glenn schrooyenandClaude Opus 5 fc9bd89dca CFG-01: refuse to start on a configuration that cannot be honoured
main.py used to read the setpoint device's own +-5000 W rating, notice a
configured max_w above it, log one WARNING, and run anyway with
write_setpoint() quietly clamping. The operator's stated ceiling was never
the real ceiling and the only evidence had scrolled off the log. specs
§1.5 is explicit that such a config is refused at startup, not survived at
runtime.

validate_startup_config() runs in amain() before the broker, the web
server or any task exists, so a refusal cannot leave half a controller
running behind a UI. It refuses exactly three things, all sharing one
property - continuing makes a safety mechanism inoperative or makes a
stated limit untrue:

  1. max_w outside the setpoint device's own rating.
  2. No setpoint_entity: every write is a no-op, the device rating is
     never read, and the ESP32 heartbeat that holds off the layer-1
     failsafe never happens. It ran, looked healthy, and moved nothing.
  3. A meter_source that can never produce a reading. These were already
     caught, but they only DISABLED ingestion, which leaves grid None
     forever: permanent inputs-missing, 0 W, and a status page
     indistinguishable from a healthy meter nobody has fed yet.

Those last predicates move into p1.validate_meter_options(), which
build_source() also calls - one definition, two callers, not two
competing validators. ha_dsmr with half its entities and mqtt_p1 with a
blank topic gained the check the other two transports already had.

Deliberately not refused, because untidy is not unsafe: integrator_max_w
above max_w (the arbiter still bounds the wire to +-max_w, so the cost is
unwind latency - warned), a missing soc/batt entity (fail-safe and
already a red NOT READY banner), a setpoint entity that has not appeared
on the Core API yet (ESPHome is routinely late; re-checked in
run_control() once the real rating arrives), and a thin meter_poll_s
margin.

A refusal is legible as one: a banner saying in words that this is
configuration and nothing is broken, numbered problems, no traceback, and
exit 78 (EX_CONFIG).

Verified on the live add-on 2026-08-28, not by reading the code: a blank
setpoint_entity and a meter_poll_s equal to meter_max_age_s each stopped
the add-on with the banner and no stack trace.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-28 19:29:35 +02:00

191 lines
9.6 KiB
Python

"""Startup configuration validation - the gate before the control loop runs.
WHAT THIS IS FOR, in one sentence: some configurations are not "a bit off", they
are configurations under which the add-on's own safety machinery does not work,
and for those the correct behaviour is to refuse to start rather than to log a
line and carry on.
⚠️ THE FAILURE THIS REPLACES. `main.py` used to read the setpoint device's own
±5000 W rating, notice that a configured `max_w` of, say, 8000 W exceeded it,
write one WARNING to a log nobody reads, and then run anyway with
`write_setpoint()` quietly clamping. The operator's stated ceiling was simply not
the ceiling, and the only evidence was a line that had scrolled off. specs §1.5
is explicit that a configuration in which the system cannot honour what it was
told is refused at startup, not survived at runtime.
WHERE THE LINE IS DRAWN, and why it is not further out. A validator that refuses
on trivia gets switched off by the first person it inconveniences, so this one
refuses on exactly three things, all of which share one property: **continuing
makes a safety mechanism inoperative or makes a stated limit untrue.**
1. `max_w` outside the setpoint device's own rating.
The stated limit is untrue. arbiter.py's `supervised` SAFETY claim says the
output is bounded by ±max_w; it is not, it is bounded by the device, and the
two numbers disagree. Which one wins is a coin toss to anyone reading the
config.
2. No `setpoint_entity`.
This is a controller with no actuator, and nothing about it looks broken.
`write_setpoint()` returns immediately on a blank entity, so: no device
rating is ever read (the `device` SAFETY claim is never made at all), and
the ESP32 heartbeat - the thing that feeds LAYER 1 - never happens. The
add-on serves a UI, publishes MQTT, resolves claims, and moves nothing. It
is fail-safe by accident, not by design, and it is indistinguishable from
working.
3. A `meter_source` that can never produce a reading.
§5.1 makes P1 the only authoritative measurement and deliberately provides
no fallback, so a transport that cannot be built means `grid` is None
forever: permanent "inputs missing", 0 W, and a status page that reports a
meter with a climbing age exactly as it would for a healthy meter nobody has
sent anything to yet. The predicates live in `p1.validate_meter_options()`,
which is also what `build_source()` uses - one definition, two callers.
WHAT IS DELIBERATELY *NOT* REFUSED, because it is untidy rather than unsafe:
- `integrator_max_w` above `max_w`. DOCS.md is right that the only thing the
extra headroom buys is more wrong-direction power to unwind after
saturation - but the arbiter's `supervised` limit still binds the wire to
±max_w, so nothing out of range ever reaches the inverter. The cost is
latency, not amperage. Warned about, not refused.
- A missing `soc_entity` / `batt_entity`. `inputs_ok` goes False, the loop
commands 0 W, and `checks()` already renders a red NOT READY banner naming
the missing entity. Fail-safe AND already loud; a refusal adds nothing.
- A `setpoint_entity` that exists in the config but is not found on the Core
API at startup. This is the transient case - ESPHome is frequently not up
yet when the add-on boots - and refusing here would turn a device that
arrives thirty seconds late into a restart loop needing a human. It stays a
NOT READY banner.
- `meter_poll_s` above half `meter_max_age_s`. One missed poll costs a stale
reading and a 0 W cycle. Warned about in p1.py, not refused.
"""
import logging
from .p1 import validate_meter_options
_LOG = logging.getLogger("goodwe.config")
# ⚠️ The complete set of option keys through which this add-on can reach an
# actuator. specs §1.5 makes "any configuration in which two writers can reach
# one actuator" a non-goal, and the way that non-goal is ENFORCED here is by
# construction: there is exactly one such key, so a second writer is not
# expressible in the options schema at all. sim/inject.py's `two_writers`
# scenario asserts on this tuple - if a second write path is ever added, that
# scenario goes red and somebody has to decide how the two are arbitrated
# BEFORE the config that allows both can ship.
ACTUATOR_WRITE_KEYS = ("setpoint_entity",)
class ConfigRefused(Exception):
"""The configuration is wrong. Not "something broke" - see main.py's handler.
Carries the list of problems so the caller can render them; str() is the
first one, so an unhandled traceback still names something useful.
"""
def __init__(self, problems: list[str]):
self.problems = problems
super().__init__(problems[0] if problems else "configuration refused")
def validate_startup_config(opts: dict, dev_min=None, dev_max=None) -> list[str]:
"""Return the list of reasons this configuration must not be started.
Empty list means go. `dev_min`/`dev_max` are the setpoint device's own
reported range (`hass.limits()`), or None when the device could not be
reached - in which case the range checks are skipped rather than guessed at,
for the transient reason in this module's docstring.
Pure and side-effect free apart from two warnings, so it can be called from
a test or from sim/inject.py without a Home Assistant anywhere near it.
"""
problems: list[str] = []
# --- 1. an actuator to write to ------------------------------------------
writers = [k for k in ACTUATOR_WRITE_KEYS
if str(opts.get(k, "") or "").strip()]
if not writers:
problems.append(
"setpoint_entity is not set, so this add-on has no actuator: every "
"write is a no-op, the device's own rating is never read, and the "
"ESP32 heartbeat that holds off the layer-1 failsafe never happens. "
"It would run, look healthy, and move no energy at all. Set it to "
"the ESPHome number entity that carries the setpoint.")
# --- 2. the configured ceiling against the device's own rating -----------
max_w = _number(opts, "max_w", 2000.0)
if max_w is None:
problems.append(f"max_w {opts.get('max_w')!r} is not a number")
elif dev_max is not None and max_w > dev_max:
problems.append(
f"max_w is {max_w:.0f} W but {opts.get('setpoint_entity') or 'the setpoint device'} accepts at "
f"most {dev_max:.0f} W - THE DEVICE WINS, so the {max_w:.0f} W you "
f"configured would silently never happen. Lower max_w to "
f"{dev_max:.0f} W or less, or point setpoint_entity at a device that "
f"can take {max_w:.0f} W.")
elif dev_min is not None and -max_w < dev_min:
problems.append(
f"max_w is {max_w:.0f} W, so this controller may command "
f"{-max_w:.0f} W, but {opts.get('setpoint_entity') or 'the setpoint device'} accepts no less "
f"than {dev_min:.0f} W - THE DEVICE WINS on the charge side. Lower "
f"max_w to {abs(dev_min):.0f} W or less.")
# --- 3. a meter that can actually read -----------------------------------
# ⚠️ Not a second copy of these rules - p1.py owns them, because
# build_source() has to apply the identical predicates and a drifted copy
# would be worse than no check.
phases = _number(opts, "meter_phases", 1.0)
max_age_s = _number(opts, "meter_max_age_s", 30.0)
if phases is None or max_age_s is None:
problems.append("meter_phases and meter_max_age_s must both be numbers "
f"(got {opts.get('meter_phases')!r} / "
f"{opts.get('meter_max_age_s')!r})")
else:
problems.extend(validate_meter_options(opts, int(phases), max_age_s))
# --- warnings: real, but not worth refusing over -------------------------
integ = opts.get("integrator_max_w")
integ_w = None if not integ else _number(opts, "integrator_max_w", None)
if integ_w is not None and max_w is not None and integ_w > max_w:
_LOG.warning(
"integrator_max_w %.0f W is above max_w %.0f W. Not refused - the "
"arbiter still bounds the wire to +-max_w - but the only thing the "
"extra headroom buys is more wrong-direction power to unwind after "
"saturation. 0 (follow max_w) is the recommended value.",
integ_w, max_w)
return problems
def _number(opts: dict, key, default):
raw = opts.get(key, default)
if raw is None or raw == "":
return default
try:
return float(raw)
except (TypeError, ValueError):
return None
def refuse(problems: list[str]) -> None:
"""Log a refusal an operator can tell apart from a crash. Does not raise.
⚠️ THE POINT OF THE BANNER. "You configured this wrong" must not read like
"it broke". A Python traceback in an add-on log means the same thing to most
operators as a segfault - file a bug - whereas this block names the keys,
names the fix, and says in words that nothing is broken. main.py catches
ConfigRefused and exits 78 (sysexits EX_CONFIG), so no traceback is printed
at all and even the exit status distinguishes the two.
"""
_LOG.error("=" * 72)
_LOG.error("REFUSING TO START: the add-on configuration is not usable.")
_LOG.error("This is a CONFIGURATION problem, not a crash. Nothing is broken;")
_LOG.error("the add-on will start as soon as the settings below are fixed.")
_LOG.error("Fix them in Settings > Add-ons > GoodWe RS485 Controller >")
_LOG.error("Configuration, then start the add-on again.")
_LOG.error("-" * 72)
for i, problem in enumerate(problems, 1):
_LOG.error(" %d. %s", i, problem)
_LOG.error("=" * 72)