The re-pinned digests differ only in OUTPUT_CLAMP log rows; every command and claim is the same as without the fix (test_safety119.py part 5). DECISIONS: the delay at a 5 s meter and the open swap case. Co-Authored-By: Claude <noreply@anthropic.com>
2.0 KiB
SAFETY-119 - no "not keeping up" when the loop takes the wire back
Status: for review. Tests: test_safety119.py.
Cause. When another owner (the peak guard, a maintenance charge) has set
the wire and the loop wins again, cycle() re-seeds the integrator from that
owner's command, and compute() adds gain * error from a meter that does
not show that command yet. On the TEST-23 rig (SAFETY-118 I-2) the guard
stepped from -2000 W to +429 W with 5 s left. A cycle later the loop's ask
crossed the +2500 W rail and beat the guard's floor, so SAFETY-85 rule 1
counted it as the loop's own bound and raised goodwe_integrator_bound. The
battery gave what it was told, and the cap held.
Decision. After a hand-back, the loop's integrator bound is not counted
until the plant's settle has passed (SHORT_CYCLES cycles and
SHORT_SPAN_S, the window SAFETY-85 grades a battery on). After that it
counts as before. An over-rating (clamped, a bug) always counts. No command
changes, and no text was added or changed.
Kept. The loop in charge at its rail warns on the same cycle as before. A loop still at its rail after a hand-back warns once the window has passed: 22 s at a 2 s meter, 55 s at 5 s. Delay, not loss. The start and a restart after a stop are not hand-backs.
Re-pinned. test_safety84 (all six) and test_safety87 (n1_crossing,
n1_above, n1_charge_low): only OUTPUT_CLAMP log rows differ; commands and
claims are the same (test_safety119.py part 5).
Open. If another owner and the loop swapped the wire every few cycles, each swap restarts the window and the loop's bound would not be counted. A loop at its rail beats a floor or ceiling on its own side, so it keeps the wire; a swap needs a claim that keeps outranking it.
Not changed. The kick itself is control behaviour: for a few seconds at
a quarter's edge the loop asks up to its rail. In test_safety119.py part 1
that is more discharge than the guard asked at a quarter's end, and a few
seconds of up to 500 W more charge at the next quarter's start.