SAFETY-119: no "not keeping up" when the loop takes the wire back
When the peak guard or a maintenance charge hands the wire back, the loop's integrator is re-seeded from that owner's command and kicked by a meter that does not show it yet. It crossed its rail for a cycle or two and raised goodwe_integrator_bound while the battery gave what it was told. The loop's integrator bound is not counted until the plant's settle (SHORT_CYCLES, SHORT_SPAN_S) has passed since the hand-back. An over-rating always counts; a bound that lasts warns after the settle. No command changes and no text changes. test_safety119.py; DECISIONS entry. Co-Authored-By: Claude <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude
parent
75f0804f9d
commit
c4e15ec4cd
@@ -0,0 +1,27 @@
|
||||
# SAFETY-119 - no "not keeping up" when the loop takes the wire back
|
||||
|
||||
**Status: for review.** Tests: `test_safety119.py`.
|
||||
|
||||
**Cause.** When another owner (the peak guard, a maintenance charge) has set
|
||||
the wire and the loop wins again, `cycle()` re-seeds the integrator from that
|
||||
owner's command, and `compute()` adds `gain * error` from a meter that does
|
||||
not show that command yet. On the TEST-23 rig (SAFETY-118 I-2) the guard's
|
||||
last-seconds step went from -2000 W to +429 W. The next cycle's ask crossed
|
||||
the +2500 W rail and beat the guard's floor, so SAFETY-85 rule 1 counted it
|
||||
as the loop's own bound and raised `goodwe_integrator_bound`. The battery gave
|
||||
what it was told; the cap held.
|
||||
|
||||
**Decision.** On the cycles after a hand-back, the loop's integrator bound is
|
||||
not counted until the plant's settle has passed (`SHORT_CYCLES` cycles and
|
||||
`SHORT_SPAN_S`, the same window SAFETY-85 grades a battery on). After that it
|
||||
counts as before. An over-rating (`clamped`, a bug) always counts. No command
|
||||
changes, and no text was added or changed.
|
||||
|
||||
**Kept.** The loop in charge at its rail warns on the same cycle as before. A
|
||||
loop still at its rail after the window warns then (about 22 s later): delay,
|
||||
not loss. The start and a restart after a stop are not hand-backs.
|
||||
|
||||
**Not changed.** The kick itself is control behaviour: for a few seconds at
|
||||
a quarter's edge the loop asks up to its rail. In `test_safety119.py` part 1
|
||||
that is more discharge than the guard asked at a quarter's end, and about
|
||||
1700 Ws more charge (2 W on that quarter's average) at the next one's start.
|
||||
Reference in New Issue