glenn schrooyenandClaude Opus 5 f4914a174a TARIFF-01: measure the month's billed peak, and make it survive a restart
checks / unit (pull_request) Successful in 2m38s
The 15-minute block average was already built and unwired. p1.QuarterAverager
computes clock-aligned 900 s blocks, time-weighted over irregular telegram
spacing, offtake-only and per-phase; P1Ingest.blocks was a 96-entry list in
memory that a restart erased. So this is the persistence and the monthly
reduction, not a second accumulator - a second one would be a second source of
truth for the exact quantity the money depends on.

BLOCKS, NOT A SLIDING WINDOW. The card says "rolling"; 9.1 bills "the highest
15-minute average offtake" and states its own worked case per QUARTER - one
4998 W quarter moving a monthly peak from 4832 to 5013 W. A trailing window
reports a peak the meter never bills, and reports it HIGH: a burst straddling
:15 fills the window completely while contributing to two block averages at
partial weight.

DELIVERED, NOT INTENDED. tariff.py only ever sees P1Sample - the meter's own
reading - and never a setpoint. SAFETY-20's open question does not arise for a
capacity tariff: the utility integrates the current that flowed.

AN UNREADABLE STORE IS NOT A ZERO PEAK. peak() answers OBSERVED / NO_RECORD /
NOT_OBSERVED with peak_w None unless observed, which is riglock.holder()'s fix
applied to something that spends money. A peak read as 0 W hands SAFETY-07
maximum headroom and disarms the guard at the moment its own storage breaks.

Restart mid-block resumes the accumulator through a new snapshot()/restore()
pair, checkpointed every 15 s and cleared in the same breath as a block close.
The held sample keeps its ORIGINAL timestamp, so an outage is integrated under
the same max_hold_s rule a running process would apply. quarter_start is the
primary key and a re-bank may only ever RAISE a figure.

Calendar months are LOCAL: a quarter starting 22:15 UTC on 31 August bills in
September.

No new option (the limit is the existing peak_cap_w), so config.yaml and
validate.py are untouched and CFG-03 is not widened. No second peak entity:
peak_forecast_entity stays the input to maintenance_charge_floor(), because
repointing that consumer changes what moves energy and belongs to SAFETY-07.

AC 3 is NOT met. It asks for 30 days of replay; two days of this house's real
meter exist and are committed here. test_tariff.py part 9 replays them, reports
the percentage next to the sample size in days, and asserts nothing about 95 %.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
2026-08-30 19:13:58 +02:00
glenn schrooyenandClaude Opus 5 7aa1bd052e SAFETY-18: a meter frozen at a wrong-but-fresh value now raises an alarm
A meter that answers 200 OK with a stale document forever is ARRIVING on every
poll, so every freshness mechanism in the stack reads it as healthy while the
loop integrates a constant error and rails: 360/135/75 s at the live install's
max_w: 5000 for a meter frozen at 350/1000/>=3000 W. Fifteen minutes of a 5 kW
unattended import sets the month's billed capaciteitstarief peak.

The detector is a conjunction, not the bare unchanged_s threshold TEL-05
measured and rejected:

    unchanged_s >= meter_freeze_s   AND   |command| within 5 % of max_w

Both terms already existed and were already on the status page, and they fail
for independent reasons: at the converged point the command is nowhere near the
rail, and at the rail against a real load the kWh registers move in seconds. At
the shipped 300 s the relation is structural rather than a margin - the slowest
a healthy 1 Wh register can tick and still look unchanged is 12 W, which is
inside the 15 W deadband, so the command there is parked at 0 W.

Notification only, deliberately: an HA persistent notification with a fixed
notification_id, an ERROR log line, a UI event and a red status row. No claim,
no latch, no 0 W. A false trip parks the battery; a false notification costs an
alert. Only meter_source: homewizard_local is covered - the status page says
NOT COVERED elsewhere rather than pretending the guard is armed.

DOCS.md states the capacity-tariff exposure this does NOT close: peak_cap_w caps
maintenance charging and nothing caps the loop. That cap is SAFETY-07.

test_freeze.py grades both directions and was verified by breaking what it
watches (six mutations, all red): silent over the committed 40-minute converged
capture, silent over an hour of TEL-05's low-power case where the rejected bare
threshold is shown to fire, alarming on a genuinely frozen meter driven over
real HTTP through the real HomeWizardLocalSource (the rig's own hwsim freeze
fault when reachable), silent on the same railed command against a meter that is
still moving, and asserting on the service call that leaves Controller.cycle()
rather than on the watchdog's own flag.