SAFETY-93: the maintenance charge end hands back smoothly, with no grid charging at a high house #167

Merged
admin merged 2 commits from safety-93-no-grid-charge-at-charge-end into release/1.0 2026-10-03 00:58:38 +02:00
Owner

SAFETY-85 rig test, check 4 (also on 9358781): at N=2, when A's maintenance charge ended, B went 0 -> -1600 W in one cycle. It charged from the grid with the house at 6000 W.

Cause. During the charge, the site target holds A's charge (SAFETY-84's ceiling, -2000 W). At the end A gets its HOLD pin (0 W), but the loop slews from last cycle's site target (-2000 -> -1600). B is the only battery left to place that on. A charge timeout (abort) or switching A Off does the same.

Fix (main.py _reseed_charge_end(), N>=2 only). On the cycle a battery leaves CHARGE, the loop's start point and its integrator become what the others stood at plus that battery's new command. That command is its pin (HOLD or abort, 0 W), or, if the battery is free, its last discharge (a charge stops). The loop then moves one slew step a cycle. The end is kept until the loop next runs, so a missed poll on that cycle does not lose it. DECISIONS/SAFETY-93-charge-end.md; one line in DOCS. No user-facing strings.

Before -> after (test_safety93.py: real Controller, 2 x 2500 W, plantsim lag 10 s, 2 s meter, cap 3500, margin 50). The test is red on f3e409c (7 checks).

case f3e409c this PR
rig case: house 6000, A charges 2000 W until the end B 0 -> -1600, charges from the grid for 4 cycles B 0 -> 400 -> 800 ..., never charges
house 1200 B 0 -> -1600 (2800 W from the grid) B steps of 400, never charges
charge times out / A switched Off B 0 -> -1600 B 0 -> 400
guard has suspended the charge, A gives 1825 W B step 675 W B step 395 W
missed poll on the end cycle B -1600 one cycle later B 0 -> 400

N=1 identity. Part 5 runs N=1 charge ends at a high and a low house, with and without the reseed: byte-identical. All 46 digests of tools/*identity*.py (N=1 and N=2) are byte-identical to f3e409c. No pinned digest was re-pinned: no identity scenario reaches a charge end.

Mutations (tools/mutation_run.sh on fresh purged copies, test_safety93.py):

# mutation result
M1 reseed call removed killed (9 checks)
M2 integrator not reseeded killed (3)
M3 a free battery keeps its charge in the start killed (2)
M4 the HOLD pin ignored killed (8)
M5 applied at N=1 too killed (2, N=1 identity)
M6 only a charge->HOLD end counts killed (2, timeout and Off)
M7 charging set never filled killed (9)
M8 sign of the drop flipped killed (10)
M9 the end lost on a missed poll (= for |=) killed (1)
M10 pending end never cleared killed (2)

Full suite: 60/60 local in the CI image.

For the reviewer / owner

  • The ending battery's own step (A -2000 -> 0 W at its HOLD pin) is still one step. That is maintenance's pin, and it lowers the grid import. Only the batteries the loop places are slewed.
  • Not changed: the peak guard's floor still moves the site in one step when it engages, for example on a house step or at a quarter edge. The guard outranks the slew. Example: house 6000 from 1500 s and HOLD at 1504 s: B +878 W, "limited by peak"; before, 1275 W. At a HOLD start under the guard, SAFETY-86 still has the other battery give first.
  • In the timeout case, the harness store has no last_start_attempt, so A restarts its drain right away. This is a fixture artifact, not graded.
  • Out-of-scope effects: SAFETY-88 (charge flapping above the aim) is untouched. Each flap is CHARGE->CHARGE, so it does not trigger this reseed. This PR does not make -89/-90/-92/-94, OPT-16 or UX-17/19 easier or harder. In the rig case, no new saturation freeze appears at the end (the loop reason reads slew-limited, then mode-bound).

🤖 Generated with Claude Code

https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr

SAFETY-85 rig test, check 4 (also on 9358781): at N=2, when A's maintenance charge ended, B went 0 -> -1600 W in one cycle. It charged from the grid with the house at 6000 W. **Cause.** During the charge, the site target holds A's charge (SAFETY-84's ceiling, -2000 W). At the end A gets its HOLD pin (0 W), but the loop slews from last cycle's site target (-2000 -> -1600). B is the only battery left to place that on. A charge timeout (abort) or switching A Off does the same. **Fix** (`main.py` `_reseed_charge_end()`, N>=2 only). On the cycle a battery leaves CHARGE, the loop's start point and its integrator become what the others stood at plus that battery's new command. That command is its pin (HOLD or abort, 0 W), or, if the battery is free, its last discharge (a charge stops). The loop then moves one slew step a cycle. The end is kept until the loop next runs, so a missed poll on that cycle does not lose it. DECISIONS/SAFETY-93-charge-end.md; one line in DOCS. No user-facing strings. **Before -> after** (`test_safety93.py`: real Controller, 2 x 2500 W, plantsim lag 10 s, 2 s meter, cap 3500, margin 50). The test is red on f3e409c (7 checks). | case | f3e409c | this PR | |---|---|---| | rig case: house 6000, A charges 2000 W until the end | B 0 -> -1600, charges from the grid for 4 cycles | B 0 -> 400 -> 800 ..., never charges | | house 1200 | B 0 -> -1600 (2800 W from the grid) | B steps of 400, never charges | | charge times out / A switched Off | B 0 -> -1600 | B 0 -> 400 | | guard has suspended the charge, A gives 1825 W | B step 675 W | B step 395 W | | missed poll on the end cycle | B -1600 one cycle later | B 0 -> 400 | **N=1 identity.** Part 5 runs N=1 charge ends at a high and a low house, with and without the reseed: byte-identical. All 46 digests of `tools/*identity*.py` (N=1 and N=2) are byte-identical to f3e409c. **No pinned digest was re-pinned**: no identity scenario reaches a charge end. **Mutations** (`tools/mutation_run.sh` on fresh purged copies, test_safety93.py): | # | mutation | result | |---|---|---| | M1 | reseed call removed | killed (9 checks) | | M2 | integrator not reseeded | killed (3) | | M3 | a free battery keeps its charge in the start | killed (2) | | M4 | the HOLD pin ignored | killed (8) | | M5 | applied at N=1 too | killed (2, N=1 identity) | | M6 | only a charge->HOLD end counts | killed (2, timeout and Off) | | M7 | charging set never filled | killed (9) | | M8 | sign of the drop flipped | killed (10) | | M9 | the end lost on a missed poll (`=` for `\|=`) | killed (1) | | M10 | pending end never cleared | killed (2) | Full suite: 60/60 local in the CI image. **For the reviewer / owner** - The ending battery's own step (A -2000 -> 0 W at its HOLD pin) is still one step. That is maintenance's pin, and it lowers the grid import. Only the batteries the loop places are slewed. - Not changed: the peak guard's floor still moves the site in one step when it engages, for example on a house step or at a quarter edge. The guard outranks the slew. Example: house 6000 from 1500 s and HOLD at 1504 s: B +878 W, "limited by peak"; before, 1275 W. At a HOLD start under the guard, SAFETY-86 still has the other battery give first. - In the timeout case, the harness store has no `last_start_attempt`, so A restarts its drain right away. This is a fixture artifact, not graded. - Out-of-scope effects: SAFETY-88 (charge flapping above the aim) is untouched. Each flap is CHARGE->CHARGE, so it does not trigger this reseed. This PR does not make -89/-90/-92/-94, OPT-16 or UX-17/19 easier or harder. In the rig case, no new saturation freeze appears at the end (the loop reason reads slew-limited, then mode-bound). 🤖 Generated with [Claude Code](https://claude.com/claude-code) https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
admin added 1 commit 2026-10-02 22:39:05 +02:00
SAFETY-93: the maintenance charge end hands back smoothly, with no grid charging at a high house
checks / unit (pull_request) Successful in 26m55s
infra-pin / fresh (pull_request) Failing after 1s
05eb93f139
At N>=2, when a battery's maintenance charge ended, its watts stayed in the
loop's start point and landed on the other battery (B 0 -> -1600 W in one
cycle, charging from the grid at a 6000 W house). On the cycle a charge
ends, the loop now starts from what the others stood at plus that
battery's new command. N=1 and all identity digests unchanged.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Author
Owner

Review round 1 (SAFETY-93). Probes and logs: scratch/SAFETY-93/review/. All runs use the real Controller on the 10 s lagging plant with a 2 s meter, in the CI image.

Verified

  • Rig case, house 1200, timeout, Off, guard-suspended and missed poll: reproduced. Red without the reseed, green with it.
  • N=3 (rig patched to abc; A charges, B and C free; house 6000 and 1200). With the fix: B and C step 0 -> 200 -> 400 ..., nobody charges. Without it: B and C go to -800 W each.
  • N=1 identity. All 46 tools/*identity*.py digests are byte-identical to f3e409c. I re-ran them myself on base and on head.
  • Peak guard at a HOLD start (your open point; house 6000 from 1500 s, HOLD at 1504 s). At 1504 B goes 1225 -> 2103 with "limited by peak(quarter peak)". The guard's floor is the binder, not the reseed. Without the fix B goes to 2500, so the fix makes this step smaller. Accepted, per owner order.
  • No spurious fires. I put a spy on _charge_ended:
    • house at the aim (SAFETY-88 conditions), 2700 s: 0 fires
    • house stepping across the aim (86 suspended cycles): 0 fires
    • guard suspends, then HOLD: 1 fire, at the HOLD
  • SAFETY-85 / -86 interaction. No double reseed: the only fire is at the CHARGE edge. A HOLD end (HOLD -> IDLE) does not fire.
  • Mutants re-run on purged copies: M1, M3, M4, M6 and M9 are all killed, matching your table.

F1 (must fix): a charge that ends by a stale link or a refusal still lands on B in one step.
In both cases A is still in CHARGE, so _charging never changes, but the allocator drops A.

  • Stale link (dropped inverter-a (stale link)): at house 1200, B goes 0 -> -1600 at 1330 s.
  • Refusal (A reads 0 W while asked to charge; dropped inverter-a (contradicts itself)): B goes 0 -> -1600 at 1322 s, then charges from the grid for 4 cycles.

This is the same stale-target mechanism, and the brief lists both as ways a charge ends.

Fix: track the end after the unit claims are filed. A battery is charging if it is in CHARGE, live, and its own claims do not contradict. With that, B goes 0 -> 400 in both cases.

  • Refusal: the spy shows one fire at the drop. A second fire at a probe edge (2256 s) leaves every row identical to base.
  • The guard suspension does not count as an end.

I'll push this, with tests (part 6).

F2 (minor): tests. Nothing graded the suspension case for spurious fires. I'll add a spy on part 4.

Mutants that survive, for the record:

  • R5 (reseed also on a DRAIN end) survives. That is acceptable, see O1.
  • R6 (pin read as 0) is an equivalent mutant: every pin is 0 W.

O1 (out of scope, follow-up ticket): the mirror case on a drain end. A switched Off mid-drain at house 1200: B goes 0 -> +1600 in one cycle (it exports). The drain floor's +2000 W stays in the start point. Not fixed here: it is a drain end, not a charge end.

O2 (pre-existing, not this PR): after a stale-link drop, the site sum still counts the dropped battery's power, so the loop can saturate-freeze. This happens on base too.

**Review round 1 (SAFETY-93).** Probes and logs: `scratch/SAFETY-93/review/`. All runs use the real Controller on the 10 s lagging plant with a 2 s meter, in the CI image. **Verified** - Rig case, house 1200, timeout, Off, guard-suspended and missed poll: reproduced. Red without the reseed, green with it. - **N=3** (rig patched to `abc`; A charges, B and C free; house 6000 and 1200). With the fix: B and C step 0 -> 200 -> 400 ..., nobody charges. Without it: B and C go to -800 W each. - **N=1 identity.** All 46 `tools/*identity*.py` digests are byte-identical to f3e409c. I re-ran them myself on base and on head. - **Peak guard at a HOLD start** (your open point; house 6000 from 1500 s, HOLD at 1504 s). At 1504 B goes 1225 -> 2103 with "limited by peak(quarter peak)". The guard's floor is the binder, not the reseed. Without the fix B goes to 2500, so the fix makes this step smaller. Accepted, per owner order. - **No spurious fires.** I put a spy on `_charge_ended`: - house at the aim (SAFETY-88 conditions), 2700 s: 0 fires - house stepping across the aim (86 suspended cycles): 0 fires - guard suspends, then HOLD: 1 fire, at the HOLD - **SAFETY-85 / -86 interaction.** No double reseed: the only fire is at the CHARGE edge. A HOLD end (HOLD -> IDLE) does not fire. - **Mutants re-run** on purged copies: M1, M3, M4, M6 and M9 are all killed, matching your table. **F1 (must fix): a charge that ends by a stale link or a refusal still lands on B in one step.** In both cases A is still in CHARGE, so `_charging` never changes, but the allocator drops A. - Stale link (`dropped inverter-a (stale link)`): at house 1200, B goes 0 -> **-1600** at 1330 s. - Refusal (A reads 0 W while asked to charge; `dropped inverter-a (contradicts itself)`): B goes 0 -> **-1600** at 1322 s, then charges from the grid for 4 cycles. This is the same stale-target mechanism, and the brief lists both as ways a charge ends. Fix: track the end after the unit claims are filed. A battery is charging if it is in CHARGE, live, and its own claims do not contradict. With that, B goes 0 -> 400 in both cases. - Refusal: the spy shows one fire at the drop. A second fire at a probe edge (2256 s) leaves every row identical to base. - The guard suspension does not count as an end. I'll push this, with tests (part 6). **F2 (minor): tests.** Nothing graded the suspension case for spurious fires. I'll add a spy on part 4. **Mutants that survive, for the record:** - **R5** (reseed also on a DRAIN end) survives. That is acceptable, see O1. - **R6** (pin read as 0) is an equivalent mutant: every pin is 0 W. **O1 (out of scope, follow-up ticket):** the mirror case on a drain end. A switched Off mid-drain at house 1200: B goes 0 -> **+1600** in one cycle (it exports). The drain floor's +2000 W stays in the start point. Not fixed here: it is a drain end, not a charge end. **O2 (pre-existing, not this PR):** after a stale-link drop, the site sum still counts the dropped battery's power, so the loop can saturate-freeze. This happens on base too.
admin added 1 commit 2026-10-03 00:28:19 +02:00
SAFETY-93 review: a charge that ends by a stale link or a refusal hands back smoothly too
checks / unit (pull_request) Successful in 27m5s
infra-pin / fresh (pull_request) Failing after 1s
214051d1a8
A battery still in CHARGE but dropped by the allocator (stale link, or a
SAFETY-73 refusal contradicting its charge) left its -2000 W in the loop's
start point, and B went 0 -> -1600 W in one cycle. The end is now noted
after the unit claims are filed: in CHARGE, live and not contradicted.
Tests: part 6 (stale link, refusal) and a spy on the guard suspension.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Author
Owner

Review round 1, fixes pushed: 214051d (ls-remote checked).

  • F1 fixed. The new _charge_track() runs after the unit claims and the mode trade, just before the loop. A battery counts as charging only if it is in CHARGE, live, and its own claims do not contradict. _reseed_charge_end() is unchanged.
    • Stale link at house 1200: B now goes 0 -> 400 -> 800. Before the fix it went to -1600.
    • Refusal at house 1200: B now goes 0 -> 400 -> 800 -> 1200. Before the fix it went to -1600.
  • F2 fixed. test_safety93.py has a new part 6: the stale-link and refusal cases (both red on 05eb93f), and a spy showing the guard suspension is no end.
  • DECISIONS has one paragraph and one table row for this. DOCS is unchanged, since its sentence already covers it.
  • N=1 unchanged. _charge_track returns at once at N=1. The 46 identity digests are still byte-identical to f3e409c, and the full suite passes 60/60 in the CI image.

Mutants on 214051d (purged copies, test_safety93.py)

Killed:

  • M1, M3, M4 and M6
  • R1: the other batteries' sign flipped
  • R7: a stale link not counted as an end
  • R8: a refusal not counted as an end
  • R9: tracking back at the old place, before the claims
  • R10: tracking also at N=1

Survived, all equivalent:

  • M9 (= for |=) and R3 (pending end cleared while inputs are missing) are now equivalent. A missed poll returns before the tracking runs, so the end is seen on the next cycle. On every other path where the loop does not run (control stopped, a long blind spell), everything is commanded to 0 W, so a pending reseed adds 0. I checked this: the rows are byte-identical across three control-off gaps and a 30 s blind spell over the end.
  • R5 (reseed also on a DRAIN end) survives on purpose. See O1 in the round-1 comment.
  • R6 (pin read as 0) is equivalent.
**Review round 1, fixes pushed: 214051d** (ls-remote checked). - **F1 fixed.** The new `_charge_track()` runs after the unit claims and the mode trade, just before the loop. A battery counts as charging only if it is in CHARGE, live, and its own claims do not contradict. `_reseed_charge_end()` is unchanged. - Stale link at house 1200: B now goes 0 -> 400 -> 800. Before the fix it went to -1600. - Refusal at house 1200: B now goes 0 -> 400 -> 800 -> 1200. Before the fix it went to -1600. - **F2 fixed.** test_safety93.py has a new part 6: the stale-link and refusal cases (both red on 05eb93f), and a spy showing the guard suspension is no end. - DECISIONS has one paragraph and one table row for this. DOCS is unchanged, since its sentence already covers it. - **N=1 unchanged.** `_charge_track` returns at once at N=1. The 46 identity digests are still byte-identical to f3e409c, and the full suite passes 60/60 in the CI image. **Mutants on 214051d** (purged copies, test_safety93.py) Killed: - M1, M3, M4 and M6 - R1: the other batteries' sign flipped - R7: a stale link not counted as an end - R8: a refusal not counted as an end - R9: tracking back at the old place, before the claims - R10: tracking also at N=1 Survived, all equivalent: - **M9** (`=` for `|=`) and **R3** (pending end cleared while inputs are missing) are now equivalent. A missed poll returns before the tracking runs, so the end is seen on the next cycle. On every other path where the loop does not run (control stopped, a long blind spell), everything is commanded to 0 W, so a pending reseed adds 0. I checked this: the rows are byte-identical across three control-off gaps and a 30 s blind spell over the end. - **R5** (reseed also on a DRAIN end) survives on purpose. See O1 in the round-1 comment. - **R6** (pin read as 0) is equivalent.
admin merged commit 858f77cfb5 into release/1.0 2026-10-03 00:58:38 +02:00