ARB-03: restore Claim.actuator and make resolve() three-stage
specs.md:467 declares `actuator: str` as the FIRST field of `Claim`.
app/arbiter.py:55 had no such field. The specification designed
per-actuator claims and the implementation dropped it, so every claim was
implicitly about "the one and only actuator", resolve() returned one scalar
Resolution.target_w, and main.py assigned it to one self.target. THERE WAS
NO SEAM AN ALLOCATOR COULD OCCUPY - and ARCH-01 (specs.md §6.2, 2026-09-02)
decided the site grid target is ALLOCATED across several inverters and never
broadcast. This is a regression fix against the written design; creating that
seam is the whole of the change.

WHY IT MATTERS, IN THE UNITS THE SYSTEM IS BILLED IN. The control primitive
is meter emulation: the master reports a fabricated grid reading and the
inverter regulates itself to it, so one number means "the battery moves X W"
to the add-on and "the grid is at X W" to the inverter - an identity that
holds only at N=1. Broadcast one target to two inverters and each supplies it
in full; the loop gain at the meter becomes N times the per-unit gain, which
at the gain config.yaml:374 accepts is a permanent limit cycle with every
watchdog in §11.2 reporting healthy. And a per-inverter reserve filed as a
site `hi` against the peak guard's site `lo` is `lo > hi`, arbiter clause 3,
0 W IN THE BILLED QUARTER - the parked battery SAFETY-25's memo calls fatal.

THE SPLIT, VERIFIED AT EACH CONSTRUCTION SITE RATHER THAN ACCEPTED FROM THE
SURVEY. Four sources are about the GRID CONNECTION and are SITE claims:
`loop` (compute() regulates grid_w, the P1 measurement, and §6.2's whole
architecture is one integrator on P1 whose output is then split), `peak` (the
15-minute average offtake AT the grid connection, which is what the capacity
tariff bills - one quarter-hour peak per site, not one per pack),
`arbitrage` (buys and sells at the grid against a day-ahead price; the price
is a property of the connection and the energy crosses the meter) and
`safety` (both construction sites read: "stopped" is the operator switching
control off for the site, "inputs missing" is the site's own meter gone -
neither is about a pack, and both must stop every inverter).

Four are about a pack, a device or one write and are PER-INVERTER: `device`
(one inverter's own reported min/max - there is no site rating),
`supervised` (max_w caps what may be WRITTEN to one setpoint entity, §11.3,
so it is scoped like `device` for the same reason), `maintenance` (§12's
recalibration is a pack procedure - drain THIS pack, charge THIS pack,
recalibrate THIS pack's counter) and `failsafe`. `failsafe` is the entry that
needed the reading rather than the survey: SAFETY-02's EVIDENCE is site-wide
(it compares P1 against the standing command) but its CONCLUSION is
"the unit I am driving is pushing power the wrong way" and its remedy is to
park that unit. At N>=2 the same evidence cannot be attributed to a sibling
this controller never commanded, so a site-wide stop would park an inverter
this watchdog never graded. The reasoning for all eight is recorded AT THE
LINE, in arbiter.CLAIM_SCOPE and again at each claims.append in main.py.

WHAT WAS BUILT. resolve() is three stages, each a separate function so a test
can construct a case at any one of them:

  pre_resolve()  - one inverter's own claims -> that unit's interval. Clauses
                   1 and 2 transposed: the unit's own winning SET gates its
                   own limits. The SET's value travels BESIDE the interval,
                   not inside it - folding a -2500 W drain into
                   [-2500, -2500] would turn "clamped to max_w" into
                   "contradicts max_w", a different and wrong answer.
  site_resolve() - THE SHIPPED ARBITER, UNCHANGED. Same code, new name.
  allocate()     - THE SEAM, AND DELIBERATELY NOT AN ALLOCATOR. ALLOC-01
                   builds it. At N<=1 it passes the target through (§6.2's
                   identity). At N>=2 it DECLINES - no shares,
                   allocated=False - and main.py refuses to write rather than
                   broadcast, because the obvious placeholder (hand the target
                   to each) is the fault ARCH-01 was filed about and no guard
                   we have can tell it apart from the real thing.

THE CONTRADICTION IS NOT GUARDED AGAINST, IT CANNOT BE WRITTEN DOWN. The
partition is by `actuator` and it is a partition: a unit's `hi` and the site's
`lo` are never both terms of one `lo > hi` test. Constructed and swept - 40
filings (every per-inverter source x unit x bound, including a unit
contradicting ITSELF at lo 900 > hi 100) against a live site floor, and not
one moves the site target or raises a contradiction. A unit's own impossible
pair parks that unit and says so on its own bounds; it does not park the site.
That is SAFETY-25 §0c's table made mechanical.

AT N=1 THIS IS A PURE REFACTOR, AND THAT IS PROVEN RATHER THAN ASSERTED. With
one inverter the fabricated grid reading and the battery setpoint are the same
number, so the grid connection and the only unit ARE one actuator:
actuator_for() routes every source to the site, no claim is filed on a unit,
stage 2 sees the whole list and answers what the shipped arbiter answered.
All 17 suites replay UNEDITED above the ARB-03 sections and are green on the
same numbers; test_arbiter.py additionally runs 13 claim lists through both
resolve() and site_resolve() and compares target, winner, binder,
contradiction flag, the considered list and the operator line.

EVIDENCE, BY BREAKING EACH THING (tools/mutation_run.sh, purged tree):
  * Claim's dataclass default emptied            -> RED (test_arbiter)
    ...and it survived until the check was added: the two helpers pass their
    own default down, so the FIELD's default never ran. Now checked directly.
  * `peak` reclassified SCOPE_UNIT               -> RED (arbiter x4, peakguard x2)
  * `maintenance` reclassified SCOPE_SITE        -> RED (arbiter x4, peakguard)
  * the N=1 identity dropped in actuator_for()   -> RED (arbiter, peakguard
    incl. the maintenance/peak suppression checks, freeze) - which is the
    measurement that says splitting at N=1 would be a behaviour change
  * resolve() stops partitioning                 -> RED (arbiter x4)
  * allocate() broadcasts at N>=2                -> RED (arbiter x2)
  * stage 1 drops clause-2 gating                -> RED (arbiter)
  * a call site routes `device` through `loop`   -> RED (peakguard 10g)
  * SAFETY-25 Option B built as a ninth source   -> RED (peakguard 10f, both
    halves, plus 10g) - the tripwire still bites

SAFETY-24's asymmetry proof is re-run and holds: 0 negative floors over the
shipped sweep, `hi` still +inf on every claim the guard files, and it now also
asserts every one of them is on the SITE actuator - a floor bound to one
inverter's share would leave the site, the thing the capacity tariff meters,
with no floor at all.

test_peakguard.py part 10f is kept, not adapted around. `source` is still
Claim.set()'s first positional argument precisely so its AST scan keeps
reading it, which is why `actuator` is the LAST field of Claim and not the
first - moving `source` off position 0 would silently blind the tripwire that
guards SAFETY-25's deferred option. The one adaptation is `**kw` on its spy,
so main.py's roster passes through unread rather than being silently dropped.
New part 10g pins CLAIM_SCOPE to the same eight-source set and grades a REAL
two-inverter cycle, which is the only place a mis-typed actuator_of(...) at a
call site is observable - at N=1 every source legitimately routes to the site,
so a swap there is invisible by construction.

No config key, no option, no operator surface, no default moved. Inverter B
does not exist yet and nothing here measures it.

Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-02 01:54:29 +02:00

GoodWe RS485 Controller — Home Assistant add-on repository

Replaces a GoodWe battery inverter's vendor controller with a local one: holds net grid exchange at zero by emulating the inverter's smart meter over RS485, and runs the monthly battery maintenance cycle the vendor box was doing.

repository.yaml            add-on repository metadata
goodwe_controller/         the add-on
  config.yaml              manifest + options schema (the per-site config form)
  app/                     the controller
    control.py             the control law — pure functions, no I/O
    maintenance.py         the monthly cycle state machine
    hass.py                Supervisor/Core API access
    store.py               persistent state in /data
    mqtt.py                optional status entities
    web.py                 ingress UI
    main.py                orchestration, heartbeat, failsafe behaviour
  test_control.py          runnable checks — no framework needed
  test_maintenance.py      runnable checks — walks a full cycle in fake time
  DOCS.md                  the add-on's documentation tab
  MUTATION.md              how to run a mutation so the result means something
  tools/mutation_run.sh    the mutation harness - purges bytecode, then grades
firmware/goodwe-master.yaml  ESPHome config for the T-CAN485
estop/rs485_log.py           optional RS485 e-stop / bus witness
docs/GoodWe-RS485-Field-Guide.pdf  the guide techs carry (10pp, A4)
docs/build_guide.py          its single source - rebuilds the HTML and PDF
FIELD-GUIDE.md             how to edit and rebuild the guide

Picking this up after a break? Read HANDOVER.md first — current state, what is known broken, and what to do next.

Install

Settings → Add-ons → Add-on store → ⋮ → Repositories → add

https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon

then install GoodWe RS485 Controller.

⚠️ The repository must be PUBLIC for this to work. Home Assistant clones it anonymously; against a private repo the store shows nothing and gives no useful error. If it must stay private, install locally instead: copy goodwe_controller/ into the machine's /addons/ folder, then ha store reload — it appears as a Local add-on.

⚠️ Bump version: in goodwe_controller/config.yaml for every change. Supervisor keys the built image by that version, so without a bump it silently reuses the old image and your fix appears not to work — on your bench and on every client's machine.

Requires Home Assistant OS or Supervised. Add-ons cannot be installed on HA Container or Core.

Read this first

The inverter holds its last command forever. It has no meter-timeout of its own — a controller that dies mid-command leaves the battery running until a human intervenes. Measured on real hardware: 5 kW of discharge held for 113 seconds after a controller went silent.

Three layers exist because of that, and only the third covers the Home Assistant machine itself dying:

  1. ESP32 watchdog — no fresh setpoint for ~30 s → command 0 W, and keep commanding it.
  2. Wind-down before firmware updates — 0 W written before the update starts.
  3. RS485 e-stop (optional) — writes 0 W after 30 s of total bus silence.

Sites sold without the e-stop must have the acknowledgement in FIELD-GUIDE.md §10 signed.

Development

The control law and the maintenance machine are pure Python with no Home Assistant imports, so they run anywhere:

cd goodwe_controller
python3 test_control.py
python3 test_maintenance.py

Both must pass before shipping any change. To prove a check bites - the way almost every claim in this repository was established - mutate the module and run tools/mutation_run.sh, which clears __pycache__ first. It is not optional: a same-size edit reverted inside one second leaves CPython reusing the old bytecode, and the run grades code that is not there. goodwe_controller/MUTATION.md has the mechanism, the measurement, and what the flags do not do. They are not unit-test theatre — each assertion corresponds to a rule whose absence produced an observed failure on real hardware, and the comments in control.py say which.

Compatibility

Check the serial number, not the model name. Characters 6-8 of the serial are the platform tag:

tag platform verdict
ESU EMU ESA BPS BPU EMJ IJL 105 — ES/EM/BP, AA55-era meter bus supported
SPB SPN 745 — SBP G2 (GW…-SBP-20) no
ESN ESC 745 — ES G2 (GW…-ES-20) no
ETU EHU BTU … 205/745/753 — ET/EH/BT hybrids no
SDT DST MSU NSU … PV-only inverters — no battery to control no

A "-20" or "G2" suffix means a different platform with a different meter protocol. The tags come from the goodwe library's PLATFORM_105_MODELS, which is also what Home Assistant's own integration uses to pick a protocol.

  • GoodWe ES / BP family inverters (AA55 / RS485 meter-bus generation)
  • The protocol is reverse-engineered. There is no vendor contract, and a firmware change on GoodWe's side could break every installation at once. Say so when you sell it.