SAFETY-119 review: DECISIONS states the steady-meter limit
The quarter-edge numbers were measured with one cycle per reading at a steady interval. With the default 15 s cycle floor, a meter that is sometimes slower adds cycles on an old reading and the false alarm can come back (reviewer's runs, 11 seeds). Text only. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
This commit is contained in:
co-authored by
Claude Opus 5.5
parent
6fd0fa05f1
commit
96375ecbec
@@ -71,6 +71,13 @@ in the case above), so nothing more is claimed there. The cap held at 1 to
|
|||||||
meters the meter's lag puts quarters over it, the same with and without the
|
meters the meter's lag puts quarters over it, the same with and without the
|
||||||
fix (commands are identical).
|
fix (commands are identical).
|
||||||
|
|
||||||
|
**Limits.** These runs have one cycle per meter reading, at a steady
|
||||||
|
interval. A 20 or 30 s cycle needs `cycle_floor_s` raised; at the default
|
||||||
|
15 s, a slower meter adds cycles on an old reading. Measured that way (11
|
||||||
|
seeds): a 15 s meter that varies by up to 30 % false-alarmed on 5 seeds, a
|
||||||
|
30 s meter on 10 (0 to 4 in 2 h, 8 to 15 without the fix); a 20 s meter on
|
||||||
|
none. The case above still warned every quarter there.
|
||||||
|
|
||||||
**Kept.** The loop in charge at its rail warns on the same cycle as before.
|
**Kept.** The loop in charge at its rail warns on the same cycle as before.
|
||||||
The start and a restart after a stop are not hand-backs. The quarter-edge
|
The start and a restart after a stop are not hand-backs. The quarter-edge
|
||||||
kick of `test_safety119.py` part 1 stays hidden (see above).
|
kick of `test_safety119.py` part 1 stays hidden (see above).
|
||||||
|
|||||||