SAFETY-10: shadow mode - the whole decision path runs and nothing reaches the inverter #89

Merged
admin merged 1 commits from SAFETY-10 into release/1.0 2026-09-14 17:44:27 +02:00
1 Commits
Author SHA1 Message Date
Claude 8fa4febfef SAFETY-10: the whole decision path runs and nothing reaches the inverter
checks / unit (pull_request) Successful in 7m58s
Every optimiser defect this project has found was invisible from outside
while it was happening, and each was paid for at the meter first: SAFETY-45's
28 charge onsets an hour against a binding peak_cap_w, TARIFF-14's wrong
quarter-hour for 45 minutes in every 60, SAFETY-46's 598 Wh spent to gain
310 Wh. There was no way to watch what the optimiser WOULD do without letting
it do it.

`shadow_mode` runs strategies, arbiter, clamps and guards, records the
decision with its reason, and commands nothing.

⚠️ IT WRITES. It writes 0 W, on the ordinary heartbeat, through the ordinary
single writer. The inverter holds its last command forever - it has no meter
timeout - so "commands nothing" implemented as "stops writing" would leave
whatever was standing when shadow mode came on standing for as long as it was
left on, under a page saying nothing is being commanded. That is the failure
this repository keeps finding. Refreshing 0 W is also what
firmware/goodwe-master.yaml's 30 s stale-input watchdog requires of us; going
quiet would keep that board tripped for the whole run, which is an alarm being
used as a mode.

⚠️ IT IS NOT A SECOND WRITE PATH. No claim, no transport, no arithmetic of its
own. It is a substitution inside Controller._write_unit() - the single choke
point every write already reaches - in the same form as the three above it,
and it is the LAST of them, so SAFETY-28's gate and SAFETY-03's clamp still
grade the number the decision path produced.

⚠️ THE DEFAULT IS `auto`, NOT `true`, AND THAT IS THE CARD'S REAL CONTENT. The
Supervisor composes options as {**config.yaml defaults, **stored user
options}, so a new key with a new default reaches EVERY EXISTING INSTALL on
the next update - including the one regulating a real battery. A boolean
default-on would have stopped it silently. There is no mechanism by which one
key can default differently for a new install and an existing one, so
"default-on for new" is a value the add-on RESOLVES: `auto` is shadow while
control is STOPPED and live once it is STARTED. A fresh install ships
`auto_start: false` and comes up observing; an install that is controlling is
started and does not change by one watt.

THE FAILSAFES. Sign watchdogs (SAFETY-02/30): INERT - they grade
Inverter.standing_w(), which shadow mode holds at 0 W. Fed the shadow decision
they would disagree with a meter that never saw it and LATCH A TRIP THAT
SURVIVES INTO LIVE OPERATION AND A RESTART. Clamp (SAFETY-03), write gate
(SAFETY-28), meter freeze (SAFETY-18), peak guard: OBSERVE. Circulation
(SAFETY-31) and delivery (SAFETY-42): observe and may legitimately latch,
because their evidence is measured power. The operator stop is the one
deliberate change: enforced at the wire rather than as a P_SAFETY claim, which
would otherwise make every recorded decision read "stopped".

⚠️ RECORDED LIMITATION: _shadow_settle() re-seeds the carried command to what
stands on the wire, which makes the exit safe by construction - and therefore
the loop leg's shadow decision is ONE SLEW STEP, not a trajectory. A shadow
run answers "what would it command now", not "what would it have done next".
The strategies are unaffected; all three defects above are visible from one.

Graded on the writes and on the rendered surface, never on the flag: 22
mutations, no survivors, including one that lets a write escape and one that
goes silent instead of commanding 0 W. Closed loop on TEST-23 stage 3's rig,
same hour twice: live drives the pack to -2000 W and SoC 50.000 -> 62.331 %;
shadow commands 0 W throughout, SoC stays 50.0 exactly, and the arbitrage
decision is identical in action, instant, signed power, reason and arbiter
winner.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-14 17:25:43 +02:00