named as a participant in a 6 kW loop (M22) is graded too.
## 7. What this card does NOT close
* **Inverter B's ramp and lag are placeholders.** Every transient number in §3
was produced with inverter A's parameters copied onto B (`measured=False`).
SPIKE-04 measures the real ones and is the revisit trigger for the 1.75×
margin. **Do not present any figure here as a measurement of inverter B.**
* **A wedged inverter still cannot be stopped by this add-on.** §1 says so; the
notification says so; there is no software fix and this card does not pretend
to one. It *can* now be produced on demand: `plantsim.Inverter.wedge()`.
* **The depth of the threshold curve is not established by anything committed.**
§3's disclosure. The window is; the knee's magnitude is not.
* **A loop below ~350 W per unit is not reported.** Deliberate, §3.
* **The saturation freeze fires under a wedged unit and leaves a standing grid
error.** Observed on the rig while producing §2's numbers: with B wedged, the
loop's anti-windup test compares a site target against a measured site power
that cannot track it, freezes the integrator and leaves the meter parked at
−3750 W. Nothing alarms on that today — a freeze is an ordinary control action
by design. It is a real finding, it is **not** in scope here, and it wants a
card of its own.