glenn schrooyenandClaude Opus 5 f47f1f0129 TEL-01: P1 ingestion, with the derivation and the age the EMS owns
A Belgian P1 meter publishes two UNSIGNED registers, not one signed figure.
Until now the add-on asked the installer to bridge that gap with a template
sensor, which put the sign convention of the whole control loop in a text box.
This moves it into the EMS: net = import - export, derived once, in one place,
with a test that fails if anyone inverts it.

Two transports behind one contract, chosen by `meter_source`: the HA WebSocket
subscribing to the DSMR integration's entities, and MQTT on a configurable
topic. Everything downstream reads P1Ingest, so switching is a config edit.
`meter_source: off` is the default and keeps the existing meter_entity path,
so no installed system changes until it opts in.

The other half is the timestamp. Every accepted sample is stamped at ingest
with a monotonic clock, `meter_max_age_s` is applied to it, and the age is
published as sensor.p1_sample_age_s for the ESP32's stale-input watchdog. That
entity is recomputed against the clock every second rather than only when a
telegram lands, because HA pushes state only on change: a meter frozen at a
constant reading emits nothing and looks, to anything watching the value,
exactly like a meter that has died. The age tells them apart.

Deliberately absent: any fallback to an inverter-side power figure. The
inverter's own AC power correlates 0.998 with battery power and 0.09 with the
real meter, so failing over to it means regulating against your own output.
A gap stays a gap - a reconnect emits no synthetic sample, and a rejected
telegram never resolves to 0 W or refreshes the timestamp.

Quarter-hour averages are time-weighted over clock-aligned blocks rather than
a mean of samples, so a cadence change cannot bias the capacity-tariff figure,
and only offtake is accumulated so a quarter of pure export averages to 0 kW.
Per-phase import is kept separately: on an unbalanced three-phase load the
phase sum and the connection net are different numbers, and only one of them
is billed.

test_p1.py: 99 checks, runnable with a bare interpreter and no meter. Includes
an end-to-end run of the HA transport against a fake Home Assistant websocket.

Stacked on SAFETY-04; nothing here touches control.py.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 23:16:31 +02:00
glenn schrooyenandClaude Opus 5 680461c9bf SAFETY-04: record the coverage audit as a comment, with its invariant
The audit found a dead mechanism twice, both times a clamp standing in for the
mechanism under test, so the technique has to survive this ticket. Not as a
script: the only cheap way to automate it is to key on source lines, that goes
stale silently, and a green audit that has quietly stopped testing anything is
this ticket's own failure mode one level up. Automating it properly would mean
decomposing compute() to make its statements separately addressable, which is a
refactor of the most safety-critical function in the repo for the benefit of
test tooling.

So it goes in as a comment block next to the checks it describes, carrying the
commit it was measured at, the thirteen figures, and the invariant with the
teeth in it: every mechanism must be noticed by at least two checks when it is
deleted, and adding a mechanism means re-running the audit. A comment cannot go
stale-green, because it never claims to be running.

Also recorded: fixtures must sit clear of every rail they are not testing,
which is the rule both misses violated; and the `python -B` / clear-pycache
discipline, with the reason (CPython invalidates on source mtime-in-seconds
plus size, so a same-second same-size rewrite reuses stale bytecode) and the
reason it casts no doubt on the figures (the error is one-directional, so every
number is a lower bound).

Figures are the lead's independent reproduction. I re-measured the one that
differed: the detector is 11 for `saturated_now = False` and 10 for the weaker
`frozen = False` form, so the table names the form.

test_control.py stays at 55 checks, all passing.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 23:07:58 +02:00
glenn schrooyenandClaude Opus 5 389d9ecd6d SAFETY-04: stop the clamps standing in for the mechanisms under test
AC 3 - "integration freezes while saturated" - had no non-vacuous test.
Deleting the integrator freeze outright failed 0 of 55 checks: the two checks
that name it used a fixture at max_w 2000 with the integrator bound following
it, so a wound value was truncated back to exactly 2000 and the assertion
passed on the clamp instead. Fixture lifted to max_w 5000, clear of every rail.
Deleting the freeze now fails 2.

Then swept the whole function for the same pattern, one mechanism at a time:
delete it, count which checks notice. It found a second instance - the OUTPUT
clamp. `clamped to max_w` and `clamped to -max_w` were both satisfied by the
integrator bound truncating first, so removing the output clamp failed only the
reason-string check. Those two fixtures now set integrator_max_w above max_w so
the mechanism they name is the binding one; the output clamp goes from 1 failure
to 3.

Every mechanism in compute() is now caught by a check that names it: freeze 2,
integrator clamp 6, bound-follows-max_w 4, output clamp 3, slew 4, output freeze
2, deadband 5, quantise 2, detector 10, duration 2, counter reset 6, grid bias 3,
None-seeding 6. No mechanism at zero.

Method note: the audit disables bytecode caching. Rewriting control.py inside
one second leaves a stale app/__pycache__ entry and silently under-reports -
it under-reported one mutation as 2 failures where the true figure is 6.

test_control.py stays at 55 checks, all passing.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 22:59:29 +02:00
glenn schrooyenandClaude Opus 5 53d301b920 SAFETY-04: exactly zero is its own case in the freeze tie-break
`min(moved, i_w) if i_w > 0 else max(moved, i_w)` files i_w == 0.0 under
rising-only, so the first push toward charging from exactly zero was blocked
permanently - the S-1 deadlock again, mirrored in sign. main.py resets i_w to
exactly 0.0 on every stop and every reseed, so it is a normal state.

Zero is now handled explicitly and both directions are allowed: nothing is
wound, so "may not wind further" has no referent, and a first step from zero is
bounded by the gain, the output clamp and the slew limit like any other.

Measured before the fix, at i_w == 0.0 and frozen: 12 800 of 25 920 ticks held
the integrator and 8 304 of those changed the emitted command, worst case
abandoning a 2 kW charge into a 4 kW export. Note this is NOT the same as the
reported symptom: at prev_w == 0 the command holds at 0 W either way, because
the output freeze forbids starting a charge while saturated, and that rule is
release/1.0's and unchanged. There is now a test asserting it deliberately.

Tests. The durable part is a property rather than more points: over 13 041
frozen states the integrator may be held ONLY by a correction pushing it
further from zero on the side it already sits, and any other hold fails. Both
signs at exactly 0.0. Mirrors added everywhere the suite tested one direction
of two - freeze wind/unwind while charging, i_w=-100, the export-direction
runaway, the negative clamp and slew.

DOCS: the cycles-vs-seconds deviation is now written down as a deviation - the
"> 10 s" criterion is not met as literally written, a cycle is one CHANGED
meter reading, and there is no guaranteed wall-clock window.

test_control.py: 43 -> 55 checks, all passing.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 22:49:01 +02:00
glenn schrooyenandClaude Opus 5 7123aa00a4 SAFETY-04: revive the clamp reason, and compare reasons in the sweep
`want = i_w` after the integrator bound, so at the default limit == max_w the
output clamp can never fire and `reason == "clamped"` had become unreachable.
Observability only today - nothing gates on the string - but SAFETY-03 exists
to alarm on exactly that engagement, so its hook was dead before it was built.

The integrator bound now reports "i-clamped", and that is the signal SAFETY-03
must watch: it is the one that fires on a default install. "clamped" stays
reachable for a configuration that lets the integrator run above the rail,
where both fire and the output clamp - which describes the value actually
emitted - is the one reported. Two names because the two events want different
alarms: the loop winding, versus a command that came out over the rating.

The real fix is the second half. The equivalence sweep compared
(target_w, sat_count), which is how a dead reason survived 3024 cases. It now
compares (target_w, sat_count, frozen, reason) and it catches this defect:
dropping the emit turns it red. Deliberate rename aliased explicitly, so any
OTHER reason divergence still fails.

Result of adding reason to the tuple: 105 of 3024 cases differ, and every one
of them is the i-clamped/clamped rename. Zero value divergences, `frozen`
included. Nothing else surfaced.

test_control.py: 41 -> 43 checks, all passing.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 22:29:10 +02:00
glenn schrooyenandClaude Opus 5 e46175559b SAFETY-04 review fixes: the freeze deadlocked, the bound was too loose
S-1. The frozen branch admitted a correction only if it shrank |i_w|. That is
unsatisfiable for BOTH signs of error whenever |correction| > 2*|i_w|, i.e.
whenever the integrator is near zero, so the loop stopped moving and the freeze
could never clear - it clears when the inverter tracks, and not tracking is
what saturation means. Measured: 0 W held into a 2 kW import indefinitely,
where release/1.0 recovers on the next cycle. Re-encoded as the same asymmetric
rule the output freeze has always used: may not wind further in the direction
it is already pushing, may fall, cross zero or reverse. Same interpretation,
an encoding that cannot deadlock.

S-2. integrator_max_w defaulted to 1.5x max_w, which ADDED windup: in
release/1.0 the accumulator was the post-clamp command and could never pass the
rail. Default is now "follow max_w" (config 0 = unset). Measured on the 4000 W
load-drop sim, first cycle after the drop: 1000 W at the new default, 1800 W at
3000. DOCS row inverted - the useful direction is below max_w, and the 14 768 W
anecdote is a vendor controller, not evidence about this code.

S-3. The claim that i_w=None preserved release/1.0 exactly was false, because
the S-1 gate ran regardless of seeding. It is true again, and now asserted
rather than asserted-about: 3024-case exhaustive comparison against a
transcription of the old law, over both freeze states, both signs and either
side of the deadband. Added the carried-i_w convergence/overshoot sim that the
shipped configuration was missing.

S-4. Cycles are distinct meter values, not seconds: cycle() runs only when the
meter reading changes, so the window has no wall-clock bound. Comment and DOCS
corrected; the stall is detection latency, not a windup hazard, because the
same condition stalls the whole loop.

test_control.py: 33 -> 41 checks, all passing.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 22:13:55 +02:00
glenn schrooyenandClaude Opus 5 37bac79ad8 SAFETY-04: clamp the integrator, not only the output
The loop was in velocity form: the accumulator WAS the commanded power, so
"clamp the integrator" and "clamp the output" were the same line of code and
could not be set apart. This makes the accumulator an explicit carried value
(`i_w`), bounds it with its own `integrator_max_w`, and keeps the output clamp
where it was. Killing either mechanism now still leaves the other holding -
which is the point of the ticket, and what the new regression test asserts.

Freeze semantics: while saturated the integrator may unwind but not wind
further. A strict freeze would strand the command at whatever it reached,
because the condition that releases it is the inverter tracking again, and not
tracking is exactly what saturation means.

The integrator is re-seeded from the arbiter's actual output whenever the loop
did not get what it asked for, so entering any failsafe (all of which resolve
to 0 W) zeroes it, and the first cycle after release does not dump the stale
period as power.

test_control.py: 24 -> 33 checks, all passing.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-24 21:44:05 +02:00
glenn schrooyenandClaude Opus 5 5184a2cfc2 Rest the meter just below zero, not at zero
The deadband is a one-way ratchet: any resting point inside it holds
indefinitely. Import and export are separate registers on the meter, so a
loop resting at +14 W bills 0.34 kWh/day while behaving perfectly.

target_grid_w (default -10 W) moves that residue onto the export register.
Worst billed rest point drops from 15 W to under 5 W. Behaviour is unchanged
at target_grid_w: 0.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-08-24 04:20:07 +02:00
adminandClaude Opus 5 017b798fe6 Precedence arbiter: one rule instead of an if/else ladder
Two controllers writing one actuator is the failure this system exists to
avoid. "Exactly one writer" was true, but only as a convention held up by
careful reading - which does not survive an EV charger and a heat pump wanting
the same battery.

Strategies now return claims and arbiter.py resolves them:

  highest-priority `set` wins (none at all means 0 W), then every `limit` whose
  priority is >= that set's applies, most restrictive first; contradictory
  limits command 0 W and are flagged as the bug they are.

The second clause is the whole point. "Money outranks maintenance" used to be a
hand-written exception inside a Jinja template; it is now a consequence of the
priorities - the charge-only limit binds the loop but cannot bind a
higher-priority peak claim.

Also: maintenance shaping moved out of control.py, which is a controller again
and not a policy engine; the loop now tracks the arbiter's actual output rather
than its own last wish, so it does not jump when it regains control; and every
decision explains itself ("loop -> 0 W, limited by maintenance(charge-only)")
in the UI and the log.

19 new assertions in test_arbiter.py, each one a precedence question someone
will eventually ask in the field. Deployed to the reference site as 0.2.0 and
holding grid within a few watts of zero.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_016NckgXecasQb2eSsPYNSW6
2026-08-23 02:45:32 +02:00
adminandClaude Opus 5 36cc837446 Point the manifests at the real repository URL
Also documents the two things that stop an install dead: the repository must be
public for Home Assistant to clone it anonymously (a private repo shows nothing
in the store and gives no useful error), and config.yaml's `version` must be
bumped for every change or Supervisor reuses the previously built image.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_016NckgXecasQb2eSsPYNSW6
2026-08-23 02:33:22 +02:00
adminandClaude Opus 5 594f8f9fc9 Six silent failures found by installing this on a live system
Migrated the reference site off the YAML packages and onto the add-on. Every
bug below presented identically: the add-on starts, logs "started", serves its
UI, and cannot do its job.

- run.sh needs #!/usr/bin/with-contenv sh. s6-overlay sanitises the environment
  for services, so a plain shebang means SUPERVISOR_TOKEN is absent and every
  Core API call is 401 - while homeassistant_api: true makes permissions look
  granted. Startup now prints the token length and probes the API.
- Supervisor keys the image by config.yaml `version`, so rebuilding without a
  bump reuses the old image. Two fixes appeared not to work because of it.
- Alpine is musl and has no aiohttp wheel on PyPI; deps now come from apk so
  nothing compiles on a client's Pi.
- Alpine ships paho-mqtt 1.x, which has no CallbackAPIVersion. That raised at
  construction and took the control loop down with it - so MQTT setup is now
  wrapped too. Observability must never be able to stop the controller.
- MQTT discovery is published from on_connect: paho silently drops QoS-0
  publishes issued before the CONNACK, so the previous code announced nothing
  while logging "MQTT connected".
- Repeated failures now log once a minute. Six warnings a second rolled the log
  buffer and destroyed the startup diagnostics needed to find the 401.
- auto_start could never fire, because the store's defaults always supplied
  auto: False for the fallback to find.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_016NckgXecasQb2eSsPYNSW6
2026-08-23 02:25:58 +02:00
adminandClaude Opus 5 0a1e61dbc9 Packaged as a Home Assistant add-on, with a field guide
Turns the reference RS485 controller into something a technician can install
at a client site: a typed config form instead of YAML, an ingress UI that
names misconfiguration in words, and persistent state that cannot be broken by
a timezone.

Why an add-on rather than YAML packages or blueprints:

- Blueprints cannot create helpers, and the maintenance cycle is a state
  machine whose phase and completion date must survive restarts.
- YAML packages need filesystem access, a configuration.yaml edit and a
  restart - none of which belong in a client install.
- Add-ons authenticate with SUPERVISOR_TOKEN, so there is no long-lived token
  to generate, store or leak on someone else's machine.
- Requires HA OS/Supervised. Container and Core installs cannot run add-ons at
  all, which is a market decision, not an oversight.

The control law and the maintenance machine are pure functions with no Home
Assistant imports, and both ship with runnable checks (22 and 22 assertions).
Every assertion corresponds to a rule whose absence caused an observed failure
on hardware - the saturation duration term, the clamp-before-slew ordering, the
deadband, the sign convention.

One behaviour deliberately differs from the implementation it replaces: when
its inputs go missing this commands 0 W rather than replaying the last
setpoint. The reference version kept replaying, which the hardware watchdog
cannot catch - from the ESP32's side, Home Assistant is still talking to it.

Includes the ESPHome firmware (now parameterised: node name, inverter rating,
watchdog timeout) and the optional RS485 e-stop. FIELD-GUIDE.md carries the
commissioning gates, all judged on the wire rather than on how Home Assistant
looks, plus the written statement a site without an e-stop needs signed.