When the peak guard or a maintenance charge hands the wire back, the loop's integrator is re-seeded from that owner's command and kicked by a meter that does not show it yet. It crossed its rail for a cycle or two and raised goodwe_integrator_bound while the battery gave what it was told. The loop's integrator bound is not counted until the plant's settle (SHORT_CYCLES, SHORT_SPAN_S) has passed since the hand-back. An over-rating always counts; a bound that lasts warns after the settle. No command changes and no text changes. test_safety119.py; DECISIONS entry. Co-Authored-By: Claude <noreply@anthropic.com>
1.5 KiB
SAFETY-119 - no "not keeping up" when the loop takes the wire back
Status: for review. Tests: test_safety119.py.
Cause. When another owner (the peak guard, a maintenance charge) has set
the wire and the loop wins again, cycle() re-seeds the integrator from that
owner's command, and compute() adds gain * error from a meter that does
not show that command yet. On the TEST-23 rig (SAFETY-118 I-2) the guard's
last-seconds step went from -2000 W to +429 W. The next cycle's ask crossed
the +2500 W rail and beat the guard's floor, so SAFETY-85 rule 1 counted it
as the loop's own bound and raised goodwe_integrator_bound. The battery gave
what it was told; the cap held.
Decision. On the cycles after a hand-back, the loop's integrator bound is
not counted until the plant's settle has passed (SHORT_CYCLES cycles and
SHORT_SPAN_S, the same window SAFETY-85 grades a battery on). After that it
counts as before. An over-rating (clamped, a bug) always counts. No command
changes, and no text was added or changed.
Kept. The loop in charge at its rail warns on the same cycle as before. A loop still at its rail after the window warns then (about 22 s later): delay, not loss. The start and a restart after a stop are not hand-backs.
Not changed. The kick itself is control behaviour: for a few seconds at
a quarter's edge the loop asks up to its rail. In test_safety119.py part 1
that is more discharge than the guard asked at a quarter's end, and about
1700 Ws more charge (2 W on that quarter's average) at the next one's start.