SAFETY-43: delinquency measured against the ask, not against a flat 500 W
`delivery.delinquent()` named a unit whose `short_by()` gap exceeded an
ABSOLUTE `min_w = Tuning.saturation_w = 500 W`. OPT-09's SoC-aware weights
shrink a low-headroom unit's share, and shrinking the share shrinks the gap, so
a unit standing at +125 W and delivering 0 W - 100 % delinquent - was never
named. Measured end to end on the real loop (test_packshare.py part 8b):

    load 1500 W, B wedged at 15 %, equal weights    named on 199/200 cycles
    load 1500 W, B wedged at 15 %, OPT-09 weights   named on   0/200 cycles

⚠️ The suppressed regime is the quiet one: at a load the healthy sibling covers,
the meter is satisfied, `unmet_w` is 0 and no action-log line fires, so this
alarm is the ONLY instrument that would have told the operator.

WHAT CHANGED, in one line:

    named if  short_by() > min_w  OR  short_by() > frac * share

⚠️ `min_w` WAS NOT LOWERED. It exists to stop normal saturation being reported
as delinquency, and lowering it trades a missed alarm for a false one on every
unit at once - SAFETY-41's four-attempt regime. This is a SECOND way to be
named, not a looser first one: all seven of test_delivery.py part 1's existing
fixtures answer identically under both rules, and the absolute arm's suppression
window is still exactly 1000 W / 6500 W, still asserted in part 8b.

THE FRACTION IS DERIVED, 0.85. admin/goodwe:sim/delivery_window.py gained a
`--fractions` axis and grades the constant over the SAME 2640 no-fault runs that
produced `delivery_hold_s`'s 35.0 s floor. Worst continuous legitimate episode,
worst of three families, twenty fractions:

    frac   0.05  0.10  0.15  0.20  0.25  0.30  0.35  0.40  0.45  0.50
    worst  90.0  90.0  70.0  70.0  60.0  55.0  55.0  60.0  45.0  45.0  s
    frac   0.55  0.60  0.65  0.70  0.75  0.80 *0.85  0.90  0.95  0.99
    worst  40.0  40.0  45.0  45.0  45.0  45.0  40.0  40.0  40.0  40.0  s
    absolute arm alone: 35.0 s (SAFETY-42 §3.3, reproduced in the same runs)

⚠️ NO CLIFF ANYWHERE: 0.45-0.99 is flat within one control cycle, and it is not
monotone - §3.3's own mechanism (c). ⚠️ "Zero false namings" is NOT achievable
at any fraction and the record says so; what is zero is false ALARMS - 90.0 s
worst against a 185 s hold, so nothing comes within 95 s of notifying anybody.
N=1 control 0.0 s at every fraction in all 2640 one-inverter runs; flapping
0.0 s in all 840.

DRIVEN. Part 8b pinned the SUPPRESSED behaviour and said "if it ever goes red
because the alarm fired, read the card that made it fire". It now grades BOTH
rules on one run - `share_frac=None` is SAFETY-42's rule exactly:

    OPT-09 weights, absolute arm alone   named on   0/200
    OPT-09 weights, the shipped rule     named on 200/200

POSITIVE CONTROL. Same fixture, same weights, same 125 W share, one legitimate
fact changed: a pack at its own 10 % cut-out is named on 0/200 (account() still
gates it), and a unit delivering HALF its share is named on 0/200.

N=1 BYTE-IDENTICAL, asserted: `plan()` handed a `weights` mapping that raises on
any read still answers identically at a roster of one, and the same mapping
raises at a roster of two; `delinquent()` answers {} on all 84 single-unit
(share, measured, rule) combinations including 0 of 125 W.

MUTATION, run on fresh :ro trees: M12 (drop the relative arm), M13 (frac -> 1.0)
and M14 (frac -> 0.05) are all red on named checks. The constant cannot move in
either direction unseen.

⚠️ CFG-07 gets ONE CONTROL CYCLE WORSE and is deliberately not fixed here: the
worst legitimate episode goes 35.0 -> 40.0 s, so the schema's `int(30,900)`
false-tripping band widens from [30,35] to [30,40]. CFG-07 should be re-derived
against 40.0 s.

No option value, no schema bound and no default changed. 27/27 suites green.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-08 03:14:16 +02:00

808 lines
48 KiB
Markdown
Raw Permalink Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# SAFETY-42 — a unit that stops delivering its share, the discriminator the card asked for, and why that discriminator does not exist
**Status: DECIDED 2026-09-06.** A new per-inverter check, `app/delivery.py`,
names an inverter that is **standing at a discharge share it is not producing**
while at least one sibling is not in that state and nothing this add-on can read
explains it. It **reports and does not act**. At a roster of one it is inert by
construction.
⚠️ **This record also FALSIFIES the discriminator the card proposed.** SAFETY-42
asked for *"saturation persisting past N while |grid error| stays above X, with N
and X derived"*. That predicate was built and run on the rig before anything was
written, and it fails in **both** directions — not for want of better N and X,
but because of what the quantity is. §2 is the measurement. This is the
SAFETY-39 shape: saying the criterion is wrong was worth more than five
near-misses at satisfying it.
Filed with SAFETY-42, card `6a9d498a49082c0086e525c1`.
---
## 0. What is uncovered, and why it is structural rather than a threshold
A unit delivering **0 W against a non-zero share** is seen by nothing:
| guard | why it is silent |
|---|---|
| [[SAFETY-30]] per-unit sign | gates on **opposition ≥ 250 W on both sides**. A unit at 0 W never opens it — it is not opposing, it is **absent** |
| SAFETY-30 site sign | the sum still **agrees with the meter in direction**; only the magnitude is short |
| [[SAFETY-31]] circulation | `Σ\|Bᵢ\| − \|ΣBᵢ\|` is **zero** when one unit does nothing — circulation needs two units pulling *against* each other |
| the saturation freeze | **fires** — and `clamp.py`:93-96 says of exactly this: *"A loop can be legally saturated all day — a cold pack, a curtailed inverter, an export limit — so a saturation-shaped alarm is one an operator learns to ignore"* |
So the one signal that does fire is the one this codebase documents as
unreadable, and that documentation is **right**. This card therefore needed a
different signal, not a louder one.
It is [[HW-01]]'s shape. On 2026-09-02 the comms subsystem failed and the power
stage went on executing its last instruction for **6 h 25 m** with all three
layers spectators. At N=2 the same fault leaves a healthy sibling regulating
alone, the site short by up to one unit's share, and nothing saying so.
## 1. The rig
Everything in §2 and §3 was measured on `admin/goodwe`'s two-master rig
(TEST-19), used **read-only** and run container-free, from a harness in a
scratch tree. Real and imported, never transcribed: the control law
(`control.compute`, `Tuning`), the allocator (`arbiter.allocate_record` →
`allocator.plan`), the per-unit envelope the shipped `supervised` and `device`
claims build, the sign predicate (`watchdog.disagrees`), the circulating sensor
(`circulation.circulating_w`), the check under test (`delivery.delinquent`,
`short_by`, `account`), the wire (`frame_check.setpoint_atomic`, the firmware's
own encoder, in and back out through `plantsim.parse`/`decode`), and the plant
(`plantsim.Plant`). The per-unit reading is **holding register 0x0518**, the one
the live `batt_entity` binds.
Modelled, and therefore not evidence about the thing modelled: the master's
failsafe machine (absent), and the two fault injections —
* **wedged** — the write never reaches the plant, so its latched command stands.
Started at 0 W, which is *"delivering 0 W against a non-zero share"*.
* **at its floor** — the write arrives and `Plant.limit()` zeroes it, because
`soc <= soc_min`. This is the benign case the acceptance criterion names.
### ⚠️ Inverter B does not physically exist
`plantsim.INVERTER_B` is **inverter A copied**, `measured=False` (NOTES.md
§1.1b; the datasheet-and-serial figures 4600 W / 20.48 kWh / floor 10 % are
deliberately *not* in the model). **Every two-inverter figure in this document
is two copies of inverter A.** §3.3 is the sensitivity sweep that sizes the
margin that costs.
### Reproducing it — ⚠️ THE HARNESS IS COMMITTED NOW (TEST-21, 2026-09-07)
⚠️ **THIS SECTION USED TO SAY THE HARNESS WAS NOT COMMITTED, AND THAT WAS THE
DEFECT TEST-21 FOUND.** A shipped safety constant whose floor the next reviewer
cannot re-run is PROC-01's shape, and PROC-01 had eleven instances in three
days. The paragraph this replaces was true — what the harness does *is* small
enough to restate — and it was not enough: a restatement in prose leaves every
axis it does not name to the next person's judgement, and §3.3 below now records
how far that moves the number. **It moved. See §3.3's second table.**
It is committed in the **other** repository, `admin/goodwe`, as
`sim/delivery_window.py`, beside `sitesim.py` — the container-free two-master
harness it is built on. From clean checkouts of both repos:
```
cd goodwe/sim
GOODWE_ADDON_REPO=/path/to/goodwe-addon python3 -B delivery_window.py --selftest
GOODWE_ADDON_REPO=/path/to/goodwe-addon python3 -B delivery_window.py --campaign --blag
```
stdlib only. No container, no HA, no esphome, **no rig and no rig lock** — it is
a `plantsim` campaign, not a rig job. About fifteen minutes for the whole thing.
⚠️ **AND IT IS IN `admin/goodwe` RATHER THAN HERE, WHICH IS CI-08's RULE
APPLIED RATHER THAN IGNORED.** It imports `plantsim` (the plant, the per-unit
wire, `Site`) and `frame_check` (the firmware's own encoder), both **owned by
that repo** and neither present in this one's CI image. Committed here it had
two possible fates and both are the coupling CI-08 has been broken by three
times: skipped for want of its imports — a green that establishes nothing — or
the plant and the encoder **restated in this tree**, which is a second copy of
something the other repo owns, free to drift, and drift in a fixture is
invisible until the number it defends is wrong. There the dependency runs one
way and stays one-directional: **this** repo's `control`, `arbiter` and
`delivery` are imported live out of whichever checkout is under test
(`$GOODWE_ADDON_REPO`), never copied — so a change to `delinquent()` moves the
number on the next run instead of silently disagreeing with a fixture. That is
the seam `sitesim.py` already stands on, which is the other reason the campaign
is its neighbour and not a third arrangement.
⚠️ **THE SELFTEST IS CI-GATED; THE CAMPAIGN IS NOT, AND THE SPLIT IS
DELIBERATE.** `admin/goodwe`'s `.gitea/workflows/checks.yml` gained one step —
`python3 -B delivery_window.py --selftest`, seconds, beside the existing
`norig, no lock` TEST-19 and TEST-20 steps, in the workflow that **already**
checks out this repo for `two_writers` and accepts that boundary in writing. So
a change **here** that moved `saturation_w`, `max_w`, `delivery_hold_s` or the
shape of `delinquent()` turns that step red rather than leaving a stale number
in this record. The **campaign** (`--campaign --blag`, ~15 minutes) is not
gated: it is a campaign, not a gate, and `failure-injection.yml`'s jobs run on
the **rig** runner, which a container-free simulation has no business holding.
What TEST-21 asked for is a command a reviewer can run from a clean checkout —
that is the block above.
⚠️ **`--selftest` IS A FALSIFIABILITY ARM, NOT A SMOKE TEST, AND IT RUNS
FIRST.** A campaign whose N=1 column and whose flapping column are 0.0 s
everywhere is indistinguishable from a campaign whose detector was never wired
up — `sitesim.broadcast_onset` exists for the same reason. So the selftest
drives a genuinely **wedged** unit through the same loop and refuses to proceed
unless the shipped `delinquent()` names it for longer than the shipped hold
(it names it for 275.0 s). Every 0.0 s in §3.3 is only worth reading because
that arm passes.
What it does, unchanged from the restatement it replaces: build two
`plantsim.Inverter`s from `INVERTER_A` / `INVERTER_B`; close the loop with the
add-on's own `compute()` on the SITE sum (`Controller.site_batt_w`) and
`arbiter.allocate_record()` over per-unit envelopes of `±min(max_w, rating)`;
put each share on its own wire through `Inverter.command()`, honouring a
configurable **write stagger** so B's number can land up to four cycles after
A's (the serialised write path); advance `Site.settle()` one control cycle; and
record, per unit, the command standing *before* the write and that unit's 0x0518
power. Then grade each cycle with the **shipped** `delivery.delinquent()` and
take the **longest run of consecutive cycles** on which it names anybody — not a
count of naming samples, because the window is cleared by any cycle that does
not.
⚠️ **SINCE [[SAFETY-43]] THE ROWS OF §3.3's TABLE ARE GRADED WITH
`share_frac=None`** — `delinquent()`'s ABSOLUTE arm alone, which is this card's
rule exactly. Said here because it is the difference between §3.3 still meaning
what it is labelled as and quietly becoming a table about a different predicate:
SAFETY-43 added a SECOND way to be named, the harness grades it in its own rows
(`--fractions`), and the numbers below are unchanged and were re-measured to
confirm it. `DECISIONS/SAFETY-43-delinquency-relative-to-the-ask.md` §3 carries
those rows and what they cost — the worst legitimate episode goes from 35.0 s to
40.0 s at the shipped fraction, which does not move `delivery_hold_s`.
⚠️ **ONE THING THE RESTATEMENT DID NOT SAY, AND IT IS LOAD-BEARING.** "The
command standing before the write" is the **controller's** standing command —
`Inverter.standing_w()`, i.e. `last_write` — and **not** the far end of the
wire. A write that has been issued but has not landed yet is standing as far as
this add-on is concerned, which is the whole of the write-stagger axis. Grading
against the plant's latch instead reads a number no add-on has, and it makes
both the stagger *and a wedged unit* invisible: a unit whose writes never arrive
shows a standing command of 0 W, is never `asked`, and is never named. That is
not a conservative harness, it is a harness that cannot fail — and the rebuild
did exactly this on its first run, which is how the falsifiability arm earned
its place above.
⚠️ MUTATION.md's note applies: this harness writes `__pycache__` into **both**
trees. Run it with `python3 -B` and purge.
## 2. The card's discriminator, measured — and it does not work
### 2.1 It fires on the benign case, and no (N, X) can stop it
`Plant.limit()` returns 0 W for a discharge command into a pack at its own
floor. A wedged unit that never receives its command also produces 0 W. The two
are not merely similar:
> **Load 2000 W, equal weights, 2000 W per-unit cap, 120 control cycles.
> The two arms are IDENTICAL on all 120 cycles** in (grid, site target, each
> unit's share, each unit's measured power), to the last emitted watt. Both
> report `reason == "saturated-freeze"` on **116 of the 120** cycles (the other
> four are `slew-limited`, before it engages on cycle 4), both hold |grid error|
> over 300 W on **all 120** and settle at **1200 W**, and `circulating_w` is
> **0.0 W** in both.
A predicate whose inputs are *saturation duration* and *|grid error|* reads the
same number on both arms at every cycle. There is no N and no X. And *"a
legitimately saturated site — cold pack at its floor — does **not** alarm"* is
this card's own acceptance criterion.
`test_delivery.py` part 4 asserts that identity on the add-on's own end-to-end
fixture, so it goes red if it ever stops being true.
### 2.2 It is silent on the headline case, because a healthy sibling erases it
The standing grid error is exactly the thing a working sibling removes.
> **Load 800 W, equal weights, 2000 W per-unit cap, B wedged, 200 cycles.**
> Over the last 30 cycles the loop is saturation-frozen on **30 of 30** — so
> "saturation persisting past N" is true for every N — while the worst
> **|grid error| in that window is 30 W**. B is standing at a **+770 W**
> discharge share and delivering **0 W**.
Any X above 30 W leaves the card's predicate silent for the whole run, on the
exact fault it was written for. The card's own sentence — *"a healthy sibling
regulating alone, the site short by up to one unit's rating"* — describes the
case, and the grid error is the one number that cannot report it.
### 2.3 What that leaves
The derivation instruction stands and is honoured in §3. What could not be
derived was a threshold on the wrong quantity. Both failures are written into
`delivery.py`'s docstring as well, because the next person to read the card will
propose the same predicate.
## 3. The quantity that does work
Per unit, for a share that asks it to **discharge**:
```
short_by(i) = share_i − measured_i # watts that did not arrive
```
and the reduction that makes it readable:
> a unit is **delinquent** while it is short by more than `saturation_w` with
> **no account for it**, and the set of units in that state is a **proper
> subset** of the units that were asked to discharge.
### 3.1 The account — the only thing that separates a wedged unit from a cold pack
§2.1 says there is nothing in the power domain. There is exactly one non-power
fact this add-on holds about a pack: **its own state of charge against its own
`bms_soc_floor`**, which SAFETY-32 made a required per-entry key. `account()`
asks it through **`peakguard.discharge_permitted()`** — public since SAFETY-32
precisely so that this question has one answer — and writes its own sentence,
because that function's wording names the *peak guard's* floor and would be a
false statement here.
Three things account for a shortfall, and each is a state already being handled:
| account | why it is not this fault |
|---|---|
| the unit is not live | `live_units()` has already dropped it from the split and the action log says so — firing inside that is the SAFETY-15/19 failure |
| the unit is parked by a sign trip | it is commanded 0 W on purpose; not delivering is compliance |
| `discharge_permitted(soc, bms_soc_floor)` | the pack is at or below its own cut-out and physically cannot |
⚠️ **The floor passed in is `bms_soc_floor` alone, NOT
`peakguard.pack_floor_pct()`'s conjunction with `peak_soc_floor`.** That
conjunction is right for the peak guard and wrong here: `peak_soc_floor` bounds
a money-saving discharge only (SAFETY-25), ordinary self-consumption discharges
straight past it, and using it would **explain away** a wedged unit sitting
anywhere between the two floors.
⚠️ **Every unknown accounts for the shortfall**, i.e. fails toward silence —
the opposite direction to `discharge_permitted()`'s own caller, and the right
one here: there it withholds a discharge, here it withholds an **alarm**. The
cost is bounded, because the same absence stops the site through `inputs_ok`
(an unreadable SoC) or is refused by the roster schema (an unstated floor).
### 3.2 The proper subset — what only exists at N ≥ 2
A derate this add-on cannot see — thermal, grid-code, a DC-side restriction —
hits **every** unit that was asked. One box that has stopped listening does not.
So if every asked unit is short and unexplained, this module says **nothing**:
it has no instrument that tells that from a plant which simply cannot deliver,
and reporting it anyway would be the saturation-shaped alarm produced by the
guard written to replace it.
**At N = 1 the subset is never proper, for every input**, so the check is inert
there — not by a roster guard, but by the algebra, the same way
`circulation.circulating_w()` is identically zero at N ≤ 1. That is AC 5, and
§3.3's control arm measures it rather than asserting it.
### 3.3 The window — the one number this card chose
**2640 closed-loop runs at a roster of two in which NOTHING is faulty** — every
unit executes the share the allocator gave it — over 6 gains × 5 slews, the
whole range `config.yaml` accepts for `gain` `float(0.05,1.0)` and `slew_w`
`int(0,5000)` (0 = follow the rail), across three families:
* **1050 load reversals** — 7 sizes (±300 W … ±5000 W) × 5 write staggers;
* **840 flapping loads** — 7 periods (10 s … 600 s) × 4 amplitudes;
* **750 weighted reversals** — 5 splits (0.5, 0.7, 0.9, 0.99, 0.1) × 5 staggers
on a ±2200 W reversal. ⚠️ **This family did not exist in SAFETY-30's campaign
and it is the one that dominates here**, for a mechanical reason: an
asymmetric split gives one unit a much larger step than its sibling, so the
big one is still ramping while the small one has settled — which is precisely
the *proper subset* this check keys on.
Every run is executed a second time at a **roster of one** on the same stimulus.
**The N=1 arm is the control**, and it is what separates *"a property of the
check"* from *"a property of the second inverter"*.
Worst **CONTINUOUS** legitimate episode, as a function of the shortfall
threshold. **ORIGINAL CAMPAIGN, 2026-09-06, from the harness that was not
committed — SUPERSEDED, and kept here because a record that quietly replaced its
own numbers would be worth less than one that shows both:**
| threshold | reversals (of 1050) | flapping (of 840) | weighted (of 750) | **N=1 control (1890 runs)** |
|---:|---:|---:|---:|---:|
| 100 W | 40.0 s (608) | 0.0 s (0) | 75.0 s (576) | **0.0 s (0)** |
| 250 W | 55.0 s (490) | 0.0 s (0) | 60.0 s (480) | **0.0 s (0)** |
| **500 W** | **20.0 s (206)** | **0.0 s (0)** | **30.0 s (368)** | **0.0 s (0)** |
| 700 W | 20.0 s (125) | 0.0 s (0) | 20.0 s (174) | **0.0 s (0)** |
| 1000 W | 15.0 s (70) | 0.0 s (0) | 15.0 s (111) | **0.0 s (0)** |
| 1500 W | 10.0 s (51) | 0.0 s (0) | 10.0 s (50) | **0.0 s (0)** |
| 2000 W | 10.0 s (24) | 0.0 s (0) | 5.0 s (23) | **0.0 s (0)** |
#### ⚠️ TEST-21, 2026-09-07 — THE RE-RUN, AND 30.0 s DID NOT REPRODUCE
`admin/goodwe:sim/delivery_window.py --campaign`, same three families, same
counts, same thresholds, the shipped `delinquent()`:
| threshold | reversals (of 1050) | flapping (of 840) | weighted (of 750) | **N=1 control (2640 runs)** |
|---:|---:|---:|---:|---:|
| 100 W | 120.0 s (770) | 0.0 s (0) | 165.0 s (685) | **0.0 s (0)** |
| 250 W | 65.0 s (687) | 0.0 s (0) | 100.0 s (590) | **0.0 s (0)** |
| **500 W** | **30.0 s (460)** | **0.0 s (0)** | **35.0 s (403)** | **0.0 s (0)** |
| 700 W | 25.0 s (342) | 0.0 s (0) | 30.0 s (318) | **0.0 s (0)** |
| 1000 W | 15.0 s (4) | 0.0 s (0) | 25.0 s (131) | **0.0 s (0)** |
| 1500 W | 0.0 s (0) | 0.0 s (0) | 20.0 s (43) | **0.0 s (0)** |
| 2000 W | 0.0 s (0) | 0.0 s (0) | 0.0 s (0) | **0.0 s (0)** |
**The floor is 35.0 s, not 30.0 s** — weighted family, and the worst single run
is `gain=0.2 slew_w=1000 stagger=4 split=0.10/0.90` on the ±2200 W reversal. The
argmax is printed with the table on purpose (see below): a worst case sitting on
an edge of the grid would be a number about the grid.
⚠️ **AND BY THAT STANDARD, TWO OF ITS FOUR AXES ARE ON AN EDGE. Measured, at the
argmax's other axes held fixed:**
stagger 0 -> 1 -> 2 -> 3 -> 4 0.0 15.0 25.0 30.0 35.0 s
weights (A) at stagger 4 0.5 -> 20.0 0.7/0.9/0.99 -> 0.0
0.10 -> 35.0 s
Strictly increasing in stagger and maximal at 4, the largest modelled stagger;
and maximal at the most asymmetric split. It is interior only in `gain` (2nd of
6) and `slew_w` (3rd of 5).
⚠️ **SO THE HEADLINE IS 0.0 s AT stagger=0, AND 35.0 s IS ENTIRELY A PRODUCT OF
THE MODELLED SERIALISED-WRITE STAGGER.** That stagger is declared MODELLED at
`sim/delivery_window.py:60-64` — it is a term of this figure, not a detail of
it. A site whose two writes land in the same cycle does not produce this episode
at all.
This does not move `delivery_hold_s`: 185 s must cover the worst case the
modelled site can produce, and a stagger of four cycles is inside what a real
two-inverter write path can do. But a reader entitled to ask "is 35.0 s about
the plant or about the grid?" deserves the answer, and the answer is: **partly
about the grid, and the grid's shape is the record's own, fixed by §3.3 before
this rebuild ran.** Found in review of TEST-21; the PR body had claimed the
argmax was interior, and it is not.
**WHAT REPRODUCED, EXACTLY:**
* the **N=1 control column is 0.0 s at every threshold**, in every run. That is
§3.2's algebra measured, and it is the claim the compatibility promise rests
on. (This rebuild ran the control arm over all three families — 2640 runs —
where the original ran 1890, i.e. the two families whose stimulus is not
weighted. The weighted stimulus at a roster of one is the same stimulus with
inert weights, and it too reports nothing at any threshold.)
* the **flapping family is 0.0 s at every threshold**, in all 840 runs. The
proper-subset rule really does defeat the family that defeated SAFETY-30's
site window.
* **45.0 s at twice A's lag**, to the cycle. See the B-lag table below.
**WHAT DID NOT:**
* the headline. **35.0 s against a recorded 30.0 s** — one control cycle worse,
and 20.0 s → 30.0 s on the reversal family, two cycles worse.
* **the non-monotonicity.** §3.3 finding 3 read the original 55.0 s at 250 W
against 40.0 s at 100 W as a property of the reduction. **This rebuild's
curve is monotone decreasing on both N=2 families.** The *mechanism* finding 3
describes is real and is still the reason not to read either table as a
sensitivity curve — lowering the threshold really can turn a proper subset
into the whole roster and break the run — but **this grid does not exhibit
it**, so the claim now rests on the mechanism alone and no longer on a
measurement. That is a weaker claim than the one this record made, and it is
written down as weaker.
* the low-threshold rows, badly: 120.0 s / 165.0 s at 100 W against 40.0 s /
75.0 s. Nothing ships at 100 W, but the size of that gap is the honest measure
of how much of the original table was a property of axes nobody wrote down.
⚠️ **WHY THE NUMBERS MOVED, AS FAR AS IT CAN BE ESTABLISHED.** §3.3 fixes the
*counts* of every axis (6 gains × 5 slews; 7 reversal sizes; 7 flap periods × 4
amplitudes; 5 staggers; and the 5 splits, which it lists) and the *ranges*
(`config.yaml`'s `gain` `float(0.05,1.0)` and `slew_w` `int(0,5000)`). It does
**not** fix the individual values, the run length, or the per-unit cap. The
rebuild spread them over the admissible ranges and **prints every one of them
above its own table**, so the caveat travels with the number instead of living
in somebody's memory. The residual disagreement — one to two control cycles at
the shipped threshold — is inside the sensitivity to that choice; the
low-threshold rows are not, and are reported as not.
⚠️ **AND THE HARNESS WAS NOT ADJUSTED UNTIL IT AGREED.** The one substantive
correction made during the rebuild was made *against* the doc's number, not
towards it, and it is recorded in §1: grading on the plant's latch rather than
the controller's standing command produced a harness that could not name even a
wedged unit. Fixing that made the numbers **larger**. Nothing else was tuned.
Findings 1-3 below are the original campaign's, kept with finding 3 now
qualified by the re-run above:
1. **The N=1 column is zero everywhere, in all 1890 runs and at every
threshold.** That is the compatibility promise measured, not argued.
2. **The flapping family is zero everywhere too** — and it is the family that
defeated SAFETY-30's site window (980 s at two inverters, 1000 s at one, no
window inside the billing quarter surviving it). It cannot touch this check,
because a common stimulus makes both units short at the same time and the
subset stops being proper. That is the proper-subset rule earning its place
on a case it was not designed for.
3. **The curve is NOT monotone** — 55.0 s at 250 W against 40.0 s at 100 W —
and that is a property of the reduction rather than noise: lowering the
threshold puts MORE units into the short set, which can turn a proper subset
into the whole roster and **break** the run. Both the numerator and the
denominator move. Do not read this table as a sensitivity curve.
#### The watts side is not a new option — it is `Tuning.saturation_w`
`main.py` hands the check `self.tuning.saturation_w` (500 W) and there is no
`delivery_w` key anywhere. That is a derivation, not a saving:
* it is already **the gap at which `compute()` itself concludes the inverter is
not following** and freezes the integrator. Below it the shipped control law
calls the divergence ordinary tracking, and an alarm under a threshold the
control law calls normal is an alarm about nothing;
* `saturation_cycles` (3) consecutive cycles over that same gap are needed
before the freeze engages, so **every cycle this counts is a cycle the freeze
has already seen**. This is a reduction over the freeze's input, not a second
opinion about it;
* CFG-03 already tracks three places a default has to be kept in step. A fourth
copy could drift, and the drift that matters has a direction: an operator who
raises `saturation_w` has told the loop that a bigger gap is ordinary
tracking, and a check that stayed put would then alarm on it.
**Rejected:** a `delivery_w` option, for the three reasons above. A margin above
`saturation_w` (the way `circulation_w` sits 1.75× above its knee) was also
rejected: there is no knee here — the table above is not monotone — so a margin
would be a preference, and all the margin this check needs is in the window.
#### `delivery_hold_s: 185` — schema `int(30,900)`
Four bounds, and the value clears all four.
* **lower, from the rig — 35.0 s** (TEST-21, 2026-09-07; **the original record
said 30.0 s and it did not reproduce**). The worst continuous legitimate
episode at the shipped threshold across all 2640 runs — weighted family, worst
single run `gain=0.2 slew_w=1000 stagger=4 split=0.10/0.90` on the ±2200 W
reversal; 30.0 s on reversals, 0.0 s on flapping. Re-run it with
`admin/goodwe:sim/delivery_window.py --campaign` (§1).
⚠️ **THIS IS NOW STRICTLY THE BINDING LOWER BOUND, WHICH IT WAS NOT BEFORE.**
At 30.0 s it coincided with the firmware's veto below and a reader could not
tell which of the two was doing the work. At 35.0 s the rig's number is on its
own, above the firmware's — so **the rig is what stops `delivery_hold_s` going
low**, and the schema's `int(30,900)` floor no longer sits above the worst
legitimate episode. An operator who sets it to the schema minimum of 30 s is
now **below** a measured legitimate episode and will get false reports; the
option is marked *derived, do not change* and this is what that marking is
for. Raising the schema floor to 35 is a change to a shipped option's
contract and is left to its own card rather than smuggled in here.
* **lower, from the firmware — 30 s (`inverter.LINK_STALE_S`).** A unit not
executing its share for less than the firmware's own veto window is a *link*
fault the add-on already answers by dropping it from the split. Reporting
inside that window would be a second, louder alarm about a state already
being handled — the SAFETY-15/SAFETY-19 failure exactly.
* **margin, from inverter B not existing.** ⚠️ **THIS ROW IS A SENSITIVITY
STUDY ON A HYPOTHESIS ABOUT B, NOT A MEASUREMENT OF B, AND THE ORIGINAL
WORDING ("MEASURED, not felt") OVERSTATED IT.** Inverter B is not installed
(~2026-09-12; NOTES.md §1.1b). The campaign's B is **A copied**, `measured=
False`, so the 35.0 s above is **two identical machines** and every row below
is a *what-if*: what a slower second unit would cost this window. **No row
here is B's lag.** What it is genuinely evidence for is the SHAPE of the
margin — which term the window has to be sized against — and that is what it
is used for. Sweeping a *different* second unit through the weighted family
(750 runs each). Second column is the original record, third is TEST-21's
re-run with the committed harness (`--blag`):
| B lag | B ramp | 2026-09-06 (uncommitted) | **TEST-21 re-run** | runs naming |
|---:|---:|---:|---:|---:|
| 10.0 s (A) | 800 W/s (A) | 30.0 s | **35.0 s** | 403/750 |
| 20.0 s | 800 W/s | 45.0 s | **45.0 s** | 454/750 |
| 10.0 s | 400 W/s | 30.0 s | **35.0 s** | 411/750 |
| 20.0 s | 400 W/s | 45.0 s | **50.0 s** | 454/750 |
| 40.0 s | 200 W/s | 90.0 s | **75.0 s** | 478/750 |
**The LAG moves it roughly linearly and the RAMP barely moves it**, which is
the original finding and it survives — with one correction: *"the RAMP does
not move it at all"* is too strong. Halving the ramp is worth 0 s at A's lag
and **+5 s at twice it** (45.0 → 50.0), so the ramp is a second-order term
rather than no term. The shortfall lasts as long as the unit's first-order lag
holds it more than `saturation_w` below its share; at these step sizes the
ramp is rarely the binding one. So the number to carry margin against is still
B's lag — and a hypothetical unit **four times slower than A** produces
**75.0 s**, where the original record said 90.0 s. ⚠️ Note the direction: this
row moved **in the margin's favour**, while the floor above moved against it.
Neither was adjusted to suit the other.
* **upper, from the bill — 900 s**, the quarter that sets the capacity tariff.
**185 s** is thirty-seven control cycles. Against the TEST-21 re-run it is
**5.29×** the measured worst legitimate episode (35.0 s), **2.47×** the
hypothetical four-times-slower second unit (75.0 s), **6.2×** the firmware veto
(30 s) and **4.9×** inside the quarter (900 s). ⚠️ Deliberately **not 180** —
that is SAFETY-02's site hold, and a reader must not be able to think this was
carried across — and not 150 or 200.
⚠️ **185 STANDS, AND HERE IS THE ARITHMETIC RATHER THAN THE ASSURANCE.** The
record claimed 6.2× the measured worst; the re-run makes that **5.29×**. All
four bounds still clear, none of them narrowly, and the *ordering* of the
argument is unchanged: the rig's floor is the binding one, the quarter is the
ceiling, and 185 sits between them with margin at both ends. So the value is
**not changed** — a shipped safety constant is not moved because its margin
went from 6.2× to 5.3× while every bound still holds, and moving it would
invalidate SAFETY-41's four-attempt false-trip regime for nothing. What IS
changed is the claim: this record no longer says 6.2×, and no longer says 30.0
s, because neither is what the harness produces.
**What it costs, stated rather than hidden:** up to 185 s of a site running
short by one unit's share before anybody is told. Against a fault that ran
6 h 25 m unnoticed, and against a guard that takes **no action**, the window
buys its margin with reporting latency and nothing else.
## 4. It reports. It does not act — and the strongest argument is for acting
Card requirement 3 asks which, and why. The answer is recorded with the
evidence **against** it first, because "alarm-only" is the weaker-looking answer.
**Command it harder — no.** HW-01 settles it: the power stage executed its last
instruction for 6 h 25 m through every command this add-on sent. A command is
not a remedy for a box that is not listening.
**Stop the site, as SAFETY-31 does — no**, and the asymmetry with SAFETY-31 is
exact. Circulating power is stopped because *this controller is one of the two
participants*: removing our half halves the loop and un-hides the residue at a
meter that was netting it to zero. Here this controller is **not** a participant,
nothing is netting, and the sibling is the only thing still delivering. Parking
it takes the site from "short by one unit" to "short by all of them".
**Re-allocate its share to the sibling — no, and NOT because the loop already
does it.** That comfortable answer is false, and the rig says so. Dropping the
wedged unit from `live` — the mechanism `live_units()` already uses for a dead
link — is a real improvement at loads the site cannot cover on one unit's
*share*:
| B wedged, per-unit cap 2000 W | kept in the split | dropped from the split |
|---|---|---|
| load 800 W | settles inside 100 W from cycle 6 | from cycle 8 |
| load 1500 W | **800 W delivered, 700 W error, NEVER inside 100 W in 150 cycles** | 1500 W delivered, inside 100 W from cycle 14 |
| load 2000 W | **800 W delivered, 1200 W error, never settles** | 2000 W delivered, inside 100 W from cycle 8 |
The mechanism is the saturation freeze doing its job on a site comparison that a
non-delivering unit has poisoned: `|site target − site batt|` stays over
`saturation_w` forever, so the target cannot rise and the sibling's *share*
never grows. That is not three cycles of latency; it is the difference between a
site that recovers and one that does not.
**What refuses it anyway** is that the only re-allocation this add-on can
express is **all or nothing**. There is no way to say *"give the sibling the
watts that did not arrive and leave this unit the ones that did"*. And a unit
delivering **part** of its share is short by more than `saturation_w` too, with
nothing here to explain it — so this detector names it, and cannot tell a 50 %
derate from a wedged box, because no instrument this add-on has can:
| B derated to 50 %, load 3000 W, cap 2000 W | site delivers | B contributes | grid error |
|---|---:|---:|---:|
| kept in the split | 2400 W | 800 W | 600 W |
| **dropped** | **2000 W** | **0 W** | **1000 W — 400 W worse** |
**SAFETY-42 names B in that run.** So the remedy would make the site worse, in a
case the detector cannot rule out, on a live control law, driven by a brand-new
alarm. A **partial** re-allocation is what would make acting safe, and the
allocator has no way to express it today. That is a card, and this section is
its evidence.
`test_delivery.py` part 5 asserts the decision as a **counterfactual** rather
than by reading the code: the same fixture run with the report tripping and with
it never tripping produces byte-identical grid, site target, shares and measured
power on every cycle.
## 5. Requirement 4: the saturation freeze is untouched
`control.py` is not modified by this card, at all. The freeze still shapes the
loop; this reports on it. `test_delivery.py` part 6 asserts what each
neighbouring guard concludes on the same fixture — SAFETY-30 per-unit silent,
SAFETY-30 site silent, SAFETY-31 identically zero, the freeze firing at the
same counter on **both** arms — which is the honest version of "every existing
guard is silent", including the one that is not.
## 6. Surviving a restart (SAFETY-34)
`persistent_notification` is **in memory**. Home Assistant restarts, the card is
gone, and the fault runs on — precisely how the 2026-09-02 outage went unseen
for 6 h 25 m with the detector correct throughout. It matters more here than
anywhere else in this add-on, because SAFETY-02 and SAFETY-31 at least leave a
**stopped** site for somebody to notice; this one leaves a site that looks like
it is working.
* durable half: `unit/<name>/delivery_tripped` / `delivery_reason`, namespaced
per unit for `store.unit_key()`'s reason, written **reason first**.
* visible half: `_delivery_announced`, a per-**process** set of unit names,
deliberately not persisted. A restart empties the set and keeps the latch, so
the alarm is re-raised on the first cycle of every process — **one code path**
for a fresh trip and for a restart into an existing one, `check_circulating()`'s
argument.
* **no flat mirror**, where SAFETY-02 has one. `store.py`'s rule 2 keeps the flat
keys so a rollback still finds its latch, and the version being rolled back to
drives exactly one actuator — a roster at which this check is inert.
* one **notification id per unit**, built from the same `unit_slugs()` TEL-07
announces the MQTT entities under. Two wedged inverters must produce two cards,
not one replacing the other.
* it **latches**, and not for SAFETY-02's reason. Nothing here removes its own
evidence, because nothing here changes what is commanded. It latches so that a
unit which stopped delivering for minutes and then resumed cannot erase its own
record — the intermittent fault is the one an operator most needs told about.
Cleared by the same **Start** press as the others.
* the status row is `ok: False, warn: True` — this list's **caution**. Every
other latched row means the site is at 0 W and a red cross is the truth; this
one means the site is still running and quietly short, and a red cross would
say the controller had stopped.
## 7. What this does NOT catch, said plainly
* **Charge shares are not graded.** The account gate needs a bound this
controller reads in the commanded direction. There is one for discharge
(`bms_soc_floor`, required of every roster entry since SAFETY-32) and **none**
for charge. A pack in constant-voltage taper legitimately takes hundreds of
watts less than it is told for tens of minutes, and arming that direction would
fire on the taper of every §12 maintenance charge. The same fault in the other
direction wants the same treatment; what it needs first is a per-pack charge
ceiling this add-on does not have. **That is a card.**
* **Every unit wedged at once is not caught.** The subset is not proper, and
there is no instrument here that separates that from a plant which simply
cannot deliver. The site is short at the meter in that case, which is where the
existing guards can see it.
* **A pack that refuses above its configured floor is reported.** That is
deliberate: either the unit has stopped delivering, or `bms_soc_floor` does not
describe that battery. The notification says both, in those words.
* **A unit with a share of 0 W is not graded**, and neither is it a peer. With
only one unit asked to discharge there is nothing to compare against.
## 8. Mutation ledger
Every run on a **freshly copied tree of its own, `__pycache__` purged and the
count printed, mounted `:ro`, `python3 -B`** — MUTATION.md's rule, followed
because the first SAFETY-30 battery reused one directory, a container mounted it
mid-copy, read a missing `config.yaml` as a failing check, and the whole run was
discarded. **The baseline is green** (23/23) or nothing below is a result. Byte
deltas measured, not estimated; the `+0 B` ones are marked, since a
size-preserving edit is what TEST-15 turned into a false survivor once already.
| # | file | mutation | Δ | result |
|---|---|---|---|---|
| M1 | `delivery.py` | the SoC account removed — a cold pack at its floor alarms | −31 B | **RED** — `test_delivery.py`. This is the card |
| M2 | `delivery.py` | the proper-subset rule removed — a whole-site cause names every unit | −34 B | **RED** |
| **M3** | `delivery.py` | **the `len(asked) < 2` fast path relaxed to `< 1`** | **+0 B** | **SURVIVOR — and an EQUIVALENT MUTANT.** See below |
| M4 | `delivery.py` | the strict bound relaxed to `>=` — a gap the control law calls tracking is named | +1 B | **RED** |
| **M5** | `delivery.py` | `share <= 0` relaxed to `share == 0` — charge shares graded | **+0 B** | **SURVIVOR on the first battery — GAP CLOSED**, then **RED**. See below |
| M6 | `delivery.py` | `delivery_hold_s` 185 → a round 300 | **+0 B** | **RED** — the CFG-03 pin |
| M7 | `main.py` | the watts threshold no longer `Tuning.saturation_w` (×4) | +6 B | **RED** |
| M8 | `main.py` | the latch never persisted — nothing survives a restart | −35 B | **RED** |
| M9 | `main.py` | `_delivery_announced` never set — one notification per cycle | −34 B | **RED** |
| M10 | `main.py` | `peakguard.pack_floor_pct()`'s conjunction with `peak_soc_floor` used instead of the pack's own cut-out | +151 B | **RED** — the between-the-floors fixture |
| **M11** | `main.py` | **`inv.is_live(now)[0]` replaced by a literal `True`** | −15 B | **SURVIVOR at review — GAP CLOSED**, then **RED**. See below |
| M12 | `inverter.py` | the latch not restored from the store on start-up | −46 B | **RED** |
**11 of 12 red. One survivor, argued rather than left.**
### M5 was a real gap, and the two obvious checks did not close it
`test_delivery.py` already asserted `short_by(-2000, 0) is None` and
`short_by(-2000, -100) is None` — and **both stayed green under the mutant**.
For a charge share that is *under*-delivered, `share − measured` is negative and
the `gap > 0` test answers `None` anyway, so those two inputs cannot separate
`share <= 0` from `share == 0`. The one input that can is a unit moving **more**
than its charge share — `-2000 W` told, `-3000 W` measured, `share − measured` =
`+1000 W` — which the mutant reports as a shortfall. It is not one; it is
something else driving that pack, which is SAFETY-30's and SAFETY-31's question.
The check now uses that input and the mutant is red.
This is MUTATION.md's third failure mode in miniature: **the assertion ran, the
sentence was true, and the data could not reach the failure it named.**
### M11 was a wiring gap the pure checks structurally could not see
`account(live=False, …)` was already graded — as a **function**. What was not
graded was that `cycle()` actually *asks* `inv.is_live(now)`, and replacing that
call with a literal `True` left every check green, because **no fixture had a
unit whose writes were being rejected**. A dropped unit still has its last
*accepted* command standing on the wire (`write_setpoint` leaves `last_write`
alone on a rejected write) and still measures nothing, so it looks exactly like a
wedged one to every number this check reads — and reporting it would be the
second, louder alarm about a state already being handled that this module takes
its 30 s floor from. `test_delivery.py` part 6 now builds that unit (with
`rejected_since` back-dated past `LINK_STALE_S`, because the fixture runs in two
seconds and the timer is `test_inverter.py`'s to grade) and the mutant is red.
### M3 is recorded as a survivor because it is one — and it is EQUIVALENT
`len(asked) < 2` → `len(asked) < 1`. With **one** asked unit, `unaccounted` is a
subset of a one-element set, so it is either empty — `not unaccounted` returns
`{}` — or equal to `asked` — `len(unaccounted) == len(asked)` returns `{}`.
There is no third case, and with **zero** asked units both spellings return `{}`
as well. **No input separates them**, so no check can, and one written to try
would be a check about nothing.
⚠️ **And finding it corrected the module's own docstring, which is the more
useful half.** That paragraph claimed `len(asked) < 2` was *what makes N=1
inert*. It is not: the **proper-subset rule** is, and the line is a fast path and
a signpost. A false attribution of the mechanism in the file's own prose is
exactly what this repository keeps finding, and a mutation that survives is how
it surfaced. The line stays — it tells a reader at a glance that a one-inverter
install never reaches any of this — with the equivalence written down beside it,
the way `circulation.circulating_w()` records its own `max(0.0, …)`.
### Not separately mutated, and said rather than left implicit
`account()`'s `parked` branch is graded as a function (part 1) but its **wiring**
— `parked=inv.sign_wd.tripped` — is not mutated on its own. Part 6's reversed-unit
fixture exercises the path end to end and asserts the account it produces, which
is weaker than a mutation and is stated as such.
## 9. Round 2 — the thresholds this check reads, and which of them are pinned at a **changed** config
Everything in §8 mutated the *logic*. This section asks a narrower question that
§8 never asked, and it found two live survivors of the whole 23-file suite:
> for each number `main.py` hands this reduction, is the check still red when
> that number is replaced by a **literal equal to the value the fixtures use**?
That is not pedantry about style. Two of these numbers are **options**, and
`delivery.MIN_W_IS_SATURATION_W` and the `delivery_hold_s` block in `config.yaml`
both make a promise about them *in shipped, operator-readable prose*: there is no
fourth copy of a default to keep in step, and no way for the two to drift,
because an operator who raises `saturation_w` has told the loop that a bigger gap
is ordinary tracking. A literal at the call site keeps every fixture green and
removes exactly that promise — and the promise is why the design was chosen over
a fourth option key.
### The enumeration
| # | what the call site reads | mutated to | Δ | before round 2 | now |
|---|---|---|---|---|---|
| R5 | `self.tuning.saturation_w` | `250.0` | −19 B | **SURVIVED all 23 suites** | red — part 4b(a) |
| R6 | `bms_floor=inv.bms_soc_floor` | `10.0` | −13 B | **SURVIVED all 23 suites** | red — part 4b(b) |
| R7 | `arm(self.delivery_cfg)` | `arm(DeliveryConfig())` | −1 B | red | red — part 4 already ran at a hold of 1 s, not the shipped 185 s |
| R8 | `inv.is_live(now)[0]` | `inv.is_live(now, 3600.0)[0]` | +8 B | red | red — part 6's link-dead fixture |
| R9 | `bms_floor=inv.bms_soc_floor` | the **conjoined** floor, `max(pack cut-out, site peak_soc_floor)` | +105 B | red | red — and now red **twice**: the pre-existing between-floors check at shipped floors, and part 4b(b)'s shallow arm at a cut-out that is not shipped |
**R7 and R8 were already pinned across a changed setting, and R5 and R6 were
not.** The difference is entirely in the fixtures, not in the code:
`delivery_hold_s` had to be moved off 185 s for any of this file to run inside a
two-second test, and part 6 had to back-date `rejected_since` past
`LINK_STALE_S` to build a dropped unit at all. Nothing ever forced
`saturation_w` off 500 or a `bms_soc_floor` off 10 — so those two sat at the
shipped value in every fixture, and a literal equal to the shipped value is
invisible to a fixture that only ever uses the shipped value. **That is this
repository's recurring defect stated in one line: a fixture whose values cannot
reach the failure it names.**
`LINK_STALE_S` (R8) is the one number here with **no option behind it** — it is a
module constant in `inverter.py` and no test reassigns it — so "pinned across a
changed config" is not available for it, and is not claimed. What part 6 pins is
that *widening* the window changes the answer. Spelling `is_live(now, 30.0)` at
the call site would be an equivalent mutant today and would only drift if the
constant moved, which is a source change and not a config change.
### Why R5 and R6 are not equivalent mutants — the inputs that separate them
Both are separating inputs found by asking where the shipped answer and the
literal's answer can differ, and both are configs the shipped schema accepts.
**R5, watts.** Two copies of inverter A, B wedged, `saturation_w: 1800` (inside
its own schema `int(100,2000)`), load 1600 W. B's standing share and its
shortfall then land strictly **between** `250.0` and the configured 1800 W:
* head → `named = {}` — the operator raised the threshold and this check moved
with them, which is the whole promise;
* R5 → `named = {inverter-b}` — an alarm at a gap the control law has been told
is ordinary tracking.
At the shipped `saturation_w: 500` **both** name it, which is why every fixture
in part 4 is blind: their gaps are all above both thresholds.
**R6, percent.** The literal is invisible because `bms_soc_floor: 10` is what
`config.yaml`'s own `inverters:` example states and what every fixture in
`test_delivery.py` used. Two arms, on either side of it, both inside the schema
`int(0,50)` and both `validate.py` rule-8-valid:
* a pack at **15 %** against its own **25 %** cut-out is genuinely cold. Head
stays silent; R6 grades it against 10 %, finds it "permitted", and **names an
empty pack** — the crying-wolf failure this card exists to remove.
* a pack at **8 %** against its own **5 %** cut-out is genuinely wedged. Head
names it; R6 grades it against 10 %, calls it a cold pack, and **loses the
fault**.
One arm on each side is what leaves no constant at all: a single deeper arm
kills `10.0` but not `50.0`, a single shallower arm kills `10.0` but not `0.0`.
The two arms are byte-identical in the power domain on every cycle — the
configured cut-out is the only thing that differs, which is §3.1's claim made
again at cut-outs that are not the shipped one.
### What is still not pinned this way, said rather than left implicit
`parked=inv.sign_wd.tripped` and `standing[inv.name]`/`inv.batt` are wiring, not
thresholds: there is no "value the fixture happens to use" for a boolean or for a
measurement, so this question does not apply to them, and §8's last note already
records that the `parked` wiring is graded end-to-end rather than by mutation.