glenn schrooyenandClaude Opus 5 5184a2cfc2 Rest the meter just below zero, not at zero
The deadband is a one-way ratchet: any resting point inside it holds
indefinitely. Import and export are separate registers on the meter, so a
loop resting at +14 W bills 0.34 kWh/day while behaving perfectly.

target_grid_w (default -10 W) moves that residue onto the export register.
Worst billed rest point drops from 15 W to under 5 W. Behaviour is unchanged
at target_grid_w: 0.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-08-24 04:20:07 +02:00

111 lines
2.8 KiB
YAML

name: GoodWe RS485 Controller
version: "0.2.1"
slug: goodwe_controller
description: >-
Drives a GoodWe ES/BP battery inverter over RS485 by emulating its smart
meter, holding net grid exchange at zero and running a monthly battery
maintenance cycle.
url: https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
arch:
- aarch64
- amd64
- armv7
init: false
startup: application
boot: auto
# Needed to read the meter and to write the ESPHome setpoint number.
homeassistant_api: true
hassio_api: true
# Own diagnostics/operations UI inside HA. This is what a field tech and a
# remote supporter both look at, so it is not optional.
ingress: true
ingress_port: 8099
panel_icon: mdi:battery-sync
panel_title: GoodWe
# Optional: publish status entities by MQTT discovery. `want` rather than
# `need` - the add-on runs fine with no broker, it just publishes nothing.
services:
- mqtt:want
options:
# --- sources (required) ---------------------------------------------------
meter_entity: sensor.p1_meter_active_power
meter_invert: false
soc_entity: ""
batt_entity: ""
batt_invert: false
setpoint_entity: ""
# --- control ---------------------------------------------------------------
max_w: 2000
gain: 0.6
slew_w: 1000
deadband_w: 15
target_grid_w: -10
step_w: 10
saturation_w: 500
saturation_cycles: 3
heartbeat_s: 10
stale_input_s: 15
auto_start: false
# --- maintenance -----------------------------------------------------------
maintenance_enabled: false
maintenance_interval_days: 28
maintenance_start_hour: 10
maintenance_discharge_w: 2500
maintenance_charge_w: 2500
maintenance_soc_floor: 11
maintenance_soc_target: 99
maintenance_hold_min: 120
# --- tariff / capacity tariff (all optional) ------------------------------
peak_forecast_entity: ""
peak_cap_w: 3500
price_now_entity: ""
price_avg_entity: ""
# --- site ------------------------------------------------------------------
estop_fitted: false
log_level: info
schema:
meter_entity: str
meter_invert: bool
soc_entity: str
batt_entity: str
batt_invert: bool
setpoint_entity: str
max_w: int(100,5000)
gain: float(0.05,1.0)
slew_w: int(50,5000)
deadband_w: int(0,500)
target_grid_w: float(-200,200)
step_w: int(1,100)
saturation_w: int(100,2000)
saturation_cycles: int(1,10)
heartbeat_s: int(2,25)
stale_input_s: int(5,120)
auto_start: bool
maintenance_enabled: bool
maintenance_interval_days: int(1,90)
maintenance_start_hour: int(0,23)
maintenance_discharge_w: int(500,5000)
maintenance_charge_w: int(500,5000)
maintenance_soc_floor: int(5,30)
maintenance_soc_target: int(50,100)
maintenance_hold_min: int(5,480)
peak_forecast_entity: str?
peak_cap_w: int(500,15000)
price_now_entity: str?
price_avg_entity: str?
estop_fitted: bool
log_level: list(trace|debug|info|warning|error)