SAFETY-119: re-pin test_safety84/87 digests (log only); prove it
The re-pinned digests differ only in OUTPUT_CLAMP log rows; every command and claim is the same as without the fix (test_safety119.py part 5). DECISIONS: the delay at a 5 s meter and the open swap case. Co-Authored-By: Claude <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude
parent
c4e15ec4cd
commit
b0c2e5977d
@@ -5,23 +5,33 @@
|
||||
**Cause.** When another owner (the peak guard, a maintenance charge) has set
|
||||
the wire and the loop wins again, `cycle()` re-seeds the integrator from that
|
||||
owner's command, and `compute()` adds `gain * error` from a meter that does
|
||||
not show that command yet. On the TEST-23 rig (SAFETY-118 I-2) the guard's
|
||||
last-seconds step went from -2000 W to +429 W. The next cycle's ask crossed
|
||||
the +2500 W rail and beat the guard's floor, so SAFETY-85 rule 1 counted it
|
||||
as the loop's own bound and raised `goodwe_integrator_bound`. The battery gave
|
||||
what it was told; the cap held.
|
||||
not show that command yet. On the TEST-23 rig (SAFETY-118 I-2) the guard
|
||||
stepped from -2000 W to +429 W with 5 s left. A cycle later the loop's ask
|
||||
crossed the +2500 W rail and beat the guard's floor, so SAFETY-85 rule 1
|
||||
counted it as the loop's own bound and raised `goodwe_integrator_bound`. The
|
||||
battery gave what it was told, and the cap held.
|
||||
|
||||
**Decision.** On the cycles after a hand-back, the loop's integrator bound is
|
||||
not counted until the plant's settle has passed (`SHORT_CYCLES` cycles and
|
||||
`SHORT_SPAN_S`, the same window SAFETY-85 grades a battery on). After that it
|
||||
**Decision.** After a hand-back, the loop's integrator bound is not counted
|
||||
until the plant's settle has passed (`SHORT_CYCLES` cycles and
|
||||
`SHORT_SPAN_S`, the window SAFETY-85 grades a battery on). After that it
|
||||
counts as before. An over-rating (`clamped`, a bug) always counts. No command
|
||||
changes, and no text was added or changed.
|
||||
|
||||
**Kept.** The loop in charge at its rail warns on the same cycle as before. A
|
||||
loop still at its rail after the window warns then (about 22 s later): delay,
|
||||
not loss. The start and a restart after a stop are not hand-backs.
|
||||
**Kept.** The loop in charge at its rail warns on the same cycle as before.
|
||||
A loop still at its rail after a hand-back warns once the window has passed:
|
||||
22 s at a 2 s meter, 55 s at 5 s. Delay, not loss. The start and a restart
|
||||
after a stop are not hand-backs.
|
||||
|
||||
**Re-pinned.** test_safety84 (all six) and test_safety87 (`n1_crossing`,
|
||||
`n1_above`, `n1_charge_low`): only OUTPUT_CLAMP log rows differ; commands and
|
||||
claims are the same (`test_safety119.py` part 5).
|
||||
|
||||
**Open.** If another owner and the loop swapped the wire every few cycles,
|
||||
each swap restarts the window and the loop's bound would not be counted.
|
||||
A loop at its rail beats a floor or ceiling on its own side, so it keeps the
|
||||
wire; a swap needs a claim that keeps outranking it.
|
||||
|
||||
**Not changed.** The kick itself is control behaviour: for a few seconds at
|
||||
a quarter's edge the loop asks up to its rail. In `test_safety119.py` part 1
|
||||
that is more discharge than the guard asked at a quarter's end, and about
|
||||
1700 Ws more charge (2 W on that quarter's average) at the next one's start.
|
||||
that is more discharge than the guard asked at a quarter's end, and a few
|
||||
seconds of up to 500 W more charge at the next quarter's start.
|
||||
|
||||