glenn schrooyenandClaude Opus 5 cc4e88490b SAFETY-02 review: a latch that a restart clears is not a latch
BLOCKER. `auto` was persisted and `sign_wd.tripped` was not, so reconstructing
the Controller against the same store - which is what a container restart does -
brought it back ARMED, into the same fault, unattended: tripped=False, banner
back to NOT READY, and it resumed commanding -1000 then -2000 W before
re-tripping 180 s later. "Restart the add-on" is the first thing an operator
looking at a FAILSAFE banner and a 0 W inverter will try, and under a supervisor
that restarts a crashed add-on it is a loop of three-minute wrong-direction
bursts. DOCS.md's "it does not clear itself" was false across a restart.

`sign_tripped` and `sign_reason` are Store keys now, beside the maintenance
state and for the reason store.py's own docstring gives. Written the moment the
trip happens - reason first, flag second, so a crash between the two can never
persist a latch with no explanation - restored in Controller.__init__, cleared
only by the operator's start. The regression is covered: reverting the restore
fails seven checks in test_watchdog.py.

Review follow-ups, no behaviour change:

- The arming gate is tested against the REAL arbiter. It is the decision the
  ticket turns on and it was asserted in three comment blocks and verified by
  nothing - every case passed `following` in as a literal. Twelve claim
  configurations now derive it from resolve(), including the redirect case
  `winner == "loop"` alone would have got wrong and the `lo` limit that raises
  magnitude without flipping sign.
- The MQTT `status: "failsafe"` value is tested. The check that claimed to cover
  it restated the line above it and never touched the payload.
- The worked example described a config that does not ship: at the defaults
  maintenance_charge_w 2500 against max_w 2000 is an arbiter contradiction and
  0 W, not a -2500 W charge. Rewritten at 1500 W. The contradiction is a real
  pre-existing bug - a default cheap-window maintenance charge silently never
  happens - filed separately and deliberately not fixed here.
- Forward hazard recorded at the gate: `winner == "loop"` disarms the watchdog
  under any higher-priority SET, and a peak-shaving strategy at P_PEAK IS
  grid-following in sign, so it would blind this for every peak event.
- disagrees() is public so the replay harness stops carrying its own copy of the
  predicate it grades.
- held_s takes the clock instead of reading one.
- The two limits are now each stated in both places rather than one each.
- The no-false-positive argument is tied to control.py's freeze permitting the
  command to cross zero; under the shrink-only encoding control.py records as
  rejected, this would false-trip on a load step.
- Measured figures corrected: 93.4 % / 4212 of 17280, per-cluster
  0.3/0.9/10.5/0.0, and the near-circularity of those figures is now stated
  rather than leaned on.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-28 22:33:15 +02:00

200 lines
7.1 KiB
YAML

name: GoodWe RS485 Controller
version: "0.5.1"
slug: goodwe_controller
description: >-
Drives a GoodWe ES/BP battery inverter over RS485 by emulating its smart
meter, holding net grid exchange at zero and running a monthly battery
maintenance cycle.
url: https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
arch:
- aarch64
- amd64
- armv7
init: false
startup: application
boot: auto
# Needed to read the meter and to write the ESPHome setpoint number.
homeassistant_api: true
hassio_api: true
# Own diagnostics/operations UI inside HA. This is what a field tech and a
# remote supporter both look at, so it is not optional.
ingress: true
ingress_port: 8099
panel_icon: mdi:battery-sync
panel_title: GoodWe
# Optional: publish status entities by MQTT discovery. `want` rather than
# `need` - the add-on runs fine with no broker, it just publishes nothing.
services:
- mqtt:want
options:
# --- sources (required) ---------------------------------------------------
meter_entity: sensor.p1_meter_active_power
meter_invert: false
soc_entity: ""
batt_entity: ""
batt_invert: false
setpoint_entity: ""
# --- P1 meter ingestion (specs §5.2 / §14 `meter:`) -------------------------
# `off` keeps the original single meter_entity path above, so an existing
# install is untouched until it opts in. ha_dsmr subscribes to the DSMR
# integration's entities over the HA WebSocket; mqtt_p1 reads the topic below;
# ha_signed reads ONE signed HA entity (+ import / - export), which is what a
# HomeWizard P1 publishes and what ha_dsmr cannot consume.
# homewizard_local skips Home Assistant entirely and polls the meter's own
# local API. ⚠️ It is the ONLY mode whose sensor.p1_sample_age_s measures when
# the meter REPORTED rather than when the value last CHANGED - HA emits
# nothing at all for a repeated reading - so it is the only mode a firmware
# watchdog may threshold. See DOCS.md.
meter_source: "off"
meter_phases: 1
meter_max_age_s: 30
meter_mqtt_topic: ""
# homewizard_local only. The meter's own address, `host` or `host:port`.
p1_host: ""
# homewizard_local only. Seconds between polls. Must be well under
# meter_max_age_s - the age is never fresher than this interval - and there is
# nothing to gain below the meter's own ~5.0 s update rate (NOTES.md:640).
meter_poll_s: 5
# The two UNSIGNED Belgian registers. The EMS derives net power from them
# (import - export); do NOT point these at a signed template sensor.
p1_import_entity: ""
p1_export_entity: ""
# Optional, in L1..L3 order. Required for the capacity-tariff peak on a
# three-phase connection; the list length must equal meter_phases.
p1_phase_import_entities: []
p1_phase_export_entities: []
# ha_signed only. ONE signed net-power sensor: positive = import from the
# grid, negative = export to it. Do NOT split it into two template sensors -
# the split is done in the add-on (p1.split_signed) precisely so the sign
# convention is tested rather than living in unreviewed YAML.
p1_net_entity: ""
# Optional, in L1..L3 order, each one signed the same way. Same role as
# p1_phase_import_entities: the capacity-tariff peak on a three-phase
# connection. The list length must equal meter_phases.
p1_phase_net_entities: []
# --- control ---------------------------------------------------------------
max_w: 2000
gain: 0.6
slew_w: 1000
deadband_w: 15
target_grid_w: -10
step_w: 10
saturation_w: 500
saturation_cycles: 3
integrator_max_w: 0
heartbeat_s: 10
stale_input_s: 15
cycle_floor_s: 15
auto_start: false
# --- SAFETY-02 sign-disagreement watchdog ----------------------------------
# Trips when the emitted setpoint and the P1 net figure point OPPOSITE ways,
# both over sign_disagree_w, continuously for sign_disagree_s. Action: 0 W and
# a failsafe that latches until an operator starts control again.
#
# Both defaults are measured, not chosen. On the captured healthy day
# (2026-08-23) the longest legitimate opposed run - a load step the loop has
# not caught up with - is 30 s, and sign agreement over the gated samples is
# 93.4 %. On the captured fault day (2026-08-20) the clusters run 0.0-10.5 %
# agreement with opposed runs up to 1752 s. 300 W / 180 s sits in the middle of
# a very wide gap: at 60 s the healthy day still trips nothing, at 300 s the
# fault day still trips 13 times. There is no reason to move either number
# without a capture that says so. They are options because the AC says
# thresholds are defaults rather than constants - not because they are knobs
# anyone is expected to turn.
#
# ⚠️ sign_disagree_w must stay BELOW max_w or the watchdog can never fire (the
# arbiter bounds the command to +-max_w). validate.py refuses that config.
sign_disagree_w: 300
sign_disagree_s: 180
# --- maintenance -----------------------------------------------------------
maintenance_enabled: false
maintenance_interval_days: 28
maintenance_start_hour: 10
maintenance_discharge_w: 2500
maintenance_charge_w: 2500
maintenance_soc_floor: 11
maintenance_soc_target: 99
maintenance_hold_min: 120
# --- tariff / capacity tariff (all optional) ------------------------------
peak_forecast_entity: ""
peak_cap_w: 3500
price_now_entity: ""
price_avg_entity: ""
# --- site ------------------------------------------------------------------
estop_fitted: false
log_level: info
schema:
meter_entity: str
meter_invert: bool
soc_entity: str
batt_entity: str
batt_invert: bool
setpoint_entity: str
meter_source: list(off|ha_dsmr|mqtt_p1|ha_signed|homewizard_local)
# ⚠️ 2 is accepted by this range but is not a real Belgian connection. A
# telegram whose phase count disagrees is rejected at ingest and logged, so a
# mis-set 2 shows up immediately as "0 telegrams accepted" rather than as a
# quietly wrong number.
meter_phases: int(1,3)
meter_max_age_s: int(5,300)
meter_poll_s: int(1,60)
meter_mqtt_topic: str?
p1_host: str?
p1_import_entity: str?
p1_export_entity: str?
p1_phase_import_entities:
- str
p1_phase_export_entities:
- str
p1_net_entity: str?
p1_phase_net_entities:
- str
max_w: int(100,5000)
gain: float(0.05,1.0)
slew_w: int(50,5000)
deadband_w: int(0,500)
target_grid_w: float(-200,200)
step_w: int(1,100)
saturation_w: int(100,2000)
saturation_cycles: int(1,10)
integrator_max_w: int(0,15000)
heartbeat_s: int(2,25)
stale_input_s: int(5,120)
cycle_floor_s: int(5,60)
auto_start: bool
# No "off" value, deliberately: this is a P0 safety check and the schema is
# not the place to make disarming it a supported configuration.
sign_disagree_w: int(50,5000)
sign_disagree_s: int(30,1800)
maintenance_enabled: bool
maintenance_interval_days: int(1,90)
maintenance_start_hour: int(0,23)
maintenance_discharge_w: int(500,5000)
maintenance_charge_w: int(500,5000)
maintenance_soc_floor: int(5,30)
maintenance_soc_target: int(50,100)
maintenance_hold_min: int(5,480)
peak_forecast_entity: str?
peak_cap_w: int(500,15000)
price_now_entity: str?
price_avg_entity: str?
estop_fitted: bool
log_level: list(trace|debug|info|warning|error)