SAFETY-47: what a shadow run can show, and the watts on its status row
Not a leak and not a write-path defect. Shadow mode's safety is intact -
the substitution, the re-seed, the authorisation gate and the clamp are
untouched. What was wrong is what three merged documents SAY a shadow run
can show you, and a number on the status row that can be 6.61x what a live
controller would command.

SHADOW MODE CANNOT SURFACE A CLOSED-LOOP DEFECT, AND THE DOCUMENTS NOW SAY
SO. The battery is held at 0 W and the carried command is re-seeded to it,
so every measured input - the meter, the billed-quarter accumulator behind
it, the battery power, the SoC - describes a plant that did not respond. A
closed-loop defect is one whose stimulus IS that response. This is the same
property that makes shadow mode safe, so it is not a gap to close later:
the closed-loop answer comes from the closed-loop rig or from a live run.
SAFETY-10 §5 already conceded this for the grid-following loop. It was
never the loop leg's limitation; it is the general case.

THE "STRATEGIES ARE UNAFFECTED" EXEMPTION WAS TRUE UNTIL SAFETY-45 MERGED,
ONE COMMIT EARLIER. That card sizes the buy leg as min(asked, headroom)
with headroom = (900/remaining) x (ceiling - projected), and `projected`
reads the open quarter's accumulator - the meter - which is a function of
what the battery did earlier in that quarter. Measured on TEST-23 stage 3
at peak_cap_w 1500 / house 1200 / max_w 2000, one hour at 5 s:

  SAFETY-45's limit cycle  NOT visible. 28 onsets live vs 1; grid
                           -455.5..+3200.0 W vs flat at the 1200 W house;
                           guard engaged 410/720 cycles vs 0/720.
  SAFETY-46's SoC churn    NOT visible. The SoC moves 0.000000000 pp.
  TARIFF-14's wrong hour   VISIBLE, and it is the only one: which hour, at
                           what price, clearing what spread - identical on
                           720 of 720 charging cycles at a binding cap.

The exemption narrows to exactly what survives: WHICH hour a strategy picks
and WHY are unaffected; HOW HARD it trades is not. The peak guard's ceiling
and reasons are worth reading from a shadow run; its ENGAGEMENTS are not.

THE NUMBER IS CAVEATED, NOT RE-COMPUTED, AND THAT IS THE DECISION. The
arithmetic is not wrong - 900/remaining is correct for a meter genuinely
under the ceiling, and in shadow the meter genuinely is. It is the right
answer to a question nobody asked. Both surfaces now introduce the watts as
what would have been commanded ON THIS CYCLE, in every state, and carry
shadow.SIZED_FROM_METER whenever a measured billed quarter sized them.
Rejected, and recorded in the decision doc: re-computing it (the recorded
decision would no longer be the decision the shipped path reached, while the
arbiter, clamp, SAFETY-28 gate, log and MQTT all ran on the real one - a
second controller everywhere except the wire); recording nothing (blanks the
row exactly when arbitrage is trading, and the log's edge key is the watts);
and recording the unsized ask beside it (a second number, no warning, and at
the shipped 3500/2000 both figures read 2000 W).

"UPPER BOUND" AND NOT "SMALLER", AND THE DIFFERENCE WAS MEASURED. Charging
only adds offtake, so the shadow size is >= the live size with EQUALITY at
the start of every quarter. Pairwise over 3600 charging cycles in five
configurations: 0 below, 730 exactly equal. The first draft said "smaller",
which would have been false on every one of those 730.

AND THE PREDICATE IS NOT KEYED ON WHETHER THE TRADE WAS CAPPED. arbitrage's
own sentence says "SIZED BY THE CAPACITY-TARIFF GUARD" only when the
headroom came out below the ask - in a shadow run, the START of the quarter,
where the two runs agree to the float. By the end, 900/remaining has
multiplied the headroom past the ask, the trade is not capped, the sentence
is silent, and the record is at its most wrong. A caveat keyed on it would
be quietest exactly where it is needed loudest.

SAFETY-10 §6's COMMITTED EVIDENCE COULD NEVER HAVE FAILED, FOR TWO
INDEPENDENT REASONS, AND CLOSING EITHER ALONE CLOSES NOTHING. Its fixture is
peak_cap_w 15000 against a 350 W house, so the guard never engages and the
sizing is inert - the harness's own comment says so. AND every identity row
reads the FIRST charging sample, where at elapsed=0 the projection IS the
held level and the two runs agree to the float even at a cap that does bind.
Measured: widening the fixture alone leaves that comparison passing. That
second reason is a new shape for MUTATION.md's habit-4 list - an INDEX, not
a fixture - and it is recorded there as the twelfth instance. §6 is re-taken
at a binding cap across the whole run: 716 of 720 charging cycles differ,
headroom 300.0..54000.0 W in shadow against 299.9..307.8 W live, recorded
-2000.0 W against a live -302.4 W.

THE GRADER IS test_arbitrage.py PART 3d, beside SAFETY-45's own closed-loop
regression and built on the same s45_loop() harness, so the runs differ in
one argument. Three lines stand in for _write_unit()'s substitution and
_shadow_settle()'s record and re-seed, marked as a transcription;
test_clamp.py part 8 remains the check on the shipped placement. The section
carries its own precondition into every check: a mutation that stopped
either run trading made it raise on its first min(), kill the file and
report ZERO reds - FCST-06's shape, driven rather than imagined.

AND THE FIX'S OWN FIRST DRAFT CARRIED THE SAME DEFECT. Deleting the caveat
from the action-log line left all 29 files green, because the sentence was
an f-string inside _shadow_settle() and the only suite that drives it uses a
meter_source:off fixture where no arbitrage decision exists. It is
shadow.log_line() now, for the reason words() is a function.

14 mutations, no survivors; M13 and M14 are +0 B and were confirmed on disk
by sha256 with every run purged. M14's first form was aimed at the wrong
direction and correctly survived - min->max makes the shadow record larger,
which is still an upper bound. All 29 check files green.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-15 01:26:57 +02:00

407 lines
25 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# SAFETY-10 — shadow mode, and why "default-on" is not `true`
**Status:** decided and implemented on branch `SAFETY-10`.
⚠️ **AMENDED BY SAFETY-47, and three of the claims below were false when this
was merged.** §5's "the strategies are unaffected" exemption, §4's peak-guard
row and §6's evidence table are corrected in place and each correction is
marked. The amendments are marked rather than rewritten silently, because what
this card believed is part of why the defect shipped. See
`DECISIONS/SAFETY-47-what-a-shadow-run-can-show.md`.
**Card:** SAFETY-10 — *"Shadow mode (default-on, log-only decisions)"*.
**Nothing here reached the inverter.** No deployment, no `ha addons update`, no
contact with 192.168.2.158 or 192.168.2.221. Everything below was measured in
the CI image and on TEST-23 stage 3's closed-loop rig.
---
## 0. The four things a reader should take away
1. **"Default-on" is delivered as `auto`, not as `true`, and the difference is
an install that is regulating a real battery today.** The Supervisor
composes an add-on's options as *its defaults, overlaid with the stored user
options*, so a new key with a new default reaches **every existing install**
on the next update. A boolean `shadow_mode: true` would silently stop the
reference site. §1.
2. **Shadow mode WRITES. It writes 0 W, on the ordinary heartbeat, through the
ordinary single writer.** "Commands nothing" implemented as "stops writing"
would leave the inverter latched on whatever was standing — it has no meter
timeout — and would put the ESP32 into a tripped stale-input watchdog for
the whole run. §2.
3. **The sign watchdogs are inert, and that was the decision that had to be got
right.** Fed the shadow decision they would trip within `sign_disagree_s`
and **latch a trip that survives into live operation and a restart**. §4.
4. **The loop leg's shadow decision is one slew step, not a trajectory, and
that is a real limitation of this feature.** §5.
5. ⚠️ **SAFETY-47: and neither is anything else that depends on the plant
answering back. A shadow run cannot surface a closed-loop defect at all**,
by the same construction that makes it safe — the battery is held at 0 W, so
every measured input describes a plant that did not respond. Of the three
defects §"WHAT DEFECT THIS PREVENTS" was written for, exactly one —
TARIFF-14's wrong quarter-hour — is visible from a shadow run. §5, §6.
---
## 1. The default
### The literal reading, and what it costs
`config.yaml`'s `options:` block **is** the default. There is exactly one of it,
and HA's Supervisor resolves an add-on's effective options as
```
{**config.yaml options, **the stored user options}
```
A key that has never been stored therefore takes the file's value — on a fresh
install and on an install that has been running for months, identically. There
is **no mechanism in the add-on options system** by which one key can default
differently for the two. So the card's title, taken at face value, is:
> the next `ha addons update` stops the battery at the reference site, and the
> only symptom is a battery that has stopped doing anything.
That is strictly worse than every defect shadow mode exists to catch. It is
refused.
### What was shipped instead
`shadow_mode` is a three-valued `list(auto|on|off)` defaulting to `"auto"`:
| value | resolves to |
|---|---|
| `off` | live |
| `on` | shadow, always |
| `auto` | shadow **while control is stopped**; live once it is started |
`auto` reads `Controller.auto` — the persisted start/stop state, which a fresh
install takes from `auto_start` and which the *Start / stop control* button
moves. No new persisted state, no migration, no guess:
* a **fresh** install ships `auto_start: false`, has no stored `auto` key, and
therefore comes up **in shadow mode**. It observes a day of decisions before
it is ever allowed to command anything. That is the card's intent, delivered
where it is safe;
* an install that is **controlling** is started, so `auto` resolves to live and
**not one watt changes**;
* an install that is **stopped** keeps its actuator at 0 W exactly as before —
the same number, from the same writer, on the same heartbeat. What changes is
what the status page and the action log **say**, and that the decision path
now runs and is recorded.
⚠️ **Under `auto`, pressing Start leaves shadow mode.** That is the point of
`auto`: the button means "control the battery". An operator who wants the
decisions recorded *while the loop runs* — the configuration this card exists
to make possible — sets `on` explicitly, and cannot reach it by accident.
⚠️ **An unrecognised value resolves to SHADOW, and is REFUSED at startup.**
`shadow.mode()` fails toward inaction; `validate.py` rule 11 refuses the value
by name so the reinterpretation is never silent. A typo is not a decision, and
an install silently left in shadow mode commands nothing indefinitely while its
status page calmly explains that this is intentional.
---
## 2. "Commands nothing" is a number, not a silence
The inverter holds its last command **forever** — `HANDOVER.md` §6 says so, and
`firmware/goodwe-master.yaml`'s header records what it cost when a controller
stopped refreshing: *"Illusmart went silent mid-command and the inverter held
+5000 W for 113 s"*. `firmware/goodwe-master.yaml` states the contract that follows — *"HA
must now REWRITE the setpoint every ~10 s even when the value has not
changed"* — because without a refresh, **"stale" and "steady" are the same
thing on the wire**.
So shadow mode holds the actuator at `shadow.WIRE_W` = **0.0 W**, refreshed on
the ordinary heartbeat. Two consequences were weighed and are recorded:
* **it is not silence.** A shadow mode that stopped writing would leave the
standing command up until the ESP32's 30 s watchdog noticed — and at a site
with no such board, forever;
* **it does not use an alarm as a mode.** Letting that watchdog trip for the
duration of a shadow run teaches the operator that `wd_tripped` is normal,
which is exactly the training that makes it useless when the add-on has
actually died.
### It is not a second writer
SAFETY-28's rule is one actuator, one writer. Shadow mode files **no claim**,
owns **no transport**, and calls nothing in `hass.py`. It is a **substitution**
inside `Controller._write_unit()` — the single choke point every write in this
add-on already reaches, including the heartbeat, the stop button, `shutdown()`
and `maint_abort()` — in exactly the form of the three substitutions above it
(non-finite → 0 W, unauthorised → 0 W, clamped → the rating).
It is the **last** of them. Below SAFETY-28's gate and below SAFETY-03's clamp,
so both still grade the number the decision path actually produced, and a
shadow run can report *"it would have hit the rating here"*.
---
## 3. What the run records
| surface | what it carries |
|---|---|
| status banner | `SHADOW MODE - the battery is NOT being controlled...`, **first in the cascade**, amber — red, with the latch named, if one is standing |
| status row `Shadow mode` | which rung decided, the watts it **would have commanded on this cycle**, where the inverter actually is, and `Resolution.explain()` — plus, when a measured billed quarter sized those watts, SAFETY-47's caveat saying so (`shadow.SIZED_FROM_METER`) |
| status row `Commanded` | `0 W` — the truth, which the row above reconciles with the `Why` row below it |
| action log | one line when shadow mode comes on; one line per **change of decision** (winner, rounded watts, or SAFETY-47's caveat state), carrying the arbiter's own sentence and the same caveat the row carries — `shadow.log_line()` is the one sentence both read |
| MQTT | `status: shadow`, its own value, below `failsafe` |
The action log is **edge**-logged, not level-logged: the log holds 40 rows, and
a line per cycle would flush the context of the run's own findings inside four
minutes at the 15 s cycle floor.
---
## 4. The failsafes, one by one
| failsafe | in shadow mode | why |
|---|---|---|
| SAFETY-02/30 sign watchdogs | **INERT** | They grade `Inverter.standing_w()` — what this controller has standing on the wire — and shadow mode holds that at 0 W, so they cannot arm. ⚠️ Fed the shadow decision instead they would disagree with a meter that never saw it and **latch a trip that survives into live operation and a restart**: shadow mode would manufacture the failsafe it exists to help debug. ⚠️ **Two rungs hold it there** — `last_write` (the wire gate) and `inv.target` (the re-seed) — which is MUTATION.md's masking shape, so the mutation that reproduces the hazard defeats both as a pair (M6). Driven singly, dropping the re-seed does not reproduce it at all — measured |
| SAFETY-03 clamp | **OBSERVES** | Runs on the decision, sets `clamp_last`, logs every engagement. Changes no command |
| SAFETY-28 write gate | **OBSERVES** | Same placement, same reason: the question is who chose the number |
| SAFETY-18 meter freeze | **OBSERVES**, unchanged | It takes no action live either; both halves of its conjunction are as true in shadow |
| SAFETY-07/24/25 peak guard | **OBSERVES, AND SEES ONLY THE HOUSE** | Level-triggered, unlatched, files its claim as usual, so the recorded decision is the real one *for this meter*. ⚠️ **AMENDED BY SAFETY-47.** This row used to end "SAFETY-45's limit cycle is visible from a shadow run, which is the point". It is not: every term of `wanted = batt_w + excess` is measured, and in shadow mode the battery contributes nothing to either. Measured on the rig, same hour, same unsized code — **410 of 720 cycles engaged live, 0 of 720 in shadow** |
| SAFETY-31 circulation | **OBSERVES AND MAY LATCH** | Its evidence is *measured* power. Packs pushing against each other while all are told 0 W is a real fault |
| SAFETY-42 delivery | **OBSERVES AND MAY LATCH** | Same, against a share that is 0 W |
| operator stop | **SUPPRESSED AS A CLAIM, ENFORCED AT THE WIRE** | The one deliberate change. Its `P_SAFETY` 0 W claim out-ranks everything, so leaving it in makes the recorded decision `"stopped"` on every cycle and the run answers the wrong question. The actuator ends at the same number either way, and the wire substitution is **strictly stronger**: a claim can be out-ranked, and it cannot |
| inputs missing, non-finite, allocator refusal, arbiter contradiction | **UNCHANGED** | All resolve to 0 W, which is what the wire gets anyway |
⚠️ **A latch that is already up stays up.** Nothing here clears one. The shadow
banner **names** any standing latch and goes red for it, because a latch that is
up while the controller is inert is up the moment it stops being inert.
⚠️ **Maintenance is not in that table because shadow mode does not touch it.**
The state machines are ticked on every cycle whether control is started or not,
so a stopped install already runs them against a battery that does not move.
Shadow mode inherits that, unchanged and unimproved. Recorded here rather than
quietly fixed under another card's name.
---
## 5. The limitation, stated rather than discovered later
`Controller._shadow_settle()` re-seeds the carried command (`self.target` and
each `inv.target`) to `WIRE_W` at the **end** of every shadow cycle — after
every in-cycle guard has read the decision. Three machines read that value as a
statement about the **hardware**: the loop's `prev_w` and integrator,
`standing_w()`, and SAFETY-42's share comparison. Re-seeded, they track reality,
and **the exit is safe by construction** — the carried command already equals
the standing one, so the first live cycle slews from 0 W like any other.
⚠️ **The cost is real.** The loop's `prev_w` is therefore 0 W on every shadow
cycle, so the loop leg's recorded decision is **one slew step from the standing
command** and stays there. A shadow run answers *"what would this controller
command NOW, from where the plant really is"* — a true statement about the
present — and **not** *"what trajectory would it have followed"*. The trajectory
is a closed-loop property, it did not happen, and reporting it would be a
simulation of a plant that does not exist; three cycles in, such a number
describes nothing.
⚠️ **AMENDED BY SAFETY-47 — THE PARAGRAPH THAT STOOD HERE WAS THE DEFECT.**
It read:
> The strategies are unaffected: arbitrage, the peak guard and maintenance all
> file `SET` claims at a fixed power from level-triggered inputs. That is why
> the three defects this card was written for — SAFETY-45's 28 onsets an hour,
> TARIFF-14's wrong quarter-hour, SAFETY-46's ceiling churn — are all visible
> from a shadow run, and the loop's ramp is not.
It was true until **SAFETY-45 merged, one commit before this card**. That
change makes the buy leg `min(asked, headroom)` with
```
headroom = (900 / remaining) x (ceiling - projected)
```
and `projected` reads the **open quarter's accumulator** — the meter — which is
a function of what the battery did earlier in that same quarter. The strategy
is closed-loop, and the loop's one-slew-step limitation above is not a special
case of anything: **it is the general case**, and the limitation is the whole
feature's, not the loop leg's.
**The correct statement, and it is now graded rather than asserted:**
> A shadow run cannot surface a **closed-loop** defect — one whose stimulus is
> the plant's response to the controller — because the battery is held at 0 W
> and there is no response to be the stimulus. **Which** hour a strategy picks
> and **why** are unaffected, because the clock and the price series are not
> functions of the battery. **How hard** it trades is not.
Of the three defects this card was written for:
| | visible from a shadow run? | measured |
|---|---|---|
| SAFETY-45's limit cycle | **no** | 28 charge onsets live, **1** in shadow; grid −455.5 … +3200.0 W live, **flat at the 1200 W house** in shadow; guard engaged 410/720 live, **0/720** in shadow |
| SAFETY-46's SoC churn | **no** | the SoC moves **0.000000000 pp** in a shadow run. No SoC limit can be *reached* in one |
| TARIFF-14's wrong quarter-hour | **yes**, and it is the one | which hour, at what price, clearing what spread: identical live and shadow on **720 of 720** charging cycles, at a binding cap |
Graded in `test_arbitrage.py` part **3d** — the same closed loop part 3c uses,
run once live and once in shadow — and the loop leg's own limitation stays
named in `test_watchdog.py` part 10 as `RECORDED LIMITATION`.
---
## 6. How "nothing reaches the inverter" is graded
**Not on a flag.** A check that asserted `Controller.shadow` would pass on a
build in which the flag is set and the substitution is deleted — which is
exactly mutation **M1**.
`test_clamp.py` part 8 drives the **shipped** `Controller.cycle()` and the
shipped heartbeat against a recording Home Assistant stub, and asserts on what
reached `set_number()`:
* **the precondition first** — the same stimulus with `shadow_mode: off` puts
30 non-zero writes on the wire, the largest 5000 W. MUTATION.md habit 4: a
check whose data cannot reach the failure it names is decoration;
* then `set(writes) == {0.0}`, **and** that there were 26 of them — a check
that only said "no non-zero write" would pass on the silent build too;
* entry and exit are measured on `inv.last_write` — what the inverter is
latched on, updated only on an **accepted** write — either side of the
boundary, against the same run that never entered shadow mode.
The closed-loop half is `/home/homelab/s10-mut/shadowloop.py` on TEST-23 stage
3's rig: the same hour, twice, against `plantsim.Plant` through the firmware's
own frame encoder.
⚠️ **SUPERSEDED BY SAFETY-47 — THE TABLE THAT STOOD HERE COULD NEVER HAVE GONE
RED, FOR TWO INDEPENDENT REASONS.** It read `arb_power_w` −2000 W *"identical"*,
`arb_reason` *"identical, verbatim"*, arbiter winner *"identical"*, and
concluded *"the decision happened, at the same instant, for the same reason, at
the same signed power — and the battery did not move."* The battery half is
true and is unchanged. The **decision** half was decoration:
1. **the fixture is `peak_cap_w: 15000` against a 350 W house**, so the
capacity guard never engages and SAFETY-45's sizing is in the run and inert.
The harness's own comment says so — *"at this scenario's `peak_cap_w: 15000`
it is not binding anyway"* — which is MUTATION.md habit 4 written down
beside the check it disables;
2. **every identity row reads the FIRST charging sample.** At `elapsed = 0`
the projection *is* the held level, so the two runs agree to the float there
**even at a cap that does bind**. Measured: closing reason (1) alone leaves
that comparison passing.
Both had to be closed. Re-taken below at **`peak_cap_w` 1500 / house 1200 /
`max_w` 2000**, one hour at a 5 s cycle, **across the whole run** — harness
`/home/homelab/s47-mut/shadowloop47.py`, same rig, same three transcribed
lines.
| | live | shadow |
|---|---|---|
| grid | 1224.1 … 1506.0 W — **held up at the ceiling** | **1200.0 W flat = the house, exactly** |
| SoC | 50.000019 → **51.856789 %** | 50.000000 → **50.000000 %** |
| `ARBITRAGE_CHARGE` cycles | 720 / 720 | **720 / 720** |
| first charging cycle, `arb_power_w` | −300.0000 W | **identical — and this is why the old table passed** |
| `arb_power_w`, **whole run** | −307.799 … −299.930 W | **−2000.000 … −300.000 W** |
| …cycles where the two differ | — | **716 of 720** |
| `arb_reason`, whole run | the strategy's own sentence | **differs on 719 of 720** |
| measured charging headroom | 299.93 … 307.80 W | **300.0 … 54 000.0 W** |
| final recorded command | **−302.4 W** | **−2000.0 W — 6.61× the live figure** |
| price / spread / which hour | | **identical on 720 of 720** |
| arbiter winner | `arbitrage` | **identical** |
**What the re-taken table says.** The decision still *happens*, at the same
instant, on the same hour, at the same price, for the same *kind* of reason,
and the battery still does not move — those were the card's real claims and
they hold. What does **not** hold is that the decision is the *same decision*:
its **size** is a function of a meter the battery never moved, and at this cap
the recorded figure is 6.61× what a live controller commands. 54 000 W of
"headroom" under a 1500 W ceiling is `900/remaining` multiplying a gap the
battery never closed.
⚠️ **And the SoC row is the second half of it.** 0.000000000 pp of movement is
not a curiosity: it is the proof that **no SoC-limit behaviour is reachable
from a shadow run at all**, which §5 used to promise.
SAFETY-47 puts the caveat on both surfaces that carry the number and narrows
the three documents' claims; `test_arbitrage.py` part 3d is the CI-side grader
so this class cannot recur.
⚠️ **Three lines of each harness are a TRANSCRIPTION and are marked as one.**
`priceloop.Rig` has no `_write_unit()`, no clamp and no failsafe machine
(divergence 2 of its README), so the substitution's **placement** is
transcribed there. The shipped placement is graded by `test_clamp.py` part 8,
which drives the real `Controller`. ⚠️ **And the rig's transcribed cycle
predates SAFETY-45**: `arbitrage.decide()` gained a required
`charge_headroom_w` after `478ba93`, and the harness supplies it from the
**shipped** `peakguard.charge_headroom_w()` reading the **shipped** peak
decision rather than from a constant, so SAFETY-45 stays in the run.
---
## 7. The mutation battery — 22 mutations, no survivors
Harness: `/home/homelab/s10-mut/run.py`, backups beside it. Each run restores
from backup, purges `__pycache__` **on the host**, and grades through the CI
image with the tree bind-mounted `:ro`, so the interpreter cannot write a cache
into the tree under test (TEST-15). The full table is in the branch report;
one per new behaviour, including **M1** (the substitution deleted — a write
escapes), **M2** (it returns instead of substituting — the inverter is left
latched), **M3** (it moves above SAFETY-28 and SAFETY-03 — the observers go
blind), **M8** (`auto` resolves to shadow unconditionally — the literal
default-on that stops the live install), **M12** (the stop claim is filed in
shadow — every recorded decision reads `stopped`), **M21** (the substitution
and the re-seed together) and **M22** (the re-seed moved one line earlier —
SAFETY-18 grades a 0 W no decision produced and goes permanently blind).
⚠️ **Two findings from driving it, both of the kind MUTATION.md says to expect.**
* **M2 first came back a SURVIVOR and was not one.** The "stop writing
altogether" build left `inv.last_write` as `None`, the check did `float()` on
it, and the section died with a `TypeError` — grading none of the checks
after it and reporting **zero reds**, which reads exactly like a survivor.
That is FCST-06's shape. The fixture now hands `None` back and names it as
its own check; M2 is red on three.
* **M6 had to become a PAIR, and only the battery said so.** `standing_w()`
prefers `last_write` — the 0.0 W the wire gate accepted — and falls back to
`inv.target`, which the re-seed also holds at 0.0. Either rung alone keeps
the detector inert, so dropping the re-seed **singly** came back red on the
limitation check and on **nothing about the latch**: the hazard it names was
not reproduced. TEST-16's rule with a new name on it.
* **M7/M8/M9/M19 had to MOVE SUITES.** They defeat `shadow.engaged()`, and a
defeated default stops `test_clamp.py` part 3's wired run reaching the wire
at all — aborting the file with an `IndexError` before part 8 is graded. The
red count there was a lower bound naming the saturation freeze. The mode
table now lives in `test_validate.py`, which drives no Controller.
* **`shadow_would_w = float(self.target)` is an EQUIVALENT mutation and was
measured as one.** `_shadow_settle()` runs before the re-seed, so at that
line `self.target` **is** `resolution.target_w`. It is recorded as equivalent
rather than reported as a survivor, and the non-equivalent form of the same
defect — the record becoming the **wire** — is driven instead.
### The table
Each row: the mutation, the file, the byte delta, the suite it was graded in,
and how many **named** checks went red. `⚠️` marks a row whose run did not
reach the end of its file, so its count is a **lower bound** (MUTATION.md).
| # | mutation | file | Δ | suite | reds |
|---|---|---|---|---|---|
| M1 | **a write escapes** — the substitution deleted | `main.py` | −6 B | clamp | 5 |
| M2 | **silence instead of 0 W** — it returns rather than substituting | `main.py` | −15 B | clamp | 3 |
| M3 | **the observers go blind** — it moves above SAFETY-28 and SAFETY-03 | `main.py` | +58 B | clamp | 1 |
| M4 | the site re-seed dropped — the exit resumes from a fiction | `main.py` | −36 B | clamp | 3 |
| M5 | the per-unit re-seed dropped | `main.py` | −22 B | clamp | 1 |
| M6 | **PAIRED**: `standing_w()` reads the target **and** the re-seed dropped — the sign latch that survives into live operation | `inverter.py` + `main.py` | −170 B | watchdog | 3 |
| M7 | `auto` inverted — shadow while started, live while stopped | `shadow.py` | +2 B | validate | 4 |
| M8 | **default-on for everyone** — `auto` always shadow; the literal reading that stops the live install | `shadow.py` | −15 B | validate | 2 |
| M9 | an unreadable value resolves to LIVE instead of shadow | `shadow.py` | +1 B | validate | 1 |
| M10 | `validate.py` stops refusing an unknown value | `shadow.py` | −9 B | validate | 9 |
| M11 | the loop leg gated on `auto` alone again — the decision path stops running | `main.py` | −17 B | clamp | 1 |
| M12 | the stop claim filed in shadow — every decision reads `stopped` | `main.py` | −20 B | clamp | 1 |
| M13 | the banner goes green while nothing is commanded | `shadow.py` | −2 B | clamp | 1 |
| M14 | the banner loses the standing latch | `shadow.py` | −2 B | clamp | 1 |
| M15 | the row renders the standing command instead of the decision | `shadow.py` | −8 B | clamp | 1 |
| M16 ⚠️ | the row disappears when live | `main.py` | +43 B | clamp | 1 |
| M17 | the record becomes the wire | `main.py` | −6 B | clamp | 7 |
| M18 | level-logged — the 40-row action log floods | `main.py` | −23 B | clamp | 1 |
| M19 | the two rungs render identically (masking) | `shadow.py` | +22 B | validate | 1 |
| M20 | the shipped default moves to `off` in `config.yaml` alone | `config.yaml` | −1 B | defaults_pin | 1 |
| M21 | **PAIRED**: the substitution **and** the re-seed deleted together | `main.py` | −103 B | clamp | 10 |
| M22 | the re-seed moved one line earlier — SAFETY-18 grades a 0 W no decision produced and goes permanently blind | `main.py` | +40 B | clamp | 1 |
**Survivors: none.** ⚠️ **M17's `+0 B`-adjacent sibling** —
`shadow_would_w = float(self.target)` — is recorded in §7 as **equivalent**
rather than counted here.