065792aad3 |
Merge release/1.0 (e3e4ba6) into opt15-price-run-fixes
Conflicts (5 files, 9 hunks) resolved keeping both sides:
- p1.py: held_t (OPT-15) beside held_since (SAFETY-90).
- modetrade.py: chargers() takes targets (P4) and probe (OPT-15); decide()
clears the chargers, a probing refuser included, while a battery drains
(SAFETY-78); the docstring lists both rules.
- main.py: the roll goes into the SAFETY-90/91 projection chain
(`_peak_proj`); the SAFETY-95 drain-tail grid_w keeps the run-edge hold on
its other branch; the P4 forecast state and the hold state both stay.
- DOCS.md, DECISIONS: both lines kept, OPT-15 item refreshed.
Adaptations the merge needs:
- SAFETY-81 x F1: a rolled projection is not graded by the saturation alarm
until the quarter's first sample, as the old edge tick was not, so a
standing overload is still notified once per quarter.
- test_safety81, test_modes_p4: modes-on pins re-pinned (with a note), modes
off pinned to e3e4ba6; test_price_run_fixes: identity pins on
|
||
|
|
9d3fbe1be9 |
SAFETY-90: the peak guard goes on after a P1 meter gap
A meter gap past meter_max_age_s left seconds the quarter average never counted, so the guard was blind for the rest of the quarter (rig case 7b: 3964.8 W against a 3450 W aim). Once readings are back, the missed seconds now count at the higher of the limit and the import seen just before and just after the gap with the batteries at 0 W (peakguard.gap_w/fill_gaps); the gap's first meter_max_age_s is topped up to that too. Seconds before the add-on's first reading count at the aim, and the page says part of the period was not measured (EN/NL). The bill record is unchanged; no option. DECISIONS/SAFETY-90-peak-guard-after-a-gap.md, test_safety90.py. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> |
||
|
|
fae6681e19 |
OPT-15: price-run fixes (quarter edge, charge-end overshoot, refusal probe)
F1: with battery modes on, the peak guard projects the quarter `now` is in
even before its first P1 sample (PeakTracker.project(roll=True)), and only
a measured stop latches the period. The edge tick no longer reads "no
seconds left", so a charge is not stopped and latched at a quarter edge.
F2: after a run edge the loop is held at E until the meter shows the step
(EDGE_HOLD_S, longer while the battery still moves). The replay gained a
lag model (dead time, reading age, P1 debounce, 1 s cycles) that shows
TEST-23's overshoot without the hold.
F3: a charge refuser's SAFETY-73 probe inside a cheap run is a charger
pinned at PROBE_W, the others rest, so the probe actually runs.
Modes off stays byte-identical to
|
||
|
|
23a3a3f5b5 |
UX-10: the last plain-language leftovers: log lines, two table rows, 'Why: Other', red at 0 s
- test_messages.py part 6: every dynamic part of a WARNING+ line is classified as data or as a built text, and every built text is produced by the real code and checked. This is the gap the 2d scan had: it counted `%s` as one word, so reasons built by loop_clamp_note() and friends were never seen. - Quoted reasons rewritten to STYLE.md (red-alarm shape, codes kept): OUTPUT_CLAMP, METER_FROZEN, CIRCULATING_POWER, STALE_READING, the peak guard (codes now PEAK_GUARD*), the migration report, price feed, price history and gate reasons. Plurals via messages.times()/count(). - Top table: Price history "96 prices over 24 hours for 26 Sep", Tariff "one every 15 minutes or every hour", "not final yet" dropped. - Levels and noise: per-cycle shadow line DEBUG, shadow on/off INFO, aiohttp access log only at log level debug, settings warnings once per start, one plain line per Home Assistant outage (hass.Outage). - INFO jargon and error texts: no "§8.3", ISO times, "banked", "keys ARE", "NOT_OBSERVED", "did NOT land", "AND". - Display bugs: WHY_WINNER covers every winner and safety reason (main.why_key(), part 7 finds them in the code); the meter row is amber "waiting for the first reading" inside its limit after a start; the missing-reading age is counted when the page asks. - STYLE.md and DECISIONS/UX-08-short-notifications.md (UX-10 section). No change to safety behaviour, alarm levels, notification ids, triggers, cadence or the banner cascade. One row colour changes (meter at start), justified in DECISIONS. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> |
||
|
|
569f16aa91 |
UX-08 2d review: action log reachable in status JSON, engaged peak row pinned, imported keys expanded
- status_payload() also returns the action log as `events`. The page does not render it. Some entries (a dropped inverter's reason, the peak guard's projection, unplaced watts) are written nowhere else, and DOCS still points installers at the action log. - test_peakguard pins the engaged row's ordered pair (the battery's share, then the limit). - test_messages expands setting keys named by constants imported from another app module, so the shown-text 30-word scan counts them. - p1.py: 'A meter message could not be read'. DOCS glossary: control board in plain words, with the hardware in an installer note. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> |
||
|
|
6a95447248 |
UX-08 2d: plain log lines, the rest of the status page, and DOCS
Every WARNING and ERROR line is one plain line of at most 25 words, with no card ids, capitals or semicolons; the reasoning of the ten longest is on a DEBUG line. The ux08 allowlist is empty and its cap is 0 (43 -> 0). The status page: the month-peak and peak-guard rows, the stale-reading row, the top table (Why, Tariff, Arbitrage, Shadow mode, labels), the Stopped banner and the line under the buttons, which now shows the plain hint of each event instead of the raw action log. The Supervisor question at start logs one line with a real reason. Refusals are counted as shown (labels expanded, long cases driven), seven were shortened, the card and parse errors lost their internals, a blank value reads "empty", and the panel no longer files inverters.max_w under the flat max_w. Option names lose "(JSON)", the NL texts are checked too. DOCS gets a glossary (control board, isolator, Developer Tools) and card ids move from headings to a "For installers" line. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p |
||
|
|
2c516a032c |
UX-08 2c: short refusals, error texts and option texts
Validator refusals name the setting by its label and key, say what is wrong and what to change, and keep the rejected value and limit. Option names and descriptions are short in en and nl; citations moved to DOCS "For installers" and the test_translations citation check now pins the instruction on the tab and the record in DOCS. No rule, key, schema, default or exit code changed. Allowlist 167 -> 43 (log lines only). Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01LyR88rXETvwhTgx6yHE39p |
||
|
|
616b62d3e9 |
SAFETY-07: cap the loop before it sets the month's billed capacity peak
checks / unit (pull_request) Successful in 3m7s
TARIFF-01 measured the quarter and said the consumer would be this card. It is
one new module, app/peakguard.py, and one new claim.
THE MECHANISM. Every cycle the guard projects the open 900 s block to its
end-of-interval average - from P1 telegrams only, never from the command - and
compares it to a ceiling. Over the ceiling it files ONE arbiter claim: a lower
bound on the setpoint at P_PEAK. That single shape is both behaviours 10.1 asks
for, a hard clamp on charging and pre-emptive discharge, and it cannot cap
discharge or export, because a floor cannot. 9.1's asymmetry becomes a property
of the object instead of a rule to remember.
excess = 900 x (projected - ceiling) / seconds remaining
floor = MEASURED battery power + excess
The 900/remaining gain is 1.0 at the top of the quarter and grows, so the guard
is gentlest where its projection rests on the least evidence. The floor is sized
from delivered battery power, not the standing command: a floor built on intent
re-adds its own unmet ask every cycle and winds to the rail whenever the inverter
fails to follow, and test_peakguard.py part 1 shows the two diverging.
IT TRIPS, AND THE CAPTURES DECIDED THAT. On the healthy reference day it engages
on zero of 95 quarters. The action is level-triggered, unlatched and re-derived
every cycle, so a false engagement costs one cycle of discharge rather than a
parked battery - the cost SAFETY-18 could not bound and this one can. Replayed on
2026-08-20 the billed quarter goes from 5029.8 W, above the inverter's own 5000 W
rating, to 3485 W, under the soft limit and without saturating. Quarters under
the limit across both committed days: 189/190 -> 190/190. Two days is not thirty
and AC 3 remains TARIFF-01's open item.
BLINDNESS IS CHECKED BEFORE THE PROJECTION IS GRADED, and it is a different
action. A fresh averager projects a confident 0 W, which is under every ceiling
there is; a meter gap longer than meter_max_age_s makes the projection read LOW;
a frozen meter reading export projects 0 W at full coverage. All three become a
floor of 0 W - no importing while the billed quantity is unobservable - which is
one-directional and cannot cost pack energy. That is the backstop SAFETY-18 could
not be: its alarm arrives at 300 s of a 900 s quarter and commands nothing. The
frozen term is freeze.looks_frozen() itself, on this cycle's standing command.
THE CEILING IS peak_cap_w, RAISED ONLY BY AN OBSERVED READING. NO_RECORD and
NOT_OBSERVED both leave it at the cap, so an unreadable peak store makes the
guard stricter and never looser. The gate is the reading's STATE, not whether a
number happens to be attached: today a `peak_w is not None` test behaves
identically, and depending on that coincidence is how a future last-known-peak
field would raise the ceiling off a read that failed. headroom_w() is
deliberately not consumed - cap minus peak turns a zero peak into FULL freedom.
TWO DEFECTS FOUND BUILDING IT, both in the interaction rather than the
arithmetic, and both caught by running the thing rather than by reading it:
* A LIMIT does not out-vote another LIMIT. arbiter.resolve() applies every
limit at or above the winner's priority and takes the most restrictive, so
the peak floor (lo >= 0) and the maintenance charge-only shaping (hi <= 0)
resolved to a CONTRADICTION and 0 W - the battery parked in the exact quarter
it should shave. Fixed by suppression, not priority: main.py drops the
maintenance shaping while the guard is engaged, which is what that branch
already did for the optional peak_forecast_entity - a key empty on a default
install, so until now the suspension could not fire on the site that needed
it.
* Thresholding `excess > 0` released the claim the instant it began working,
producing seventeen engage/release cycles in one 900 s quarter and leaving
that quarter 49 W over the limit it had spent fifteen minutes holding. That
is 10.2's oscillation. The threshold is now the floor itself, which is the
same arithmetic read as a level rather than as a switch.
PeakTracker.project() no longer reads a private name with a default.
getattr(averager, "_last_net", 0.0) failed quiet AND disarming - a rename credits
0 W held, the projection reads low, the money guard does not engage.
QuarterAverager.held_net_w is a documented public property now, read without a
default, and Projection carries it. TEST-13 item 4.
NO NEW OPTION AND NO FOURTH DEFAULTS SITE. The ceiling is peak_cap_w, the
coverage threshold is meter_max_age_s, the freeze predicate is meter_freeze_s,
and the achievable discharge comes from max_w and the device rating. config.yaml
and validate.py are untouched; 14's capacity_peak_limit_kw stays declined. On
meter_source: off there are no telegrams, so the guard does not run at all and
the status page says NOT COVERED - running it there blinded it permanently and
stopped every legacy install from charging, which is what the first cut did until
test_clamp.py's export case caught it.
test_peakguard.py: eight parts, all figures derived from the shipped config.yaml
and the committed captures. Part 8 runs seven one-line defeats of the guard and
reports which check bites; six do, and the seventh is reported as NOT caught,
because max(cap, peak) makes a zero peak the strictest ceiling there is and there
is nothing left to catch.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC
|
||
|
|
f4914a174a |
TARIFF-01: measure the month's billed peak, and make it survive a restart
checks / unit (pull_request) Successful in 2m38s
The 15-minute block average was already built and unwired. p1.QuarterAverager computes clock-aligned 900 s blocks, time-weighted over irregular telegram spacing, offtake-only and per-phase; P1Ingest.blocks was a 96-entry list in memory that a restart erased. So this is the persistence and the monthly reduction, not a second accumulator - a second one would be a second source of truth for the exact quantity the money depends on. BLOCKS, NOT A SLIDING WINDOW. The card says "rolling"; 9.1 bills "the highest 15-minute average offtake" and states its own worked case per QUARTER - one 4998 W quarter moving a monthly peak from 4832 to 5013 W. A trailing window reports a peak the meter never bills, and reports it HIGH: a burst straddling :15 fills the window completely while contributing to two block averages at partial weight. DELIVERED, NOT INTENDED. tariff.py only ever sees P1Sample - the meter's own reading - and never a setpoint. SAFETY-20's open question does not arise for a capacity tariff: the utility integrates the current that flowed. AN UNREADABLE STORE IS NOT A ZERO PEAK. peak() answers OBSERVED / NO_RECORD / NOT_OBSERVED with peak_w None unless observed, which is riglock.holder()'s fix applied to something that spends money. A peak read as 0 W hands SAFETY-07 maximum headroom and disarms the guard at the moment its own storage breaks. Restart mid-block resumes the accumulator through a new snapshot()/restore() pair, checkpointed every 15 s and cleared in the same breath as a block close. The held sample keeps its ORIGINAL timestamp, so an outage is integrated under the same max_hold_s rule a running process would apply. quarter_start is the primary key and a re-bank may only ever RAISE a figure. Calendar months are LOCAL: a quarter starting 22:15 UTC on 31 August bills in September. No new option (the limit is the existing peak_cap_w), so config.yaml and validate.py are untouched and CFG-03 is not widened. No second peak entity: peak_forecast_entity stays the input to maintenance_charge_floor(), because repointing that consumer changes what moves energy and belongs to SAFETY-07. AC 3 is NOT met. It asks for 30 days of replay; two days of this house's real meter exist and are committed here. test_tariff.py part 9 replays them, reports the percentage next to the sample size in days, and asserts nothing about 95 %. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_015VXjA3LWccN1rJsk3okyPC |
||
|
|
fc9bd89dca |
CFG-01: refuse to start on a configuration that cannot be honoured
main.py used to read the setpoint device's own +-5000 W rating, notice a
configured max_w above it, log one WARNING, and run anyway with
write_setpoint() quietly clamping. The operator's stated ceiling was never
the real ceiling and the only evidence had scrolled off the log. specs
§1.5 is explicit that such a config is refused at startup, not survived at
runtime.
validate_startup_config() runs in amain() before the broker, the web
server or any task exists, so a refusal cannot leave half a controller
running behind a UI. It refuses exactly three things, all sharing one
property - continuing makes a safety mechanism inoperative or makes a
stated limit untrue:
1. max_w outside the setpoint device's own rating.
2. No setpoint_entity: every write is a no-op, the device rating is
never read, and the ESP32 heartbeat that holds off the layer-1
failsafe never happens. It ran, looked healthy, and moved nothing.
3. A meter_source that can never produce a reading. These were already
caught, but they only DISABLED ingestion, which leaves grid None
forever: permanent inputs-missing, 0 W, and a status page
indistinguishable from a healthy meter nobody has fed yet.
Those last predicates move into p1.validate_meter_options(), which
build_source() also calls - one definition, two callers, not two
competing validators. ha_dsmr with half its entities and mqtt_p1 with a
blank topic gained the check the other two transports already had.
Deliberately not refused, because untidy is not unsafe: integrator_max_w
above max_w (the arbiter still bounds the wire to +-max_w, so the cost is
unwind latency - warned), a missing soc/batt entity (fail-safe and
already a red NOT READY banner), a setpoint entity that has not appeared
on the Core API yet (ESPHome is routinely late; re-checked in
run_control() once the real rating arrives), and a thin meter_poll_s
margin.
A refusal is legible as one: a banner saying in words that this is
configuration and nothing is broken, numbered problems, no traceback, and
exit 78 (EX_CONFIG).
Verified on the live add-on 2026-08-28, not by reading the code: a blank
setpoint_entity and a meter_poll_s equal to meter_max_age_s each stopped
the add-on with the banner and no stack trace.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
|
||
|
|
4d41b0a79e |
TEL-05 review follow-ups: show unchanged_s, name a timeout, keep the poll task alive
Four follow-ups on the reviewed and approved TEL-05 work. Additive; no shipped behaviour changes except the two failure paths below. 1. unchanged_s had no operator surface. DOCS.md told a reader "the transport tracks it as unchanged_s" and there was nowhere to look: main.py built the transport, scheduled run(), and never read the object again. The status page now shows it on the healthy P1 line. Still NOT thresholded and NOT folded into the age - that refusal was reviewed and upheld, because at the converged -10 W this controller aims for a 1 Wh register needs ~6 minutes to move, so any limit false-trips at the target operating point. The whole argument for leaving it to a human requires the human being able to see it. 2. The "equivalent mutant" note on the content_type guard was wrong, and the comment is downgraded to say so. web.Response(text=...) defaults to text/plain, so the fake meter CAN serve valid JSON under the wrong mimetype. Test added; shipped behaviour was already correct. 3. A timed-out poll logged an empty reason: str(asyncio.TimeoutError()) is "", so the status page read "last error:" and then nothing, on a hung meter, at the moment the battery had just gone to 0 W. Falls back to the class name. Note str(err), not `err or ...` - an exception object is always truthy. 4. submit() sat outside the try in poll_once() and run() had no except, so a raise would kill the poll task permanently and SILENTLY - safe (the age climbs, the controller commands 0 W) but indistinguishable from a dead meter. Both wrapped; poll_s is already the retry cadence, so no backoff. Also a comment at the parse_homewizard range(phases) slice: a 3-phase meter configured as 1-phase understates the capacity-tariff figure. Filed separately, not fixed here. 242 checks in test_p1.py (236 before, 6 new). test_control 55, test_arbiter 18, test_maintenance 21, all untouched and green. Each new check proved non-vacuous: six mutations, six named reds, no suite aborts, sources restored byte-identical. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa |
||
|
|
98109a9b91 |
TEL-05: read the meter, not Home Assistant's opinion of the meter
A fourth meter_source, `homewizard_local`, polling a HomeWizard P1's own local API (GET /api/v1/data) instead of watching an HA entity. The point is the age sensor. sensor.p1_sample_age_s is FW-01's watchdog input, and on every transport we had it measured "time since the value CHANGED", not "time since the meter REPORTED". Home Assistant offers nothing better: a repeated reading emits no state_changed, advances last_reported on neither serialiser, and state_reported cannot be subscribed to at all. Measured twice - 70 s of a frozen meter on the ENV-01 rig, and ten repeated readings against the live house. Our own capture of this house's meter goes 42.2 s and 97.0 s between changes, both past the default meter_max_age_s of 30, so the age sensor would have commanded 0 W on a perfectly healthy meter. Here every HTTP response is an arrival. The meter answered, now, with its current reading; whether the number moved is not consulted. Five identical readings are five arrivals. Reuses TEL-01's pipeline rather than restructuring it: same split_signed sign convention as ha_signed, same make_sample, same ingest stamping, meter_max_age_s, clock-recomputed age, plausibility bounds and the §20 unsigned-decode rejection. A failed or timed-out poll submits nothing, so it is a missing reading - never 0 W - and does not reset the age. meter_poll_s (default 5 s, the meter's own rate) is checked against meter_max_age_s once at startup, like the ha_signed entity ids. ⚠️ An arrival stamp cannot see a FROZEN meter, and no arrival detector can - one answering 200 OK with a stale number is arriving. The local API does expose what HA never had (the total_power_*_kwh registers stop advancing) and the transport tracks it as `unchanged_s`, but it is deliberately not folded into the age and not thresholded: this controller regulates grid toward ~0 W, and at a converged -10 W the export register needs six minutes to move by its 1 Wh resolution while the power figure legitimately repeats. Thresholding that would rebuild the false-trip limit cycle at the exact operating point we aim for. test_p1.py 179 -> 236 checks. Still defaults to off. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa |
||
|
|
e663e10245 |
TEL-04 review: unshadow the helper, validate config at startup, and record
what the rig proved about the age sensor
Review findings 1, 3, 5 and 6. Finding 2 is deliberately untouched - it is
its own ticket.
3. `built` was rebound at test_p1.py:816 by `built = build_source(...)`,
silently disarming the build() wrapper for anything appended below it.
Renamed to `sel`. Reproduced the reviewer's failure before fixing:
appending a check that calls built() after that line gives
`TypeError: 'HaSignedSource' object is not callable` and aborts at 163 of
180; with the rename the same probe reaches 180 and passes.
5. DOCS.md now states the "length must equal meter_phases" constraint that
config.yaml already carried, plus what leaving the list empty actually
costs: on the surveyed reading the phases carry 2769 W of import while the
connection nets 187 W, so the tariff quantity is understated ~15x.
6. build_source now checks the ha_signed wiring once at startup instead of
once per telegram: a blank p1_net_entity, or a phase list whose length
disagrees with meter_phases, logs an error and disables ingestion. Both
otherwise fail in the single way indistinguishable from a healthy source
nobody has fed yet - no samples, a climbing age, the watchdog holding the
battery at 0 W, and nothing in the log.
1. THE AGE SENSOR. Measured on the ENV-01 rig against the real HomeWizard
integration, meter frozen via hwsim's `?fault=freeze` seam (cleared in a
finally:, rig verified restored):
- websocket state_changed for the meter over 70 s : 0
- last_reported advanced (REST serialiser) : no
- last_reported advanced (websocket serialiser) : no
- subscribe_events(state_reported) : rejected,
"Event filter is required for event state_reported"
So Home Assistant exposes NO arrival signal for a repeated reading, and
the proposed fix - stamp from last_reported via subscribe_entities - is
not available. subscribe_entities listens only to EVENT_STATE_CHANGED, and
as_compressed_state carries no last_reported at all.
The age is therefore "time since the value changed", which on ha_dsmr is
mostly harmless (a telegram moves several entities) and on ha_signed is
not: one entity means a healthy meter under a flat load is
indistinguishable from a dead one. Recorded loudly in DOCS.md, in the
HaSignedSource docstring and in the CHANGELOG, with the measured 42.2 s
and 97.0 s gaps from our own capture.
meter_max_age_s is deliberately NOT widened. The two conditions produce an
identical signal, so a larger number does not separate them - it only
chooses which of the two errors you get, and it would disarm the watchdog
for a genuinely dead meter as well. The honest fix is an arrival stamp the
meter itself provides.
test_p1.py: 174 -> 179 checks, all green. Other three suites unchanged.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
|
||
|
|
8b51a51e20 |
TEL-04: a third meter_source for a single signed entity
TEL-01 shipped ha_dsmr and mqtt_p1, and neither can read the meter that is
actually fitted here. The house has a HomeWizard P1 exposing ONE signed
entity, sensor.p1_meter_active_power (+ import, - export); ha_dsmr wants two
unsigned registers and refuses a negative one outright, which is every
exporting telegram. So sensor.p1_sample_age_s could not be produced at this
site, and FW-01's watchdog needs it - measured, not theoretical: the house P1
went 51.1 s and 36.2 s without a state change overnight, both past
meter_max_age_s 30, so without the age sensor the watchdog would false-trip
the battery to 0 W.
Adds meter_source: ha_signed, reading p1_net_entity (and optionally
p1_phase_net_entities in L1..L3 order for the capacity-tariff peak). The
derivation is split_signed(), sitting next to make_sample's subtraction for
the same reason it does - the moment a user is asked to write two template
sensors that split a signed value, the sign convention is back in unreviewed
YAML underneath a safety input, which is exactly what TEL-01 removed.
The transport is a subclass of HaDsmrSource overriding only _wanted() and
build(), so every rule TEL-01 established is inherited rather than
re-implemented: ingest timestamping, meter_max_age_s, the clock-recomputed
sensor.p1_sample_age_s republished ~1 Hz, the plausibility ceiling, the
"prime the cache from get_states but never build a sample out of it" rule,
"a reconnect emits nothing", and unavailable/unknown treated as a MISSING
reading and never as 0 W.
Defaults to off. An existing install is unaffected until it opts in.
test_p1.py: 122 -> 174 checks. Includes an end-to-end run of the new
transport against a fake Home Assistant websocket, and the sign convention
asserted against real captured readings from
sim/scenarios/ha-p1_meter_active_power-2026-08-{20,23}.json (-5710 W at
13:46 local under full sun is export; +775 W at midnight is import).
Non-vacuity: ten mutations of the new rules, each applied alone and reverted
byte-identical. Nine turn the suite red. The tenth - splitting the per-phase
signed values rather than passing them through - is an equivalent mutant,
because make_sample subtracts the two lists again and does not sign-check
per-phase figures. That is recorded in a ponytail: comment at the site rather
than left for the next reviewer to rediscover.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
|
||
|
|
4bd659c499 |
TEL-01 review fixes: stop the age sensor tripping installs that have no meter
T-1, and it was a fleet-wide trip to zero. publish() emitted p1_age unconditionally, and published_age_s counts from P1Ingest.__init__ when no sample has ever arrived. With meter_source defaulting to off, every existing install would have published sensor.p1_sample_age_s climbing without bound; the ESP32 does `has_state() && state >= max_age_s` and forces the layer-1 failsafe, so each of them would have pinned its inverter at 0 W within 30 s. Exactly the opposite of the zero-regression the off default was for. The key is now omitted from the payload AND from MQTT discovery when P1 is off, so the entity does not exist at all - which is the status quo, and what has_state() is testing for. The predicate is one function, is_enabled(), because the grid reading, the task start and the discovery announcement have to agree or this comes back. T-2, connect no longer manufactures a sample. get_states returns whatever HA currently holds, which after a Core restart is a RestoreEntity value of unknown age; stamping it with ingest_ts=now reset the age and reported a fresh meter that could have been dead for an hour. run()'s own docstring already said a reconnect must emit nothing - the code disagreed with it, and a test asserted the violation. The cache is still primed, so the first real state_changed builds a complete sample; the age just stays honest until one arrives. T-3, gaps are no longer filled with the last held value. The averager held a sample forward across any interval, so a meter dying at 5 kW and returning ten minutes later credited 5 kW x 600 s to the capacity-tariff accumulator - a fabricated peak on a permanent record. The hold is capped at max_age_s: past that the stretch is walked so block boundaries still land correctly, but nothing accumulates and elapsed does not grow, which is what finally makes the comment about a gap dragging the billed average down true. Same threshold for control and billing: a reading too old to steer by is too old to bill by. T-4, the out-of-order/duplicate guard is covered. It was untested, and the reason is worth recording: the obvious assertion passes without the guard, because the negative interval is separately refused by the covered > 0 test. What the guard prevents is the timestamp REWIND, which only shows up one sample later as a re-integrated window. The test now goes one sample later. T-6, DOCS was wrong about latency. meter_max_age_s and stale_input_s stack, so meter death to 0 W is 45 s and not 30. Documented as a table with both clocks. Also documented the T-5 asymmetry rather than papering over it: the age measures arrival, not change, so a stuck MQTT bridge republishing its last telegram still looks fresh. Correct on ha_dsmr, not detectable on mqtt_p1 without a change-detector. Written up as a known limit. Writing the T-1 test caught a second defect in the test itself: it recorded only MQTT topics, and object_id lives in the payload, so "the age sensor is not announced" had been passing for the wrong reason. test_p1.py: 99 -> 122 checks. 14 mutations run, all 14 red, files restored byte-identical - including one per fix above. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa |
||
|
|
f47f1f0129 |
TEL-01: P1 ingestion, with the derivation and the age the EMS owns
A Belgian P1 meter publishes two UNSIGNED registers, not one signed figure. Until now the add-on asked the installer to bridge that gap with a template sensor, which put the sign convention of the whole control loop in a text box. This moves it into the EMS: net = import - export, derived once, in one place, with a test that fails if anyone inverts it. Two transports behind one contract, chosen by `meter_source`: the HA WebSocket subscribing to the DSMR integration's entities, and MQTT on a configurable topic. Everything downstream reads P1Ingest, so switching is a config edit. `meter_source: off` is the default and keeps the existing meter_entity path, so no installed system changes until it opts in. The other half is the timestamp. Every accepted sample is stamped at ingest with a monotonic clock, `meter_max_age_s` is applied to it, and the age is published as sensor.p1_sample_age_s for the ESP32's stale-input watchdog. That entity is recomputed against the clock every second rather than only when a telegram lands, because HA pushes state only on change: a meter frozen at a constant reading emits nothing and looks, to anything watching the value, exactly like a meter that has died. The age tells them apart. Deliberately absent: any fallback to an inverter-side power figure. The inverter's own AC power correlates 0.998 with battery power and 0.09 with the real meter, so failing over to it means regulating against your own output. A gap stays a gap - a reconnect emits no synthetic sample, and a rejected telegram never resolves to 0 W or refreshes the timestamp. Quarter-hour averages are time-weighted over clock-aligned blocks rather than a mean of samples, so a cadence change cannot bias the capacity-tariff figure, and only offtake is accumulated so a quarter of pure export averages to 0 kW. Per-phase import is kept separately: on an unbalanced three-phase load the phase sum and the connection net are different numbers, and only one of them is billed. test_p1.py: 99 checks, runnable with a bare interpreter and no meter. Includes an end-to-end run of the HA transport against a fake Home Assistant websocket. Stacked on SAFETY-04; nothing here touches control.py. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa |