SAFETY-31 AC 4: the alarm's attribution was graded by nothing, and a mutation proved it #68
@@ -149,8 +149,70 @@ each swept across the **whole range `config.yaml` accepts** for the two settings
|
||||
that decide how fast the site can turn around: `gain` `float(0.05,1.0)` and
|
||||
`slew_w` `int(50,5000)`.
|
||||
|
||||
### ⚠️ THE HARNESS BEHIND EVERY FIGURE ABOVE IS NOT COMMITTED, AND UNTIL 2026-09-07 THAT MADE THEM UNCHECKABLE
|
||||
|
||||
**Read this before quoting any number in this section.** The paragraph below
|
||||
said the campaign harness "is not committed here" and treated that as a
|
||||
packaging detail. It is not: a figure produced by a script that exists in
|
||||
nobody's tree cannot be re-run, cannot be reviewed, and cannot be defended when
|
||||
it is contradicted. It has now been contradicted twice.
|
||||
|
||||
| sweep | worst peak | worst continuous | trips |
|
||||
|---|---:|---:|---:|
|
||||
| the 924-run campaign below — **harness uncommitted** | 1700 W | 505.0 s at 100 W; 5.0 s above 700 W | 0 / 924 |
|
||||
| independent reviewer sweep, 2026-09-07, 48 honest reversals | **2750 W** | **15.0 s above 700 W** | 0 / 48 |
|
||||
| `admin/goodwe` `two_master_circulation`, 840 runs — **committed** | 1048 W | 10.0 s at 100 W; 5.0 s above 700 W | **0 / 840** |
|
||||
|
||||
**This is not proof that anything was fabricated, and it should not be reported
|
||||
as one.** The three swept different grids. What the third one adds is a
|
||||
measurement of *why* the spread is that wide — on one grid, changing nothing but
|
||||
the model:
|
||||
|
||||
| plant / stagger | worst legitimate peak |
|
||||
|---|---:|
|
||||
| modelled plant (lag 10 s, ramp 800 W/s), staggers up to a whole cycle | 1048 W |
|
||||
| `INSTANT` (lag 0, unbounded ramp), staggers up to a whole cycle | 2250 W |
|
||||
| `INSTANT`, staggers strictly under a whole cycle | **0 W** |
|
||||
|
||||
A factor of 2.1×, and a factor of infinity, between three defensible
|
||||
descriptions of the same rig. **The plant model and the write-stagger set are
|
||||
terms of the number**, and a worst case quoted without them is not a
|
||||
measurement. That is enough to explain the whole spread above without anybody
|
||||
having invented anything — and it is exactly what cannot be established when the
|
||||
instrument is missing.
|
||||
|
||||
**What survives, and what does not.**
|
||||
|
||||
* **The window argument survives, and is now committed.** The claim that
|
||||
decides `circulation_hold_s: 75` is *"the worst continuous legitimate episode
|
||||
above 700 W is about one control cycle"*. All three sweeps agree on the shape
|
||||
of that (5.0 s, 15.0 s, 5.0 s — one to three cycles against a fifteen-cycle
|
||||
window), and **all three trip zero times**. `two_master_circulation` re-runs
|
||||
it on every pull request in `admin/goodwe`.
|
||||
* **The threshold curve does NOT survive as stated.** `505.0 s at 100 W` is the
|
||||
number the "knee at 400 W" argument for `circulation_w: 700` rests on, and the
|
||||
committed sweep measures **10.0 s** at 100 W on its grid — 50× smaller. The
|
||||
curve still *falls* with the threshold (126 of 840 runs cross 100 W against 1
|
||||
that crosses 700 W), so the knee is real in direction; its depth is not
|
||||
established by anything anybody can run. **Do not quote 505.0 s.**
|
||||
* **Nothing about the guard is compromised.** 0 trips in 924 + 48 + 840
|
||||
non-faulty runs, from three independent grids.
|
||||
|
||||
**What would settle it:** the original harness, committed. Until then the
|
||||
committed sweep is the only figure in this section anybody can check, and it is
|
||||
labelled as its own grid's rather than as a reproduction.
|
||||
|
||||
### Reproducing it
|
||||
|
||||
⚠️ **THE COMMITTED VERSION IS `admin/goodwe`'s `sim/inject.py
|
||||
two_master_circulation`** (`sim/sitesim.py:circulation_findings`, runnable on its
|
||||
own as `python3 sim/sitesim.py --circulation`, `norig`, ~36 s, graded by
|
||||
`checks.yml` on every pull request there). It produces the fault with
|
||||
`plantsim.Inverter.wedge()` — a unit answering its bus and no longer steering its
|
||||
power stage, which is HW-01 — and sweeps the legitimate family with the
|
||||
serialised write path staggered up to a whole control cycle. The paragraph below
|
||||
describes the ORIGINAL campaign, which is the one that is not committed.
|
||||
|
||||
The rig lives in `admin/goodwe` (`sim/`) and was used **read-only**; the harness
|
||||
is not committed here because it imports that repo's `plantsim`/`frame_check`,
|
||||
which are not present in this one or in CI. What it does is small enough to
|
||||
@@ -206,7 +268,11 @@ margin above the knee is what absorbs that without re-opening this card.
|
||||
**Revisit when SPIKE-04 lands, not before.**
|
||||
|
||||
The **schema floor is the knee itself**, 400 W, so a legally configured install
|
||||
cannot land in the 445–505 s regime. What the threshold costs: a circulating
|
||||
cannot land in the 445–505 s regime — ⚠️ and those two figures are from the
|
||||
uncommitted campaign; the committed sweep measures 10.0 s at 100 W on its own
|
||||
grid. See the disclosure at the head of this section. The floor is still the
|
||||
right shape (fewer runs cross a higher threshold, measured 126/840 at 100 W
|
||||
against 1/840 at 700 W); its DEPTH is not established by anything re-runnable. What the threshold costs: a circulating
|
||||
loop smaller than 350 W per unit is not reported, which is deliberate — at that
|
||||
scale the round-trip loss is a few watts.
|
||||
|
||||
@@ -289,6 +355,32 @@ SAFETY-25 — so no stale `.pyc` could exist to be read. Byte deltas recorded;
|
||||
| M17 | `circulation.py` | default `700` → `500` | **+0 B** | **RED** — the CFG-03 pin and the not-a-round-number check |
|
||||
| M18 | `main.py` | `await self.check_circulating()` removed | −39 B | **RED** — all four notification checks |
|
||||
| M19 | `main.py` | publish `round(x or 0.0)` instead of `None` | −68 B | **survivor on the first battery — GAP CLOSED**, then RED |
|
||||
| **M20** | `main.py` | **`pos, neg = opposing(...)` → `([], [])`** — the attribution clause deleted from the alarm | −102 B | **SURVIVED ALL 26 FILES on the shipped battery — GAP CLOSED**, then RED on §6a |
|
||||
| M21 | `main.py` | `pos` and `neg` exchanged — the alarm names both packs, both the wrong way round | **+0 B** | **RED** — §6a ×3 (the mirrored run, and "only its own sentence") |
|
||||
| M22 | `main.py` | `opposing(..., min_w=cfg.min_w / 2.0)` → `min_w=0.0` | −25 B | **RED** — §6a's resting-pack check |
|
||||
|
||||
**And four in `admin/goodwe`**, graded through `python3 sim/sitesim.py
|
||||
--circulation` rather than through the injector — deliberately, because
|
||||
`inject.py` is the file that takes the rig lock, and "run the injector to grade a
|
||||
mutation" is not a sentence anybody should have to type. Byte deltas over
|
||||
`plantsim.py` + `sitesim.py` together.
|
||||
|
||||
| # | file | mutation | Δ | result |
|
||||
|---|---|---|---|---|
|
||||
| S1 | `plantsim.py` | `wedge()` no longer stops the latch reaching the power stage | −20 B | **RED** — the opposing-signs precondition **and** "the watchdog did not trip" |
|
||||
| S2 | `sitesim.py` | the sensor computed over the **allocation record** instead of register 0x0518 | **+0 B** | **RED** ×3 — this is M10 restated on the rig |
|
||||
| S3 | `sitesim.py` | the campaign run on `plant=INSTANT` | −51 B | **RED** — the plant is a *term* of the figures; it was a SURVIVOR until that check was added, and finding out why produced §3's 1048/2250/0 W table |
|
||||
| S4 | `sitesim.py` | the write stagger removed from the legitimate campaign | −19 B | **RED** — "the legitimate campaign produced no opposition at all" |
|
||||
|
||||
**S3 is recorded as a survivor because it was one, and it is the most useful
|
||||
result in this table.** The scenario first shipped with a vacuity check whose
|
||||
text claimed `plant=INSTANT` would make the sweep measure 0 W. S3 was run and
|
||||
**passed**: `INSTANT` with a stagger of exactly one control cycle samples the
|
||||
plant before the second unit has stepped, so it produces opposition anyway — and
|
||||
a *larger* worst peak (2250 W) than the modelled plant does (1048 W). The claim
|
||||
in the check's own text was wrong. It was corrected against the measurement, the
|
||||
plant was pinned as an explicit term, and S3 is red now for a stated reason
|
||||
rather than by accident. §3's spread table is that measurement.
|
||||
|
||||
**M19 is recorded as a survivor because it was one.** The first battery found no
|
||||
check grading what `publish()` does when a per-unit reading is missing, so
|
||||
@@ -297,6 +389,30 @@ watches went unnoticed — the sensor's own `None` rule, defeated one layer out.
|
||||
A check was added and the mutation re-run; it is red now. The run that found it
|
||||
was purged, so it is a result and not an artefact.
|
||||
|
||||
**M20 IS RECORDED AS A SURVIVOR BECAUSE IT WAS ONE, AND IT IS THE MORE
|
||||
UNCOMFORTABLE OF THE TWO.** The commit message for this card claimed *"18
|
||||
mutations, all RED"*, and M1–M19 above have no entry for the notification's
|
||||
attribution clause. Verification on 2026-09-07 ran it and it **survived the
|
||||
whole 26-file suite**: the alarm still fires, still stops the site, still says
|
||||
the meter cannot see it — and no longer says *which two packs* or *which way
|
||||
round*. `circulation.py`'s own docstring calls that sentence the first thing
|
||||
somebody woken by this alarm needs and *"impossible to reconstruct from the
|
||||
number alone"*.
|
||||
|
||||
It survived for one reason, and it is not reachability: **M18 (the whole call
|
||||
removed) is red**, so `check_circulating()` is exercised. The three checks on
|
||||
that notification asserted `METER CANNOT SEE`, `CONTROL HAS BEEN STOPPED` and
|
||||
`isolator` — and **never an inverter name**. Nothing graded the attribution.
|
||||
|
||||
`test_watchdog.py` §6a closes it, and closes it on a fixture that can tell the
|
||||
three failures apart. It runs a roster of **`["garage", "shed", "cellar"]`** —
|
||||
operator names, none of them `UNIT_A`, for test_maintenance.py §11's reason:
|
||||
on a fixture whose names are the module's own constants a check cannot tell the
|
||||
roster from the constant. It runs the site **twice, mirrored**, so the sentence
|
||||
is not symmetric and a swap (M21, `+0 B`) is a different red from a deletion.
|
||||
And it carries a **third pack resting at 5 W**, so the floor that stops a pack
|
||||
in standby being named as a participant in a 6 kW loop (M22) is graded too.
|
||||
|
||||
## 7. What this card does NOT close
|
||||
|
||||
* **Inverter B's ramp and lag are placeholders.** Every transient number in §3
|
||||
@@ -305,7 +421,9 @@ was purged, so it is a result and not an artefact.
|
||||
margin. **Do not present any figure here as a measurement of inverter B.**
|
||||
* **A wedged inverter still cannot be stopped by this add-on.** §1 says so; the
|
||||
notification says so; there is no software fix and this card does not pretend
|
||||
to one.
|
||||
to one. It *can* now be produced on demand: `plantsim.Inverter.wedge()`.
|
||||
* **The depth of the threshold curve is not established by anything committed.**
|
||||
§3's disclosure. The window is; the knee's magnitude is not.
|
||||
* **A loop below ~350 W per unit is not reported.** Deliberate, §3.
|
||||
* **The saturation freeze fires under a wedged unit and leaves a standing grid
|
||||
error.** Observed on the rig while producing §2's numbers: with B wedged, the
|
||||
|
||||
@@ -722,18 +722,41 @@ print(f" e.g. {_sustained.reason!r}")
|
||||
|
||||
print()
|
||||
print(" ⚠️ AND NOT ON THE TRANSIENT, WHICH IS THE FALSE-ALARM CASE")
|
||||
# ⚠️ THE SHAPES BELOW ARE THE RIG'S, NOT INVENTED. Measured on TEST-19 over 924
|
||||
# closed-loop runs in which every unit executed the share it was given: the
|
||||
# worst continuous opposition above 700 W is 5.0 s - ONE control cycle - at a
|
||||
# peak of 1700 W. That is the serialised write path: on a reversing cycle B's
|
||||
# new number lands up to a whole cycle after A's, both slew through zero at
|
||||
# 800 W/s behind a 10 s lag, and between the two crossings they genuinely
|
||||
# oppose. A guard that trips on that is a false-alarm generator, and this
|
||||
# project's doctrine on crying wolf is explicit (SAFETY-15, SAFETY-19).
|
||||
# THE SHAPE BELOW IS THE RIG'S: the serialised write path means that on a
|
||||
# reversing cycle B's new number lands up to a whole control cycle after A's,
|
||||
# both slew through zero behind a real ramp and a real lag, and between the two
|
||||
# crossings they genuinely oppose. A guard that trips on that is a false-alarm
|
||||
# generator, and this project's doctrine on crying wolf is explicit (SAFETY-15,
|
||||
# SAFETY-19).
|
||||
#
|
||||
# ⚠️ THE MAGNITUDE IS A FIXTURE INPUT, NOT A MEASUREMENT, AND THIS COMMENT USED
|
||||
# TO SAY OTHERWISE. It read "the worst single transient the rig can produce -
|
||||
# 1700 W", sourced to a 924-run campaign whose harness IS NOT COMMITTED IN
|
||||
# EITHER REPOSITORY (DECISIONS/SAFETY-31-circulating-power.md §3 says so in its
|
||||
# own words). Three sweeps have now been run against that claim and no two agree:
|
||||
#
|
||||
# 924-run campaign, harness uncommitted peak 1700 W, 505.0 s at 100 W
|
||||
# independent reviewer sweep, 2026-09-07 peak 2750 W, 15.0 s above 700 W
|
||||
# goodwe `two_master_circulation`, 840 runs peak 1048 W, 5.0 s above 700 W
|
||||
#
|
||||
# ⚠️ THAT IS NOT EVIDENCE THAT ANY OF THEM IS WRONG. The three swept different
|
||||
# grids, and the last one measured WHY the spread is so wide: on its own grid the
|
||||
# worst legitimate peak is 1048 W on the modelled plant, 2250 W on `INSTANT`, and
|
||||
# 0 W on `INSTANT` with no write stagger reaching a whole cycle. The plant model
|
||||
# and the stagger set are TERMS of the number, and a worst case quoted without
|
||||
# them is not a measurement. It is evidence that the claim cannot be adjudicated
|
||||
# while the instrument is missing.
|
||||
#
|
||||
# So what this check now says is what it can support: 1700 W is LARGER than
|
||||
# anything any of the three sweeps produced legitimately, and one control cycle
|
||||
# of it does not trip. The committed, re-runnable version of the claim is
|
||||
# `admin/goodwe`'s `sim/inject.py two_master_circulation`, which runs on every
|
||||
# pull request there and requires ZERO of ~840 non-faulty runs to trip.
|
||||
_one_cycle = [0.0] * 5 + [1700.0] + [0.0] * 30
|
||||
_t1, _ = circ_drive(_one_cycle)
|
||||
check("the worst single transient the rig can produce - 1700 W for ONE control "
|
||||
"cycle - does not trip", not _t1.tripped)
|
||||
check("a single transient of 1700 W - larger than the worst peak any committed "
|
||||
"sweep of the legitimate family has produced - lasting ONE control cycle "
|
||||
"does not trip", not _t1.tripped)
|
||||
_repeated = ([0.0] * 3 + [1700.0]) * 20
|
||||
_t2, _ = circ_drive(_repeated)
|
||||
check("...and neither does it REPEATED every fourth cycle for 400 s, which is "
|
||||
@@ -1091,6 +1114,158 @@ check("...and it does not raise the same card on every cycle - a per-PROCESS "
|
||||
"this' a different question from 'is this site tripped'",
|
||||
len(_notes2) == 1)
|
||||
|
||||
|
||||
print()
|
||||
print("6a. AC 4: THE ALARM NAMES WHICH PACKS, AND WHICH WAY ROUND")
|
||||
# ⚠️ THIS BLOCK EXISTS BECAUSE A MUTATION SURVIVED ALL 26 FILES. Replacing
|
||||
#
|
||||
# pos, neg = opposing([inv.batt for inv in self.inverters],
|
||||
# min_w=self.circ_wd.cfg.min_w / 2.0)
|
||||
#
|
||||
# in `check_circulating()` with `pos, neg = ([], [])` (-102 B) silently deletes
|
||||
# the "Right now X is discharging while Y charges" clause from the notification,
|
||||
# and the whole suite stayed GREEN. The block above asserts three tokens -
|
||||
# METER CANNOT SEE, CONTROL HAS BEEN STOPPED, isolator - and NEVER an inverter
|
||||
# name, so the one sentence `circulation.py` calls "the first thing somebody
|
||||
# woken by this alarm needs" and "impossible to reconstruct from the number
|
||||
# alone" was graded by nothing at all.
|
||||
#
|
||||
# ⚠️ IT IS NOT DEAD CODE, WHICH IS THE PART THAT MAKES IT A CHECK GAP RATHER
|
||||
# THAN A REACHABILITY ONE. Ledger M18 - the `await self.check_circulating()`
|
||||
# call removed - goes red on four checks above, so this function runs. What
|
||||
# nothing asserted was the ATTRIBUTION.
|
||||
#
|
||||
# ⚠️ AND THE ROSTER IS ["garage", "shed", "cellar"], WHICH IS THE OTHER HALF OF
|
||||
# THE FIX. Every fixture above runs on `inverter-a`/`inverter-b`;
|
||||
# test_maintenance.py section 11 records what that costs - on a fixture whose
|
||||
# names are the module's own constants, a check cannot tell the roster from the
|
||||
# constant, and `UNIT_A` is not even what a nameless entry falls back to. Here
|
||||
# the names are an operator's, the two participants pull OPPOSITE ways so the
|
||||
# sentence is not symmetric, and a third pack rests at 5 W. That makes three
|
||||
# DIFFERENT mutations - the clause dropped, the two directions swapped, and the
|
||||
# `min_w` floor dropped - into three DIFFERENT red checks. A fixture naming both
|
||||
# units the same, or one in which the direction did not matter, would see the
|
||||
# first and neither of the others.
|
||||
|
||||
_CIRC_ROSTER = [
|
||||
dict(name="garage", setpoint_entity="number.sp_a", soc_entity="sensor.soc_a",
|
||||
batt_entity="sensor.batt_a", max_w=5000),
|
||||
# ⚠️ B_RATING_HYPOTHESIS, and part 4's note above says why it is not 4600:
|
||||
# inverter B does not physically exist and a datasheet is not a measurement.
|
||||
dict(name="shed", setpoint_entity="number.sp_b", soc_entity="sensor.soc_b",
|
||||
batt_entity="sensor.batt_b", max_w=B_RATING_HYPOTHESIS),
|
||||
# THE BYSTANDER. A third pack resting at standby draw, on the roster, read
|
||||
# every cycle, and NOT a participant in anybody's loop.
|
||||
dict(name="cellar", setpoint_entity="number.sp_c", soc_entity="sensor.soc_c",
|
||||
batt_entity="sensor.batt_c", max_w=B_RATING_HYPOTHESIS),
|
||||
]
|
||||
_CIRC_NAMES = [e["name"] for e in _CIRC_ROSTER]
|
||||
_REST_W = 5.0
|
||||
|
||||
|
||||
class _NamedCircHass(_Hass):
|
||||
"""Three named packs; the meter still reads exactly zero.
|
||||
|
||||
Same house as `_CircHass` - grid = load - sum(B) with two units cancelling -
|
||||
with one extra pack idling at standby draw so that "who is named" and "who
|
||||
is merely on the roster" are different questions.
|
||||
"""
|
||||
|
||||
def __init__(self, a_w, b_w, c_w=_REST_W):
|
||||
super().__init__()
|
||||
self.vals = {"sensor.batt_a": a_w, "sensor.batt_b": b_w,
|
||||
"sensor.batt_c": c_w}
|
||||
|
||||
async def number(self, entity, invert=False):
|
||||
return {"sensor.grid": 0.0, "sensor.soc_a": 50.0,
|
||||
"sensor.soc_b": 50.0, "sensor.soc_c": 50.0,
|
||||
**self.vals}.get(entity)
|
||||
|
||||
|
||||
def _named_trio(hass, store, *, hold_s=1, min_w=700):
|
||||
opts = {"meter_entity": "sensor.grid", "meter_source": "off",
|
||||
"max_w": 5000, "gain": 0.6, "auto_start": True,
|
||||
"circulation_w": min_w, "circulation_hold_s": hold_s,
|
||||
"inverters": _CIRC_ROSTER}
|
||||
c = Controller(opts, hass, store, _P(), stop=asyncio.Event())
|
||||
c.auto = True
|
||||
for inv in c.inverters:
|
||||
inv.dev_min, inv.dev_max = -5000.0, 5000.0
|
||||
return c
|
||||
|
||||
|
||||
async def _circ_named(a_w, b_w):
|
||||
hass = _NamedCircHass(a_w, b_w)
|
||||
c = _named_trio(hass, _MemStore())
|
||||
for _ in range(14):
|
||||
await c.read_inputs()
|
||||
await c.cycle()
|
||||
await asyncio.sleep(0.25)
|
||||
notes = [x for x in hass.calls
|
||||
if x[0] == "persistent_notification"
|
||||
and x[2].get("notification_id") == "goodwe_circulating_power"]
|
||||
return c, notes
|
||||
|
||||
|
||||
_cg, _notes_g = asyncio.run(_circ_named(+3000.0, -3000.0))
|
||||
_cs, _notes_s = asyncio.run(_circ_named(-3000.0, +3000.0))
|
||||
_msg_g = _notes_g[0][2]["message"] if _notes_g else ""
|
||||
_msg_s = _notes_s[0][2]["message"] if _notes_s else ""
|
||||
print(f" roster : {_cg.units}")
|
||||
print(f" garage discharging, measured: "
|
||||
f"{dict(zip(_cg.units, [i.batt for i in _cg.inverters]))}")
|
||||
print(f" -> {_msg_g.split(chr(10))[2] if _msg_g.count(chr(10)) > 2 else _msg_g!r}")
|
||||
print(f" shed discharging, measured: "
|
||||
f"{dict(zip(_cs.units, [i.batt for i in _cs.inverters]))}")
|
||||
print(f" -> {_msg_s.split(chr(10))[2] if _msg_s.count(chr(10)) > 2 else _msg_s!r}")
|
||||
|
||||
# --- THE PRECONDITIONS, AS THEIR OWN CHECKS (MUTATION.md rule 1) ------------
|
||||
check("PRECONDITION: the roster carries three DISTINCT operator-chosen names, "
|
||||
f"none of them `UNIT_A` ({UNIT_A!r}) - so every claim below is a claim "
|
||||
"about the roster and not about a constant that happens to equal it",
|
||||
_cg.units == tuple(_CIRC_NAMES) and len(set(_CIRC_NAMES)) == 3
|
||||
and UNIT_A not in _CIRC_NAMES)
|
||||
check("PRECONDITION: the two runs are MIRROR IMAGES - same house, same meter at "
|
||||
"0 W, same magnitudes, and the two participants swapped. Without this the "
|
||||
"direction claim below could be satisfied by a sentence that ignores the "
|
||||
"measurement entirely",
|
||||
[i.batt for i in _cg.inverters] == [+3000.0, -3000.0, _REST_W]
|
||||
and [i.batt for i in _cs.inverters] == [-3000.0, +3000.0, _REST_W]
|
||||
and _cg.grid == 0.0 and _cs.grid == 0.0)
|
||||
check("PRECONDITION: both runs actually tripped and actually raised the card, "
|
||||
"so an absent sentence below is an absent sentence and not an absent alarm",
|
||||
_cg.circ_wd.tripped and _cs.circ_wd.tripped
|
||||
and len(_notes_g) == 1 and len(_notes_s) == 1)
|
||||
|
||||
# --- AC 4: THE ATTRIBUTION ITSELF -------------------------------------------
|
||||
_WHO_G = "Right now garage is discharging while shed charges."
|
||||
_WHO_S = "Right now shed is discharging while garage charges."
|
||||
check("⚠️ THE ALARM NAMES THE TWO PACKS AND SAYS WHICH WAY EACH ONE IS PULLING. "
|
||||
"`circulation.py` calls this the first thing somebody woken at 3 a.m. "
|
||||
"needs and impossible to reconstruct from the watts alone, and until this "
|
||||
"line the sentence could be deleted with all 26 files green",
|
||||
_WHO_G in _msg_g)
|
||||
check("⚠️ AND WITH THE TWO SWAPPED, THE SENTENCE SWAPS. This is the half a "
|
||||
"single fixture cannot have: `pos` and `neg` exchanged, or a hard-coded "
|
||||
"sentence, satisfies the check above and fails this one. The operator is "
|
||||
"being told which pack to walk to",
|
||||
_WHO_S in _msg_s)
|
||||
check("...and each run carries ONLY its own sentence - the mirrored alarm does "
|
||||
"not also contain the other direction, so the clause is derived from this "
|
||||
"cycle's measurement rather than assembled from the roster",
|
||||
_WHO_S not in _msg_g and _WHO_G not in _msg_s)
|
||||
check("...and the RESTING pack is not named. `cellar` is on the roster, is read "
|
||||
"every cycle and is measured at 5 W of standby draw - `opposing()` is "
|
||||
"called with a floor of half the trip threshold precisely so a pack idling "
|
||||
"beside a 6 kW loop is not reported as one of its two participants",
|
||||
"cellar" not in _msg_g and "cellar" not in _msg_s
|
||||
and _cg.inverters[2].batt == _REST_W)
|
||||
check("...and the sentence sits with the figure, not instead of it: the same "
|
||||
"card still carries the watts, the window and the three things only this "
|
||||
"alarm can say",
|
||||
all("CIRCULATING_POWER" in m and "METER CANNOT SEE" in m
|
||||
and "CONTROL HAS BEEN STOPPED" in m and "isolator" in m
|
||||
for m in (_msg_g, _msg_s)))
|
||||
print()
|
||||
print(" the operator's press is the only way out, and it clears BOTH halves")
|
||||
|
||||
|
||||
Reference in New Issue