Files
adminandClaude Opus 5.5 4cd604afcb
checks / unit (pull_request) Successful in 26m26s
infra-pin / fresh (pull_request) Successful in 1s
SAFETY-91 review: a held-back battery is released 1 point above its reserve
A SoC reading flipping across the reserve swapped ~1000 W between the
batteries on each flip (grid +-500 W with unequal lags). Also grades
next_quarter()'s staleness boundary (29.5 / 30.5 s).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-02 14:54:20 +02:00
..
2026-10-02 09:04:47 +02:00
2026-09-29 02:37:44 +02:00