753f70053986f1db27eca56654dc8649cca15249
8
Commits
| Author | SHA1 | Message | Date | |
|---|---|---|---|---|
|
|
753f700539 |
DEV-02: merge release/1.0, and close the two review blockers
checks / unit (pull_request) Successful in 4m15s
PR #43 was rejected on two findings and had gone unmergeable behind SAFETY-28 and the ALLOC-01 fix. This is the merge commit; the conflict resolution and both fixes are below, because a merge that also changes behaviour has to say so. THE MERGE, AND WHAT IT COST =========================== Two conflicts in main.py, both where SAFETY-28 and this card touched the same method: * `write_setpoint()` split into a site entry point plus a per-unit `_write_unit()` here, while SAFETY-28 put its record gate in the old single-unit body. `write_refusal()` now takes the INVERTER it is about. Asking it with `self.unit` - as release/1.0 does - would authorise A's share on B's wire, and would also trip test_inverter.py part 1's AST scan, which goes red on any read of a Controller N=1 view inside Controller. * the SAFETY-28 gate sits above the clamp and below the non-finite coercion, exactly where release/1.0 put it, and is now asked about `inv`. Fallout the merge produced in the checks, re-aimed rather than relaxed: * every fixture that calls `write_setpoint()` DIRECTLY - the clamp probe, the hung-heartbeat experiment and its serialised counterfactual, the split deadline probe - now arms a real allocation record first. test_inverter.py grows an `arm()` built through the shipped `resolve()`, the same shape test_clamp.py's is: the per-unit envelopes are filed as real `supervised` claims and the site target is their sum, so the water-fill has exactly one answer and the fixture cannot quietly become its own allocator. * test_clamp.py's two-unit failsafe fixture assigned `c.units`, which DEV-02 made a derived property with no setter. It appends a real `Inverter`. BLOCKER 1 - AC 4's ARBITER-BOUND EVIDENCE WAS VACUOUS ===================================================== test_peakguard.py claimed "each unit's `supervised` bound is ITS OWN `max_w` - give inverter B a different rating and the claim filed on inverter B moves with it", and compared B's bound against `_b2.max_w`. `second_inverter()` DEFAULTED B's rating to `LIVE_MAX_W`, which is A's. IT COMPARED (-5000, 5000) AGAINST (-5000, 5000): a number against itself, unable to observe the failure it named. Reproduced: filing the per-unit `device`/`supervised` claims from `self.inverters[0]`'s numbers while leaving `actuator=self.actuator_of(..., inv)` alone left ALL 19 FILES GREEN. At a roster of two with A=5000/B=3000 that makes inverter B's planned envelope (-5000, 5000) instead of (-3000, 3000) - a 2000 W over-command the arbiter believes is supervised. It is a DIFFERENT defect from the actuator variant the static routing pin catches, and only the actuator variant was in the mutation table. * `second_inverter()` gives B 3000 W - a hypothesis, marked as one - for every fixture in the file, so no check there can compare B against A by accident. * the claim is asserted against LITERAL numbers rather than against an expression that can read the same object twice, for `supervised` AND for `device` (whose `dev` had the same defect), plus the envelope the ARBITER RESOLVED for B - a claim filed right and resolved wrong is the same defect one layer down. * a PRECONDITION check fails if the two ratings are ever made equal again. * the BOUND mutation is in the table, beside the actuator one, and was observed RED (3 checks in test_peakguard.py) via tools/mutation_run.sh. ⚠️ THIRD INSTANCE THIS SESSION of a check whose DATA cannot reach the failure it names - ARB-03's call-site scan saw 3 of 8 appends, ALLOC-01's replay generator saw 0 escapes where a widened one saw 39,991. MUTATION.md gains a section for it beside the stale-bytecode and masking ones, and the rule is written at the line: ANY CHECK ASSERTING "X DIFFERS FROM Y" MUST BE RUN ONCE WITH X AND Y ACTUALLY MADE DIFFERENT. BLOCKER 2 - THE LATCH WAS SILENTLY DISARMED BY THE ROLLBACK ROUND TRIP ====================================================================== store.py's rule 2 keeps the flat keys "so a rollback still finds its latch". The operator path that rule contemplates is a ROUND TRIP, and this card lost the latch on it: 1. install migrates -> schema_version=1, unit/inverter-a/... = False 2. operator DOWNGRADES; SAFETY-02 trips inside the downgrade window and the old add-on writes only the flat `sign_tripped: true` 3. operator upgrades again -> `rep.ran` is False, so `_grade_store_migration()` returned early, and `Inverter.__init__` read the namespaced key: False Observed: the controller came up with `sign_wd.tripped = False` while /data/state.json said `sign_tripped: true`. That is store.py's own header sentence - "the file still says sign_tripped: true, the banner is green, and the controller resumes driving the wrong way" - rebuilt by the version marker. A firmware version change with a rollback path was performed on this site on 2026-09-02, so this is not hypothetical. Three changes, each graded by a mutation observed RED: * THE OPERATOR'S CLEAR CLEARS BOTH SPELLINGS. That is what removes the "re-arm forever" objection the `rep.ran` gate existed to answer: with the fossil cleared, `flat True + namespaced False` is unambiguously a downgrade-window latch. * A TRIP MIRRORS THE FLAT PAIR. Rule 2 only ever covered the latch present AT MIGRATION TIME - nothing flat was written for a trip taken afterwards, so an operator who downgraded found `sign_tripped: false` and came up DRIVING. store.py claimed the staleness could only fail toward a SPURIOUS latch. It could not; that sentence is corrected rather than left standing. * THE GUARD RUNS ON EVERY START, and asks the STORE - not the roster - whether anything namespaced is latched. A mirrored trip on B must not re-arm a healthy A, and the store is the right place to ask because it holds every `unit/*/sign_tripped` this install has written, including one belonging to a unit that is not in today's roster. Graded by the three-step scenario itself, run end to end in test_inverter.py part 2, with all three preconditions asserted - including that the catching start did NOT migrate anything, which is what used to skip the guard. Part 2's idempotence check now PRESSES the button instead of hand-writing the store, because the state it used to construct is not one the shipped clear path can produce. Part 3 grades the mirror and the clear on a real roster of two. test_watchdog.py's "the flat key is NOT written" assertion is re-aimed rather than deleted: its argument was right about the READ and wrong about the WRITE. Nothing at runtime reads that key, and the one thing that does ignores it whenever any namespaced latch is set - which a sibling's trip always leaves. What its absence actually cost was the rollback. HANDOVER.md and DOCS.md said the flat key "is never read again", which was the instruction an operator clearing a trip by hand would follow. Both corrected: it is a maintained rollback view, it IS read on every start, and clearing a trip by hand means clearing both spellings. MUTATIONS THIS ROUND, each applied on a purged tree via tools/mutation_run.sh and observed RED: * per-unit `device`/`supervised` BOUNDS from `self.inverters[0]`, actuator left correct -> test_peakguard.py 10g * `_grade_store_migration()` gated on `rep.ran` -> test_inverter.py part 2 * the operator's clear leaving the flat keys set -> test_inverter.py part 2/3 * a trip not mirroring the flat pair -> test_inverter.py part 3 * the guard asking only `self.inverters[0]` -> test_inverter.py part 3 19/19 files green on the merged tree. No hardware was touched. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU |
||
|
|
e306c74cb8 |
DEV-02: per-instance inverter objects, so nothing is graded against a sibling
checks / unit (pull_request) Successful in 4m15s
Every piece of per-device state in the Controller was a scalar, and several of
them are safety inputs. app/inverter.py introduces an `Inverter` that owns its
entities, its rating, its device range, its SignWatchdog, its last_write and
its last_beat, under store keys namespaced by unit name. The Controller holds a
list of them and keeps only what is genuinely site-level: the P1 reading, the
site integrator, and the tariff quarter.
WHAT THE SCALARS WERE SILENTLY ASSERTING
dev_min/dev_max one pair, read from one setpoint_entity. A second
inverter's rating was NEVER READ AT ALL, so its clamp, its
freeze rail and the peak guard's achievable_w were the
first one's numbers.
soc one reading into the maintenance FSM, SAFETY-24's pack
floor and arbitrage's bounds. An average lets the emptier
pack be driven below its own floor.
sign_wd ONE SignWatchdog, whose own docstring says "one instance
per actuator", latched under FLAT store keys - so a trip
caused by B latched A across restarts and one operator
press cleared both.
last_beat one deadline and one serialised hass.call(), so a hung
write to A ate B's 30 s layer-1 budget.
actual_w BECAME SITE LEVEL WHILE THE READINGS BECAME PER-INSTANCE, and those
are opposite directions on purpose. compute()'s anti-windup test is
`abs(prev_w - actual_w) > saturation_w` with prev_w the SITE target, so feeding
it one inverter's power compares a site number against a unit number, trips the
saturation freeze permanently and leaves a standing grid error. Measured on
admin/goodwe's two-master rig (tools/alloc_sim.py --splits, 2 kW load, 40
cycles), worst |delta| between splits at the meter:
gain one unit's power the site sum
0.2 510 W 0 W
0.4 250 W 0 W
0.6 50 W 0 W
That was ALLOC-01's disclosed finding; test_alloc.py part 8 kept its stimulus
and now grades the other row.
THE STORE MIGRATION IS GRADED, NOT MERELY PERFORMED. sign_tripped/sign_reason
move to unit/<name>/... once, verified by READING BACK what was written, and
the version marker is set only when nothing that carried state was lost. The
flat keys stay in the file so a rollback still finds its latch. And __init__
compares the pre-migration flat latch against what unit A actually came up
with: if the latch did not survive it is RE-ARMED from the legacy value and
shouted about. A latch that silently fails to migrate is a disarmed safety
guard on an install whose state file says it is protected - which is strictly
worse than never persisting it, because now there is evidence saying it is
fine. test_inverter.py part 2 breaks the migration and watches the guard fire.
HEARTBEATS ARE INDEPENDENT AND THE BUDGET IS DERIVED. Each inverter owns its
deadline, the refreshes go out concurrently, and each write is bounded by
WRITE_BUDGET_S = 4 s. The inequality is graded rather than asserted: 4 +
heartbeat_s's schema maximum of 25 < 30, validate.FIRMWARE_INGEST_VETO_S.
Verified by injecting a transport that accepts and never answers.
live_units() ANSWERS HONESTLY. A unit whose every write has been rejected for a
whole layer-1 window is not commandable; the allocator drops it, the survivors
carry its share, the action log names it, and the dropped unit is commanded
0 W rather than left standing on its last share. A roster entry with NO
setpoint_entity is deliberately not handled there - that is a configuration
that cannot be delivered, and it reaches main.py's refusal branch, which is how
that branch keeps a live trigger after this card removed its old one.
AT N=1 NOTHING MOVES. The removed scalars survive as read/write properties of
the sole inverter, so every existing replay runs unmodified - and they REFUSE
at N>=2 rather than answering for the first inverter, which is the tripwire on
a consumer that was never made per-instance.
EVIDENCE. 19 files green. test_inverter.py is new (82 checks). Eighteen
mutations were applied to the shipped modules on a purged tree via
tools/mutation_run.sh and each was observed RED. Two of them SURVIVED first
time and the checks were changed rather than the table: the serialised dispatch
and the shared last_beat both passed while part 6 gathered its own writes and
computed its own `due` list. send_heartbeats() was extracted from run_control()
so the shipped dispatch is reachable by a check at all.
INVERTER B STILL DOES NOT EXIST. build_roster() returns exactly one inverter
from the flat options and is the one function CFG-04 changes; every two-unit
figure here is architecture, and the second rating in the checks is marked a
hypothesis.
Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
591c35ed01 |
SAFETY-28: gate the write path on the allocation record, not on key count
checks / unit (pull_request) Successful in 4m19s
specs §1.5 makes "any configuration in which two writers can reach one
actuator" a non-goal. That non-goal was enforced by counting config keys:
validate.py's ACTUATOR_WRITE_KEYS = ("setpoint_entity",), consumed at rule 1,
with a comment stating the guarantee outright - "there is exactly one such
key, so a second writer is not expressible in the options schema at all".
That was true and it graded THE SHAPE OF THE OPTIONS SCHEMA, not the writes.
Add CFG-04's per-inverter config - a roster of inverters each with its own
setpoint_entity - and there are two real writers with len() of that tuple
still equal to 1. The check stays green while the property it protects is
gone. sim/inject.py's two_writers scenario asserted on the same tuple, so it
went green too. That is this repository's named failure mode: a check that
observes something other than what it claims to observe.
Demonstrated rather than argued. test_validate.py part 2 now constructs the
hazardous per-inverter config, asserts that the OLD proxy is still green on
it, and then asserts the new check refuses it. Against release/1.0's
validator the updated sim scenario reports: "validate_startup_config()
ACCEPTED a configuration in which 3 declarations reach the ONE actuator
number.goodwe_setpoint ... the old proxy reports 1 write key(s) on this same
config and is therefore GREEN on it".
THE WRITE PATH IS NOW GATED ON THE RECORD
=========================================
Controller.write_refusal() asks Allocation.authorises() whether the single
allocator placed exactly this number, for this unit, on this tick.
write_setpoint() refuses anything else. A second writer with arithmetic of
its own cannot satisfy that - its number appears in no record - so it has to
file a Claim and go through resolve(), which is the one allocator. "Exactly
one allocator per shared resource" stops being a convention somebody can
forget and becomes something the write path checks.
The refusal is a SUBSTITUTION, not a return: 0 W goes on the wire in place of
the number nothing stands behind. Returning would leave the inverter latched
on its last command with the ESP32 heartbeat still being fed - holding an
unauthorised setpoint quietly, which is the outcome the gate exists to stop.
AC 1 is "refused at the write path, not merely logged", and test_clamp.py
part 7a grades the device's writes, not the log.
The gate sits BELOW the non-finite coercion and ABOVE the clamp. Below,
because a nan is loss of input and rule 1 has already turned it into 0 W.
Above, because the question is who chose this number, and the answer is only
meaningful about the number that was asked for - gating the CLAMPED value
would refuse exactly the cycles SAFETY-03 exists for, since a clamped write
differs from the allocator's share by construction. Mutation M7 moves the
gate below the clamp and turns nine checks red, part 6c among them.
A STALE RECORD CANNOT BE REPLAYED
=================================
Every Allocation now carries the `tick` it was made for. It is handed IN by
the caller - plan(..., tick=) - rather than counted inside the allocator,
because test_alloc.py part 10 grades that the module holds no state at all,
and a serial number incremented in there would be the cached-across-ticks
thing the envelope rule forbids wearing a different hat.
Controller.alloc_tick advances ONCE PER RESOLUTION, not once per loop
iteration, and both halves are load-bearing:
* a new allocation makes the previous record stale immediately, so a record
whose envelopes have moved cannot authorise a write. That is the replay
half (AC 2), graded by capturing a real record, running another real
cycle, putting the old one back and observing refusal.
* the "inputs missing, not yet stale" hold returns BEFORE the allocator
runs, exactly so one dropped meter reading does not zero the inverter,
and the heartbeat re-affirms self.target through this same gate while it
does. A tick incremented per loop iteration would refuse that heartbeat
and turn the hold into the outage it exists to prevent. Graded.
An UNSTAMPED record (tick None) authorises nothing: "I cannot say when I was
made" fails closed rather than reading as tick zero.
THE FAILSAFE CANNOT DEADLOCK BEHIND THE GATE, AND HERE IS WHY
=============================================================
write_setpoint() is also how layer 2 commands 0 W. cycle()'s two refusal
branches substitute a 0 W failsafe and write it like any other cycle;
shutdown() and the operator's stop button do the same. EVERY ONE OF THOSE
RUNS WHILE THE ALLOCATOR HAS REFUSED - ok is False and there are no shares -
so a gate that asked the allocator's permission to command zero would block
the safety write behind the very component whose failure the safety write
answers. A gate that can do that is worse than the hole it closes.
Resolved by authorising 0 W unconditionally, and on the VALUE rather than on
a failsafe=True flag: a flag is an assertion by the caller, which is exactly
what a second writer would pass; the value is a fact about what will be
written. The argument that this is safe and not merely convenient is that the
hazard §1.5 names is N-times loop gain from BROADCAST - handing every inverter
the same target so each supplies it in full (allocator.py's opening argument;
TEST-19 measured a permanent 4000 W p2p limit cycle at gain 1.0 with no guard
firing). At S = 0 the broadcast and the correct allocation COINCIDE: a_i = 1
for every unit gives every unit 0 W, which is exactly its share. There is no
over-command to make at zero. Said at the line, in write_refusal().
test_clamp.py part 7c drives it end to end through the real cycle() and the
real REFUSE_EMPTY branch: the allocator refuses every tick, the device still
sees 0 W, and the action log says ARBITER: REFUSED rather than WRITE REFUSED
so the two failures stay distinguishable to whoever has to debug them.
unmet_w IS STILL NOT ok
=======================
The gate reads ok and the unit's share and never unmet_w. allocator.py:179
says why: an allocation that could not place every watt is still safe to
write, and fusing them would let one saturated inverter park the whole site.
Graded on a record with 3800 W unmet and every share legal - mutation M5 adds
`or self.unmet_w` to the gate and that check goes red.
THE CONFIG CHECK, REPLACED RATHER THAN DELETED
==============================================
actuator_writers() counts WRITERS PER ACTUATOR instead of option keys. It
walks the options TREE rather than looking for a container called `inverters`,
because CFG-04 has not chosen that name yet and a census that guessed wrong
would go green while two writers existed - the same defect one step along.
Entity ids are folded to lower case so a second writer cannot be smuggled in
as Number.X versus number.x.
Two inverters with two entities are ACCEPTED - that is what the per-inverter
roster is for, and a validator that refuses the feature it guards is one
somebody switches off. Two declarations aimed at ONE entity are refused,
naming the actuator and every writer pointed at it. That includes the case an
author will meet first - keeping setpoint_entity as A's and listing A again -
because "they happen to be the same entity, so it is fine" is precisely the
reasoning that makes two writers invisible.
ACTUATOR_WRITE_KEYS survives ONLY as the enumeration a census needs, with its
guarantee comment deleted; nothing asserts on its length any more. Keeping the
name is also what stops admin/goodwe's current two_writers scenario failing on
an AttributeError between the two merges.
WHAT NEITHER CHECK OBSERVES, SAID OUT LOUD
==========================================
The census sees CONFIGURED writers. A second write path added in CODE - a
hass.set_number() call next to some new strategy - declares nothing and is
invisible to it, exactly as it was invisible to the tuple. That half is not
closed at startup and cannot be; it is closed at runtime by the record gate,
which does not care what the options look like or who called the method. The
two checks are deliberately different kinds, and only the runtime one survives
a schema this file has not seen yet.
EVIDENCE
========
* Full 18-file suite green on a purged tree (tools/mutation_run.sh).
* Verified by breaking it - seven mutations, each on a purged tree, each
reverted and re-verified:
M1 remove the gate -> test_clamp red (4 checks)
M2 make the zero exit an amnesty -> test_clamp red (12 checks)
M3 drop the tick comparison -> test_clamp red (5 checks)
M4 delete the census refusal -> test_validate red (3 checks)
M5 fuse unmet_w into ok -> test_clamp red (1 check)
M6 freeze the tick on the live path -> test_clamp red (2 checks)
M7 move the gate below the clamp -> test_clamp red (9 checks)
* AC 5: no existing check was weakened. The two edits to test_clamp.py are
fixtures, not assertions - parts 5 and 6c call write_setpoint() directly
with a number nothing allocated, which is now refused, so they say where
their number came from. Every assertion in both parts is unchanged, and
part 7f asserts that across part 3's sixty real cycles the gate refused
zero writes.
* admin/goodwe's TEST-19 norig scenarios (planner_binding, two_master_plant,
two_master_broadcast) still pass against this tree - they import the
add-on's control law across the repo boundary.
Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
|
||
|
|
186e13ceca |
ALLOC-01: allocate the site grid target, sum-invariant, never broadcast
checks / unit (pull_request) Successful in 4m6s
ARB-03 left `allocate()` as a documented seam that passed through at N<=1 and
DECLINED at N>=2, with the reasoning recorded at the line: the obvious
placeholder - hand the site target to each inverter - IS the ARCH-01 fault, and
"a placeholder that cannot be told apart from the real thing by any guard we
have is worse than no placeholder". This fills the seam.
WHY A BROADCAST IS A FAULT AND NOT AN INEFFICIENCY. The control primitive is
meter emulation: the master reports a FABRICATED grid reading and the inverter
regulates itself to it, so one number means "the battery moves X W" to this
add-on and "the grid is at X W" to the inverter - an identity that holds only at
N=1. Hand two inverters the same target and each supplies it IN FULL, so the
loop gain at the meter becomes N times the per-unit gain. Reproduced on
admin/goodwe's two-master rig against this tree: -400 W export overshoot at
gain 0.6, and at gain 1.0 - which config.yaml accepts as its documented maximum
- a permanent 4000 W peak-to-peak limit cycle, commands alternating
1000/2000/1000/0 W, with NOT ONE GUARD FIRING. The sign watchdog is evaluated on
every cycle and never trips, because the disagreement flips on alternate ticks
and never holds its 180 s window.
WHAT WAS BUILT. `app/allocator.py`, host-side and strictly above the driver
seam. It consumes intervals and a number and nothing else - no claims, no
priorities, and no measurement, because an allocator that read P1 would be a
SECOND integrator on the site measurement.
* ENVELOPE CLAMP, from ARB-03 stage 1's `UnitBounds`, read PER TICK. `plan()`
is a pure function and the module holds no state, so there is nowhere for a
construction-time envelope to be cached.
* WATER-FILL by weight, with the surplus of a full unit moving to the others.
Weights express PREFERENCE, envelopes express PERMISSION: a zero weight is
honoured while another unit has headroom and overridden when it does not,
because the SUM is the safety property and stranding capacity behind a
comfort choice manufactures a standing error at the meter.
* LARGEST-REMAINDER ROUNDING. The target is rounded ONCE, at the top; every
sum below that line is integer arithmetic, so it cannot drift. Measured: a
per-unit round() drifts -125 W over 50 000 ticks at three inverters.
* THE ALLOCATION RECORD, with `unmet_w`, `dropped` and a per-unit reason.
`ok` is one boolean for SAFETY-28 to gate on, and `unmet_w` is deliberately
NOT fused into it - a saturated inverter must not park the whole site.
THE STABILITY PROPERTY IS STRUCTURAL. With sum(a_i) = 1 the gain at the meter is
sum(a_i * g_i), a convex combination of the per-unit gains, so it lies in
[min g_i, max g_i] FOR ANY SPLIT. That is what makes the weights a comfort
choice rather than a tuning parameter, and it is why a bad split cannot
destabilise the site. Graded directly, and measured end to end: 90/10, 50/50 and
100/0 give a bit-identical aggregate trace at the meter, and a gain sweep to 1.0
at every split has a flat tail at all 84 combinations.
THE TWO REFUSALS main.py NOW MAKES, AND WHY THERE ARE TWO. `allocated=False` no
longer means "no allocator"; it means no safe split EXISTS - a mis-routed claim,
an empty envelope set, or a split that could only be made by commanding one pack
to charge while another discharges. Separately, and this guard is the price of
making allocate() succeed rather than something inherited, main.py refuses to
act on a valid split it cannot DELIVER: there is one `setpoint_entity`, so
writing the site target to the one inverter it can reach would over-command that
inverter by exactly the other's share. Commanding a partial site is a worse
instruction than commanding nothing. DEV-02 gives it the second writer.
scope_violations() IS NOW CONSUMED, AND AS A REFUSAL. ARB-03 left it logging
without changing the resolution. A mis-routed claim means the number about to be
divided may itself be wrong, and dividing a number that may be wrong is worse
than not dividing it - the same answer clause 3 already gives a contradiction.
It is NOT promoted into an envelope: a unit-scoped claim that landed on the site
names no unit, so promoting it would mean guessing one, or applying one
inverter's rating to a sibling that does not have it.
AT N<=1 IT IS A PASS-THROUGH, BYTE-IDENTICAL: the share is the site target, as a
float, unrounded and unclamped. All 17 existing suites replay unedited.
test_peakguard.py part 10h and test_arbiter.py part 7 were RE-AIMED, not
deleted. PR #40's reviewer proved that refusal branch was unreachable and
untested once; removing its trigger without giving it a new one would have
rebuilt the hole. Part 10h now drives three real cycles - a deliverable split, a
dead sibling, and every master stale - and grades all three.
KNOWN AND NOT CLOSED HERE: at a roster of two the loop's `actual_w` is one
inverter's power used as a site measurement, because the add-on binds a single
`inverter_power` sensor. That is the SENSING half of the same N=1 identity this
card removes from the COMMANDING half, and it makes the aggregate trace
split-dependent below gain 1.0. Measured with its counterfactual in test_alloc.py
part 8 and tools/alloc_sim.py --splits. It belongs to DEV-02.
Verified: all 18 suites green in the CI image. 16 mutations run through
tools/mutation_run.sh on a purged tree; 13 red, and the 3 survivors are recorded
in test_alloc.py part 12 with the reason each cannot be caught.
Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
|
||
|
|
b68f288fef |
TEST-11: pin the clamp guard to the write it reads
checks / unit (pull_request) Successful in 3m40s
check_output_clamp() sits one line below `await self.write_setpoint(self.target)` in cycle(), and moving it above the write left test_clamp.py, test_freeze.py and test_loop.py ALL GREEN. Measured on the move itself before this commit; measured again after, where test_clamp.py part 6 goes red and the other two are still green - the gap was real and it was only ever in this file. WHAT IS ACTUALLY LOST. The guard has two evidence sources. `self.loop_clamped` is set from the Decision well above the write and survives the move, and on the 10.3 runaway replay it is the source of every engagement the alarm reports (0 write-path engagements against 2 loop-side ones) - which is exactly what makes the move nearly invisible. `self.clamp_last` is assigned by write_setpoint() and by nothing else, is None until it has run, and is what `engaged_write` reads at main.py:856. Moved above the write, that consumer goes quietly false and a DEVICE-bound clamp - max_w above the inverter's own rating, SAFETY-20's install - is reported by nothing. A guard whose second evidence source can be silently disconnected is one refactor from being half a guard. WHAT THE CHECK PINS, AND WHAT IT DELIBERATELY DOES NOT. Not the position: the comment at that line warns against tidying SAFETY-03's ordering and SAFETY-18's into one rule, and a check a rename breaks is worse than none. It pins the CONSEQUENCE - what `self.clamp_last` held each time the guard consulted the watchdog - using a spy subclassed from the shipped ClampWatchdog over a slew-limited ramp where every cycle's command is a different number, so "this cycle's evidence" and "last cycle's" are distinguishable at all. The spy hooks `clamp_wd.note()`, the consumer, rather than the guard's name: that is what keeps a rename legitimate. The same assertions are re-run through a controller whose guard is renamed and whose write lives in a helper, and were verified against main.py itself - renaming the method throughout AND moving both calls into a new `_emit_and_guard()` helper keeps part 6 green; swapping the two calls turns it red on a line that names clamp_last. WHY AC 3 NEEDED A NEW STIMULUS, AND WHY IT IS NOT DRIVEN THROUGH cycle(). Through the real cycle() the write-path half cannot engage: the arbiter files the device range and max_w as P_SAFETY LIMIT claims, so resolution.target_w is already inside both bounds before write_setpoint() re-applies them. That duplication is deliberate defence in depth; part 6 now MEASURES the zero engagements rather than leaving it as a claim in a comment, and then drives the write path directly at max_w 5000 against a +-2500 W device - the wire carries 2500 W, every loop-side flag stays clean, and the alarm fires on clamp_last alone. With the two calls swapped the same stimulus clamps the same value and the alarm is silent, which is the ticket in one pair of runs. main.py gains one comment sentence naming the check, mirroring the one SAFETY-18's block already carries for test_freeze.py part 5. No behaviour changes. Full suite: 17/17 green in goodwe-addon-ci. Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com> |
||
|
|
7b4877d56d |
TEST-15: purge the bytecode cache before a mutation run, not after
checks / unit (pull_request) Successful in 3m35s
FCST-03's developer reverted `self.provisional` to `here.provisional`, re-ran, and reported the mutation as a survivor. It was not one. CPython validates a cached `.pyc` on (source size, source mtime truncated to whole seconds), and that edit moved neither number - same length, same second - so the interpreter loaded the bytecode it already had. Disassembly settled it at the time: the source read `here`, the running code loaded `self`. A mutation run had graded code that was not there, with no error and exit status 0. This does not make the results already on the record wrong. It makes them UNVERIFIED, and that distinction is the whole card - so nothing here re-runs a campaign and nothing here quietly assumes the old numbers hold. REPRODUCED, THEN CLOSED. test_bytecode.py builds a real package whose two return values are the same length, imports it in a real subprocess, rewrites it inside the same second (retrying until both writes land in one whole second - milliseconds, no sleep) and reads back which value ran. Part 1 shows the interpreter running SELF off a file that says HERE. AND THE TWO OBVIOUS MITIGATIONS DO NOT WORK. Measured, not read off documentation: `python3 -B` and PYTHONDONTWRITEBYTECODE=1 are write-side only. Neither stops an EXISTING stale .pyc being read, and a mutation run always has one, because the previous run wrote it. Part 2 grades both still running the old code. The advice in test_control.py's coverage audit led with `-B`; it is corrected here - the purge is the half that works, and `-B` earns its place by keeping THIS run from leaving a cache for the NEXT edit to inherit. NO SLEEP ANYWHERE. One-second mtime resolution is the mechanism, not the enemy. Waiting it out would slow every run down and would still only cover the edit somebody remembered to slow down. THE HARNESS. tools/mutation_run.sh purges, prints a sha256/byte fingerprint of every app/*.py it is about to grade - so a mutation report can say WHICH source produced it, which is the reviewer's addition to this card - runs each suite under `python3 -B`, refuses a tree with no test_*.py (CI-01's rule, for CI-01's reason), and fails if a cache appears during the run. It takes the tree as an argument so the infra repo's replay harnesses can call it without being moved. WHERE IT IS SAID (AC 2). MUTATION.md carries the mechanism, the measurement, the reporting rules and the survey, and every one of the 16 suites now points at it from its docstring. That list is DERIVED FROM THE TREE by test_bytecode.py part 5, so a new suite that joins this directory without the pointer is red - the same failure shape CI-01's file glob exists to prevent. CI WAS ALREADY IMMUNE, AND IS DESCRIBED THAT WAY (AC 4). Verified rather than reasoned: with the checkout bind mounted `-v "$WS:/w:ro"` the interpreter writes no __pycache__ into the tree at all, and it fails SILENTLY - no error, exit status 0 - while the same probe on a writable mount produces one. Each job also rm -rf's its workspace and clones afresh, so nothing crosses between jobs on the shared runner. PYTHONDONTWRITEBYTECODE=1 is added as belt and braces only: the `:ro` is one character wide and the next person debugging a write will be tempted by it. Part 6 grades both ON THE DOCKER COMMAND LINE rather than on the file - the first draft searched the whole workflow and stayed green after the flag was deleted, because the comment explaining it still named it. THE SHIPPED ADD-ON IS NOT AFFECTED and the question is closed: goodwe_controller/Dockerfile has set PYTHONDONTWRITEBYTECODE=1 since it was written. There is no deploy-side finding. THE SURVEY (AC 3), in MUTATION.md, scoped BY THE PROPERTY. The defect is one-directional - a mutation that never took leaves the suite green, so stale bytecode manufactures SURVIVORS and cannot manufacture a red - which puts every "all red, no survivors" claim in the window out of scope, along with mutations executed in-process (SAFETY-07's B1/B2/B3, test_peakguard parts 7 and 10, where no source file is edited) and everything run after the purge discipline landed on 2026-08-31 (SAFETY-24, SAFETY-26, OPT-04, FCST-03's re-run). What is left is the recorded SURVIVORS from source-edit runs before that date. Two were re-run here under the harness and both still stand: TARIFF-01's record_block() ignoring its policy argument, and SAFETY-03's abs() on the clamp limit - 15 suites green each, on the tree as it stood. The rest are labelled still-unverified rather than assumed or re-run; each is one harness run to close, and the moment to spend it is when somebody next touches that module. OUT OF SCOPE AND RECORDED: the infra repo's sim/ replay harnesses import the add-on and write bytecode into both trees (goodwe/sim/__pycache__ exists today), so SAFETY-02's headline replay carries the same exposure. mutation_run.sh takes a tree argument for exactly that, but the change belongs in that repo and some of those harnesses want the rig. RED AND GREEN. Every new check was broken and watched fail: the purge commented out of the harness turns part 4 red (and its non-vacuity probe already proves the fixture would mis-grade without it); one docstring pointer removed turns part 5 red naming the file; `:ro` and the `-e` flag removed from the workflow turn part 6 red. Full suite green, 16 files, in the CI image on a read-only mount - the shape the runner uses. Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com> |
||
|
|
4e66583a52 |
SAFETY-03 review fixes: both clamp stages always run, and two checks that could not fail
1. BEHAVIOURAL, and a regression this PR introduced. clamp_to_rating() returned early from the max_w stage, so the device bound was applied only when the rating bound had NOT fired - the bigger the overshoot, the less the guard did. At max_w 5000 against a +-4000 device, +9999 emitted +5000 W, outside the device range, while +4500 was correctly held to +4000. It undid the pre-PR guarantee "never send a value the device will reject outright" and undercut this module's own case for max_w-not-min(), which rests on that stage catching a validation that did not run. Both stages now always run; the result names both bounds when both bite (max_w+device). Asserted over a 492-point sweep, because the defect was invisible to any single-value check sitting inside one stage. 2. The hysteresis check issued range(CLEAR_CYCLES - 1) clean cycles, which at CLEAR_CYCLES = 1 issues zero, passes, and prints "0 clean cycles do NOT clear it" - green for the chatter setting the constant exists to prevent. Now: ONE clean cycle must not clear the alarm, a literal that does not move with the constant, and the de-assert count is measured by looping until it clears. 3. The re-assert check stimulated at REASSERT_S + 9, green for any value including 3600 - the hour of silence the module promises not to produce. Now stated in wall-clock terms: a loop pinned across the 900 s capacity-tariff quarter must speak at least 5 times and on no more than 20% of cycles. Pinned in both directions. Red confirmed for each: the restored early return (3 checks), CLEAR_CYCLES = 1 (1), REASSERT_S = 3600 (1) and REASSERT_S = 0 (3). Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC |
||
|
|
c040aac4b8 |
SAFETY-03: alarm when a computed setpoint exceeds the rating, do not just clip it
The clamp was never the missing half. specs.md 10.3 records an unclamped integrator climbing ~130 W per 4 s past 10 kW and reporting 14 768 W pinned at the 5 kW rail; clipped silently that is a flat, legal-looking 5000 W hold and nothing says the loop asked for three times it. write_setpoint() - the one path every write takes - now clamps to the VALIDATED max_w and reports whether the raw value differed; check_output_clamp() raises OUTPUT_CLAMP as a notification, an ERROR, an event row and a red status banner. Not a trip: the clamped value is written and the loop keeps running. The rating is max_w and nothing is min()ed at runtime - CFG-01 already refuses a max_w outside the device range at startup. The device range is applied second as defence in depth; it cannot bite after a successful validation, so if it ever does it alarms too and names the bound. No new config key. Decision grew i_clamped / clamped booleans, and that is the load-bearing part: `reason` is one string that slew-limiting and the saturation freeze overwrite, so an alarm keyed on it is silent on exactly the cycles a winding loop produces. Mutating main.py back onto the string drops the 10.3 replay from 2 engagements to 0. Distinct from saturation by construction - no shared reason code, notification id, status row or counter - and checked in the negative, after first asserting the saturation freeze really did engage. Two things found by running it rather than by reading it: a row per engagement flushed the 40-row event log and evicted SAFETY-18's own METER FROZEN? row (now coalesced per episode with an exact count), and a naive clamp turns a nan into a command at the full rating because every comparison against nan is False. test_clamp.py is new: assert-based, no framework. Six author mutations reproduced red, including "clamp kept, alarm deleted". Two of the check's own hypotheses about the freeze/clamp interaction were refused by its sweep and rewritten to what it measured. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC |