checks / unit (pull_request) Successful in 6m20s
`delivery.delinquent()` named a unit whose `short_by()` gap exceeded an
ABSOLUTE `min_w = Tuning.saturation_w = 500 W`. OPT-09's SoC-aware weights
shrink a low-headroom unit's share, and shrinking the share shrinks the gap, so
a unit standing at +125 W and delivering 0 W - 100 % delinquent - was never
named. Measured end to end on the real loop (test_packshare.py part 8b):
load 1500 W, B wedged at 15 %, equal weights named on 199/200 cycles
load 1500 W, B wedged at 15 %, OPT-09 weights named on 0/200 cycles
⚠️ The suppressed regime is the quiet one: at a load the healthy sibling covers,
the meter is satisfied, `unmet_w` is 0 and no action-log line fires, so this
alarm is the ONLY instrument that would have told the operator.
WHAT CHANGED, in one line:
named if short_by() > min_w OR short_by() > frac * share
⚠️ `min_w` WAS NOT LOWERED. It exists to stop normal saturation being reported
as delinquency, and lowering it trades a missed alarm for a false one on every
unit at once - SAFETY-41's four-attempt regime. This is a SECOND way to be
named, not a looser first one: all seven of test_delivery.py part 1's existing
fixtures answer identically under both rules, and the absolute arm's suppression
window is still exactly 1000 W / 6500 W, still asserted in part 8b.
THE FRACTION IS DERIVED, 0.85. admin/goodwe:sim/delivery_window.py gained a
`--fractions` axis and grades the constant over the SAME 2640 no-fault runs that
produced `delivery_hold_s`'s 35.0 s floor. Worst continuous legitimate episode,
worst of three families, twenty fractions:
frac 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50
worst 90.0 90.0 70.0 70.0 60.0 55.0 55.0 60.0 45.0 45.0 s
frac 0.55 0.60 0.65 0.70 0.75 0.80 *0.85 0.90 0.95 0.99
worst 40.0 40.0 45.0 45.0 45.0 45.0 40.0 40.0 40.0 40.0 s
absolute arm alone: 35.0 s (SAFETY-42 §3.3, reproduced in the same runs)
⚠️ NO CLIFF ANYWHERE: 0.45-0.99 is flat within one control cycle, and it is not
monotone - §3.3's own mechanism (c). ⚠️ "Zero false namings" is NOT achievable
at any fraction and the record says so; what is zero is false ALARMS - 90.0 s
worst against a 185 s hold, so nothing comes within 95 s of notifying anybody.
N=1 control 0.0 s at every fraction in all 2640 one-inverter runs; flapping
0.0 s in all 840.
DRIVEN. Part 8b pinned the SUPPRESSED behaviour and said "if it ever goes red
because the alarm fired, read the card that made it fire". It now grades BOTH
rules on one run - `share_frac=None` is SAFETY-42's rule exactly:
OPT-09 weights, absolute arm alone named on 0/200
OPT-09 weights, the shipped rule named on 200/200
POSITIVE CONTROL. Same fixture, same weights, same 125 W share, one legitimate
fact changed: a pack at its own 10 % cut-out is named on 0/200 (account() still
gates it), and a unit delivering HALF its share is named on 0/200.
N=1 BYTE-IDENTICAL, asserted: `plan()` handed a `weights` mapping that raises on
any read still answers identically at a roster of one, and the same mapping
raises at a roster of two; `delinquent()` answers {} on all 84 single-unit
(share, measured, rule) combinations including 0 of 125 W.
MUTATION, run on fresh :ro trees: M12 (drop the relative arm), M13 (frac -> 1.0)
and M14 (frac -> 0.05) are all red on named checks. The constant cannot move in
either direction unseen.
⚠️ CFG-07 gets ONE CONTROL CYCLE WORSE and is deliberately not fixed here: the
worst legitimate episode goes 35.0 -> 40.0 s, so the schema's `int(30,900)`
false-tripping band widens from [30,35] to [30,40]. CFG-07 should be re-derived
against 40.0 s.
No option value, no schema bound and no default changed. 27/27 suites green.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
335 lines
19 KiB
Markdown
335 lines
19 KiB
Markdown
# OPT-09 - the weights parameter, and what it is honestly for
|
|
|
|
**Status:** implemented. **Branch:** `OPT-09`. **Base:** `release/1.0` @ `3d29993` (rebased onto the UX-02 merge; it read `3368231`, and before that `464d398` - each rebase moved it and review caught it each time, which is why the counts in `test_translations.py` are now computed rather than typed)
|
|
(`git merge-base HEAD 3368231`; the branch was rebased and this line used to name
|
|
the pre-rebase base, `464d398`).
|
|
|
|
## 0. What was actually wrong
|
|
|
|
`allocator.plan()` has taken a `weights` argument since ALLOC-01, `_fill()`
|
|
consumes it in two passes, and **nothing had ever passed one**. Confirmed on the
|
|
base commit:
|
|
|
|
arbiter.py:535 def resolve(claims, *, units=None, weights=None, live=None, ...)
|
|
main.py:2422 resolve(claims, units=self.units, live=self.live_units(), ...)
|
|
|
|
So `weights` was None on every tick of every install, `plan()` turned that into
|
|
1.0 per unit, and the site target was split **50/50 regardless of what either
|
|
pack could do**. The card was filed as "per-pack arbitrage sizing"; the architect
|
|
pass found the sharper content, and it is the sharper content that this branch is
|
|
mostly about.
|
|
|
|
## 1. Two instruments, and they are not interchangeable
|
|
|
|
`allocator.py` states the rule this card is built on, and it is mechanical rather
|
|
than advisory:
|
|
|
|
> WEIGHTS EXPRESS PREFERENCE. ENVELOPES EXPRESS PERMISSION. A weight of 0 is
|
|
> "please do not use this unit", and it is honoured while any other unit has
|
|
> headroom - but it is NOT a constraint.
|
|
|
|
`_fill()` runs a deliberate **last-resort pass** over the zero-weight units when
|
|
the preferred ones saturate, so that a preference can never manufacture a
|
|
standing error at the meter. A pack at its own cut-out that is only *weighted*
|
|
to zero is therefore still commanded to discharge the moment its sibling fills
|
|
up. So this branch ships both:
|
|
|
|
| | question | mechanism |
|
|
|---|---|---|
|
|
| `packshare.envelope()` | MAY this pack be asked, at all, in this direction? | a `pack` UNIT claim at `P_SAFETY`, `hi = 0` at the cut-out, `lo = 0` at 100 % |
|
|
| `packshare.weights()` | GIVEN that both may, which should carry more? | energy headroom in kWh, handed to `resolve()` |
|
|
|
|
## 2. ⚠️ What the weights CANNOT do
|
|
|
|
ARCH-01's convex-combination argument - the gain at the meter is
|
|
`sum(a_i * g_i)`, so it lies in `[min g_i, max g_i]` for **any** split -
|
|
guarantees that a bad split cannot **destabilise** the site. It says nothing
|
|
about whether the site can **regulate**. A unit at its energy limit has
|
|
`g_i = 0`; the combination is still inside the interval and the load it was
|
|
asked to carry simply does not move.
|
|
|
|
Measured, `test_packshare.py` part 8, two units rated 2000 W each, B sitting on
|
|
its own floor and therefore answering 0 W to any discharge command. The plant is
|
|
modelled in that file (`lag_s = 0`, obeys within one cycle, bounded by its
|
|
rating) and the loop is the real `compute()`:
|
|
|
|
| load | arm | site target | shares | grid | unmet |
|
|
|---|---|---|---|---|---|
|
|
| 1500 W | shipped | +3000 W | A +1500, B +1500 | 0 W | 0 W |
|
|
| 1500 W | weights | +1500 W | A +1500, B +0 | 0 W | 0 W |
|
|
| 1500 W | envelope | +1500 W | A +1500, B +0 | 0 W | 0 W |
|
|
| 3000 W | shipped | +4000 W | A +2000, B +2000 | +1000 W | 0 W |
|
|
| 3000 W | weights | +4000 W | A +2000, B +2000 | +1000 W | 0 W |
|
|
| 3000 W | envelope | +4000 W | A +2000, B **+0** | +1000 W | **+2000 W** |
|
|
|
|
Three things are worth reading off that table, and the second and third are the
|
|
uncomfortable ones:
|
|
|
|
1. At a load the healthy pack can cover, the weights alone deliver the whole
|
|
improvement. The shipped arm reaches the same meter reading only by winding
|
|
the site target to **twice the load** and standing a +1500 W command on a
|
|
battery that answers nothing, permanently saturation-frozen. That is not a
|
|
working site, it is a site with no headroom left for the next load step.
|
|
2. At a load it cannot cover, **the weights stop working entirely**. The
|
|
weighted arm and the shipped arm command the identical +2000 W into the empty
|
|
pack, because `_fill()`'s last-resort pass hands the remainder to the
|
|
zero-weighted unit. Same shares, same watts, same error.
|
|
3. **And the envelope does not rescue the delivery either - it names the
|
|
shortfall.** Same 2000 W delivered, same 1000 W standing at the meter. What
|
|
changes is that the empty pack is commanded 0 W instead of 2000 W, and 2000 W
|
|
of site target is *reported* as unplaceable instead of appearing to have been
|
|
placed.
|
|
|
|
> **Weights are a comfort choice for STABILITY and NOT for DELIVERY.** Nothing in
|
|
> this add-on shifts a unit's load to its sibling once the sibling is at its
|
|
> rating, and weighting a failing unit down is not a remedy for it.
|
|
|
|
## 2b. ⚠️ The card's own premise is only half true
|
|
|
|
The card opens with *"a unit that stops delivering its share (empty, full,
|
|
curtailed, wedged) parks the site with a standing grid error and no alarm."*
|
|
After this branch: the **ask** stops, and while the sibling has headroom the site
|
|
regulates to zero error instead of winding to twice the load. The **standing grid
|
|
error does not stop** once the sibling is at its rating - §2's table measures
|
|
1000 W standing in all three arms - and there is **still no alarm** for it, only
|
|
a report. SAFETY-42 will not alarm on a pack at its own floor; that is one of its
|
|
acceptance criteria and its evidence is that the benign and the wedged case are
|
|
indistinguishable in the power domain.
|
|
|
|
So the two cards together mean: an empty pack limiting the site is now REPORTED
|
|
(`unmet_w`, an action-log line) and still, deliberately, NOT ALARMED. Whether it
|
|
should be alarmed is a decision - and the alarm it would need is about a site's
|
|
stored ENERGY, not about an inverter's delivery, so it is not this card's and not
|
|
SAFETY-42's. Recorded rather than quietly closed against a premise this card only
|
|
half meets.
|
|
|
|
## 3. Which floor, and which ceiling - the two places this could have become policy
|
|
|
|
**The floor is `bms_soc_floor` alone, never `peakguard.pack_floor_pct()`.** That
|
|
function's conjunction with `peak_soc_floor` is right for the peak guard and
|
|
wrong here: SAFETY-25 decided (2026-09-02, Option A) that `peak_soc_floor` bounds
|
|
the peak guard **only**, ordinary self-consumption discharges straight past it,
|
|
and closing an envelope at it would turn an operator preference into a hard stop
|
|
on the grid-following loop - the memo's **deferred Option B**, built by accident.
|
|
`delivery.py`'s `account()` made the same choice one step out, for the same
|
|
reason. Graded: a pack at 15 % with a 10 % cut-out is not closed, though a 20 %
|
|
EMS floor would have closed it.
|
|
|
|
**The ceiling is 100 %, and the coarseness is the honest answer.** There is no
|
|
per-pack charge ceiling anywhere in this add-on - `delivery.py` says so at length
|
|
and calls it a card, and it is why SAFETY-42 is armed on discharge shares only.
|
|
The only other number available is `arbitrage_soc_ceiling`, which is one
|
|
site-wide **trade policy**; filing it as a `P_SAFETY` envelope on the loop would
|
|
be the mistake above in the charge direction. So the envelope closes only where
|
|
the ask is physically impossible, and everything between is left to the weights -
|
|
which is the right instrument for a graded preference and is honest about being
|
|
only a preference.
|
|
|
|
## 4. N=1, and the tripwire this had to argue past
|
|
|
|
`actuator_for()` routes **every** source to the site at one inverter, so a `pack`
|
|
interval filed there would bound the SITE TARGET rather than a share. `main.py`
|
|
therefore does not file it at all below a roster of two - the same guard, for the
|
|
same reason, that SAFETY-30's `sign_site` carries. AC 4 ("at N=1 allocation is
|
|
byte-identical") is that `if`.
|
|
|
|
`test_peakguard.py` part 10f pins the claim-source set against `main.py`'s own
|
|
AST precisely so that a state-of-charge-conditioned claim cannot arrive quietly.
|
|
`pack` is state-of-charge-conditioned, so the argument is written at that set
|
|
rather than the count edited: the number is not an option, the claim is
|
|
unit-scoped so it cannot bound the site target, it is not filed at N=1, and part
|
|
10f's own note names this as the revisit trigger - *"under ALLOC-01 the reserve
|
|
becomes a PER-INVERTER INTERVAL AT THE ALLOCATOR rather than a ninth claim
|
|
here"*. Stage 1 is how an interval reaches the allocator and stage 1's input is
|
|
claims, so a unit-scoped claim is the shape that sentence asks for.
|
|
|
|
**What N=1 still does not get, said plainly:** nothing stops the loop discharging
|
|
into the BMS cut-out at one inverter. That is unchanged, it is SAFETY-25's
|
|
deferred option, and the BMS is what stops it.
|
|
|
|
## 5. SAFETY-42 - the same hazard from the opposite side
|
|
|
|
The seam is **the state of charge** - and they overlap in one direction, which
|
|
is what the rest of this section is about:
|
|
|
|
* **OPT-09 stops the site ASKING** a pack whose own SoC says it cannot deliver.
|
|
* **SAFETY-42 alarms** when a pack that said it could does not.
|
|
|
|
A wedged unit reads a healthy SoC, so **no envelope closes** - that half is
|
|
absolute, and it is why this card cannot stop the ask on a wedged box. A pack at
|
|
its floor is `account()`'s explained case, so SAFETY-42 stays silent - and after
|
|
this card that ask does not arrive in the first place, which removes the benign
|
|
arm from the detector's input rather than teaching it a new discriminator.
|
|
|
|
⚠️ **BUT THE WEIGHT DOES MOVE, AND IT NARROWED SAFETY-42's DETECTION WINDOW.
|
|
THAT WAS A DETECTION REGRESSION AT N=2, IT WAS NOT FIXED HERE, AND SAFETY-43
|
|
CLOSED IT - see the block at the end of this section.** An earlier draft of
|
|
this section said "no envelope closes and no weight moves - OPT-09 cannot see it
|
|
at all". The second clause was **false**, and it was load-bearing for the claim
|
|
that the two cards do not overlap. A weight is a function of the pack's ENERGY
|
|
HEADROOM, not of what the pack delivers, so a wedged unit's weight moves whenever
|
|
its headroom differs from its sibling's - which is the ordinary case this card
|
|
exists to exploit. And `delivery.delinquent()`
|
|
named a unit only while its `short_by()` gap exceeded `min_w =
|
|
Tuning.saturation_w`, and that was **500 W in absolute watts** with nothing
|
|
else beside it. Shrinking a unit's share shrinks its gap. Shrink the
|
|
share far enough and the gap drops below 500 W while the unit is still delivering
|
|
nothing, and the alarm stops firing.
|
|
|
|
Measured on the closed loop - real `compute()`, real `plan()`, real
|
|
`delinquent()`, modelled plant, B wedged at 15 % against its own 10 % floor so
|
|
nothing closes and `account()` explains nothing, i.e. a SAFETY-42 **true
|
|
positive** by that card's own definition:
|
|
|
|
load 1500 W equal weights (shipped) named on 199/200 cycles
|
|
shares {a:1500, b:1500} grid +0 W named=['inverter-b']
|
|
load 1500 W OPT-09 weights named on 0/200 cycles
|
|
shares {a:1505, b: 125} grid -5 W named=(nobody)
|
|
|
|
⚠️ That plant is modelled in `test_packshare.py`, and **inverter B does not
|
|
exist** (expected ~2026-09-12): it is two copies of A driven with different
|
|
numbers, and B's 4600 W / 20.48 kWh / 10 % floor are from the datasheet and the
|
|
serial. The claim is about the arithmetic of the split and the threshold, which
|
|
needs no hardware, and not about a GW5000S-BP.
|
|
|
|
At a load the healthy pack can cover - the regime where nothing else tells the
|
|
operator anything, `unmet_w` is 0, the meter is satisfied and no action-log line
|
|
fires - a wedged inverter goes from named on essentially every cycle to **never
|
|
named**. The suppression window widens from `site target < 2 * min_w` = 1000 W to
|
|
`site target < min_w * (w_A + w_B) / w_B`, which on that fixture is **6500 W** of
|
|
a 9600 W site; above it - once the healthy pack is at its own rating and
|
|
`_fill()`'s last-resort pass hands the wedged unit a big share again - the alarm
|
|
returns. ⚠️ BOTH BOUNDS ARE ARITHMETIC ABOUT `_fill()`'s PROPORTIONAL REGIME AND NEITHER IS A REACHABLE STEADY STATE. Swept on this fixture, the healthy pack's own 5000 W rating binds FIRST: suppressed 0/200 up to a 3000 W load, 4/200 at 4000 W, 41/200 at 4900 W (site target 5320 W, the largest reached with the wedged unit still under 500 W), then 195/200 at 5000 W once `_fill()` pins A at its cap and hands B 3000 W. So the alarm returns BELOW the 6500 W formula bound, not above it. The equal-weights 1000 W bound is unreachable for the same reason - the equal arm names the wedged unit 199/200 at every load swept, 1000 W included.
|
|
|
|
`test_packshare.py` part 8b graded all of it and **pinned the unflattering
|
|
behaviour**, so that the day it changed a named check would move. It has moved.
|
|
|
|
### ⚠️ CLOSED BY SAFETY-43 - THIS IS NO LONGER A DISCLOSED RESIDUAL
|
|
|
|
This section used to end *"until then this is a disclosed residual [...] at two
|
|
inverters, a wedged unit with materially less energy headroom than its sibling
|
|
can go unreported at ordinary house loads"*. That sentence is **retired, not
|
|
softened**, and what replaces it is a measurement rather than an intention.
|
|
|
|
`delivery.delinquent()` is now relative to the ask **as well as** absolute:
|
|
|
|
named if short_by() > min_w OR short_by() > frac * share
|
|
|
|
with `frac = delivery.DELIVERY_SHARE_FRACTION`. A unit delivering 0 of 125 W is
|
|
100 % delinquent and is named; a unit delivering 0 of 1500 W was already named
|
|
and still is. On the **same fixture, under the same weights**, part 8b now
|
|
grades both rules in one run - `share_frac=None` is SAFETY-42's absolute arm,
|
|
exactly:
|
|
|
|
load 1500 W OPT-09 weights absolute arm alone named on 0/200 cycles
|
|
load 1500 W OPT-09 weights the shipped rule named on 200/200 cycles
|
|
|
|
⚠️ **`min_w` WAS NOT LOWERED, AND THAT IS THE HALF THAT MATTERS HERE.** The
|
|
absolute arm's suppression window is still exactly the arithmetic above - 1000 W
|
|
at equal weights, 6500 W at these - and part 8b still asserts both numbers.
|
|
Lowering `saturation_w` would have traded a missed alarm for a false one on
|
|
every unit at once, which is SAFETY-41's four-attempt regime. SAFETY-43 added a
|
|
**second** way to be named and left the first where it was.
|
|
|
|
⚠️ **AND WHAT OPT-09 STILL DOES NOT DO IS UNCHANGED.** This card stops the site
|
|
ASKING a pack whose own SoC says it cannot deliver; it does not re-allocate a
|
|
wedged unit's watts, and SAFETY-43 did not make it. The alarm got louder; the
|
|
loop did not move. The derivation of `frac` - swept over the same 2640 no-fault
|
|
runs that produced `delivery_hold_s`'s floor - is in
|
|
`DECISIONS/SAFETY-43-delinquency-relative-to-the-ask.md`.
|
|
|
|
So the seam, stated accurately **as of SAFETY-43**: OPT-09 stops the ask, and it
|
|
still narrows the ABSOLUTE arm's window for a low-headroom unit exactly as
|
|
described above - but it no longer narrows the DETECTOR, because the detector no
|
|
longer reads only that arm.
|
|
|
|
⚠️ **And OPT-09 supplies the mechanism SAFETY-42 said was missing, without
|
|
connecting it.** That module's rejection of re-allocation rests on *"the only
|
|
re-allocation this add-on can express is ALL OR NOTHING [...] a partial
|
|
re-allocation is what would make acting safe, and the allocator has no way to
|
|
express it today"*. Passing weights **is** that expression. Wiring delinquency
|
|
into them is deliberately **not** done here: it would be acting on the alarm,
|
|
which SAFETY-42 refused with rig evidence (a unit derated to 50 % is 400 W worse
|
|
dropped than kept, and no instrument this add-on has can tell it from a wedged
|
|
one), and - see §2 - a weight cannot stop a unit being commanded anyway. That is
|
|
a card, and this paragraph is its input.
|
|
|
|
## 6. Per-pack arbitrage sizing, and the half that is deliberately not moved
|
|
|
|
`arbitrage.decide()` was handed `site_max_w` on **both** sides, so a two-pack
|
|
site would buy at the sum of the ratings whatever either pack's state of charge
|
|
was. It is now sized to the packs whose own SoC permits that direction
|
|
(`Controller.trade_power_w()`), using **arbitrage's own** bounds rather than the
|
|
BMS cut-out - sizing a trade is the trade's business; permitting a command is the
|
|
pack's.
|
|
|
|
Two honest limits:
|
|
|
|
* **The sell side is a no-op on every roster today.** `decide()` is handed
|
|
`pack_floor_soc` - the emptiest pack - so a sell is refused outright whenever
|
|
*any* pack is at or under the floor, i.e. in exactly the states where the sum
|
|
could be smaller than the site rating. The arithmetic is graded directly
|
|
(`test_packshare.py` part 9); it becomes reachable the day that gate is
|
|
per-pack.
|
|
* **Moving that gate is not this card's.** Sizing a sell off the *fullest* pack
|
|
would let the trade proceed while the emptiest pack was below
|
|
`arbitrage_soc_floor`, and the only per-pack instrument that could keep it out
|
|
of that pack is the weights - which are a preference, and `_fill()` will hand
|
|
it watts anyway. Doing it safely needs an envelope that depends on WHICH CLAIM
|
|
WON the tick, which the arbiter's partition does not express. §2 is why that is
|
|
a real objection and not a hedge.
|
|
|
|
`arbitrage.decide()` also now refuses a **0 W sizing** by name (`IDLE_NO_SIZE`),
|
|
because a `Claim.set(..., 0.0)` at `P_ARBITRAGE` is a park order that outranks
|
|
the loop - the failure the note on `claim()` is already written against. The
|
|
sizing can never be zero on a tick that trades today; that is a coincidence of
|
|
the existing gate, and this makes it structural instead.
|
|
|
|
## 7. The fixture, which is the hard part
|
|
|
|
Two packs that differ in only ONE of SoC and capacity cannot separate a
|
|
SoC-aware weighting from a capacity-aware one; two identical packs cannot
|
|
separate ANY weighting from any other. `test_packshare.py` part 1 grades the
|
|
fixture itself before anything is asserted with it - four candidate schemes
|
|
(equal, power rating, SoC only, energy), four distinct splits of the same
|
|
1000 W:
|
|
|
|
equal A +500, B +500
|
|
power A +521, B +479
|
|
soc only A +125, B +875
|
|
energy A +97, B +903
|
|
|
|
and the counterfactuals: on two identical packs all four collapse to one answer;
|
|
at the same SoC, `soc only` collapses onto `equal`; at the same capacity,
|
|
`energy` collapses onto `soc only`.
|
|
|
|
## 8. Provenance of every number
|
|
|
|
* A: **5000 W, 15.36 kWh, 10 % floor** - measured (GW5000S-BP, register 0x0560).
|
|
* B: **4600 W, 20.48 kWh, 10 % floor** - **FROM DATASHEET AND SERIAL**
|
|
(`goodwe/NOTES.md` §1.1b, GW5048D-ES `55048ESU22AW0992`). ⚠️ **Inverter B does
|
|
not exist** (expected ~2026-09-12).
|
|
* Every two-unit run in `test_packshare.py` is arithmetic over intervals and
|
|
weights, or a plant modelled in that file. `sim/plantsim.py:216`'s `INVERTER_B`
|
|
is **inverter A copied** with `measured=False`, so any two-inverter simulation
|
|
result anywhere in this project is **two copies of A**.
|
|
* No rig was taken, no hardware was touched, and nothing here is evidence about
|
|
a second GoodWe inverter.
|
|
|
|
## 9. Config
|
|
|
|
`capacity_kwh` joins the `inverters` roster as an **optional** per-entry key
|
|
(`float(0.1,200)?`) - the opposite choice to SAFETY-32's required
|
|
`bms_soc_floor`, and for that card's own reason: a missing cut-out would have to
|
|
be *defaulted*, and one default for two batteries protects the shallower pack
|
|
with the deeper pack's number, whereas a missing capacity has an honest answer -
|
|
no opinion about the split, every unit weighs 1.0, which is exactly what shipped.
|
|
|
|
It is **all or nothing across the roster** and rule 9 refuses a partial one: a
|
|
pack measured in kWh beside a sibling weighing a dimensionless 1.0 is not a
|
|
comparison, `weights()` answers "no opinion" for the whole roster in that case,
|
|
and a key that silently changes nothing is worse than one that refuses to load.
|
|
|
|
There is deliberately **no flat `capacity_kwh`**: at one inverter there is no
|
|
split to weight, so it would be an option an operator can set and nothing reads.
|