glenn schrooyenandClaude Opus 5 e40eb0768d SAFETY-02: the P_PEAK assertion was pinning the test's copy of the gate
Review finding 2, and it is the same duplication `disagrees()` just removed, so
it gets the same fix rather than a follow-up card.

`following_from()` in test_watchdog.py was a TRANSCRIPTION of the gate in
main.py, carrying "keep the two in step" as an instruction - which is exactly the
arrangement that does not keep two things in step. Measured: editing the shipped
gate alone to `winner in ("loop", "peak")` left every suite green while the
watchdog went blind for the duration of every peak event. The row whose whole job
is to force whoever lands peak shaving to come and change an expectation did not
do that.

The expression is now `watchdog.loop_is_following()`, called by main.py and by
the test. One definition, two callers, same reasoning as `disagrees()`: the copy
that drifts is always the one in the harness doing the grading.

⚠️ AND EXTRACTING IT WAS NOT SUFFICIENT - the drift proof still came out green
after the extraction, which is why it was worth running rather than assuming. The
realistic P_PEAK row has peak shaving asking for MORE than the loop, so the
magnitude term rejects it whatever `winner` says and masks the term under test. A
second row with peak asking for LESS makes `winner` the only deciding term. With
that row, widening the shipped gate fails two checks; without it, none.

Also enforcing the write ordering that was documented and not asserted: swapping
the two `store.set` calls passed everything. A store that fails the second write
now proves the property the ordering exists for - a crash mid-trip leaves a
reason with no latch, never a latch with no explanation. Swapping them now turns
that check red.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-28 22:59:46 +02:00

32 KiB
Raw Blame History

Changelog

0.5.1

SAFETY-02's latch now survives an add-on restart, which is the difference between a latch and a pause. auto was persisted and sign_wd.tripped was not, so reconstructing the Controller against the same store — exactly what a container restart does — brought it back armed, into the same fault, with no operator involved: tripped=False, banner back to NOT READY, and it resumed commanding (measured: −1000 W, −2000 W) before re-tripping 180 s later. Under a Supervisor that restarts a crashed add-on that is a loop of three-minute wrong-direction bursts — and "restart the add-on" is the first thing an operator looking at a FAILSAFE banner and a 0 W inverter will try.

sign_tripped and sign_reason are now Store keys beside the maintenance state, written the moment the trip happens (reason first, flag second, so a crash between the two can never persist a latch with no explanation) and restored in Controller.__init__. Cleared only by the operator's start. DOCS.md said "it does not clear itself"; that was false across a restart and now is not.

Also in this release, all of it review follow-up rather than new behaviour:

  • The arming gate is tested against the real arbiter. It was the decision the whole ticket turns on and it was asserted in three comment blocks and verified by nothing — every case passed following in as a literal. test_watchdog.py now derives it from resolve() across twelve claim configurations, including the redirect case winner == "loop" alone would have got wrong and the lo limit that raises magnitude without flipping sign.

  • The MQTT status: "failsafe" value is tested. The check that claimed to cover it restated the assertion three lines above it and never touched the payload.

  • A forward hazard written down where it will be read, and made to bite. winner == "loop" disarms the watchdog under any higher-priority SET claim. Today only maintenance and the safety stops emit one and neither follows the meter; a peak-shaving strategy at P_PEAK does, and would blind the watchdog for every peak event.

    The gate is now watchdog.loop_is_following(), called by both main.py and the test, for the same reason disagrees() was extracted: the test held a transcription of the shipped expression, so editing the shipped gate alone to winner in ("loop", "peak") left every suite green while the watchdog went blind. Two copies, and the one that drifts is the one doing the grading.

    ⚠️ Extracting it was not sufficient on its own. The realistic P_PEAK row — peak shaving asking for more than the loop — still could not detect the widened gate, because the magnitude term rejects it regardless and masks the winner term. A second row with peak asking for less isolates winner as the only deciding term, and that is the one that turns red.

  • The worked example described a configuration that does not ship. At the defaults maintenance_charge_w (2500) exceeds max_w (2000), so that claim is an arbiter contradiction resolving to 0 W, not a −2500 W charge. The example is now written at 1500 W. (The contradiction is a real pre-existing bug — a default cheap-window maintenance charge silently never happens — filed separately, deliberately not fixed here.)

  • disagrees() is public, so sim/replay_sign.py stops carrying its own copy of the predicate it grades.

  • held_s takes the clock instead of reading one, restoring the pure-function property the module advertises.

  • The sign_reason-before-sign_tripped write ordering is enforced, not just documented. Swapping the two lines used to pass every check. A store that fails the second write now proves the property the ordering exists for: what survives a crash mid-trip is a reason with no latch, never a latch with no explanation.

  • Measured figures corrected throughout: 93.4 % / 4212 of 17280 (was 92.9 % / 4127 of 16349), per-cluster 0.3 / 0.9 / 10.5 / 0.0 %.

0.5.0

SAFETY-02 — the sign-disagreement watchdog. The add-on now watches whether the setpoint it is emitting and the grid figure it is regulating on point the same way. If they oppose each other, both over sign_disagree_w (300 W), for sign_disagree_s (180 s) continuously, it files a failsafe claim at P_SAFETY, commands 0 W, and latches there until an operator starts control again. New module app/watchdog.py; new options sign_disagree_w and sign_disagree_s.

This is the gap the existing failsafes leave open. The stale-input watchdog asks whether the meter is still talking, the saturation freeze asks whether the inverter can follow, the output clamp asks whether the number is too big — a loop can pass all three while charging the battery out of the grid, because the only thing wrong is the sign. On 2026-08-20 a commercial controller did exactly that four times in one day, for up to 77 minutes at a stretch, and reached a commanded −14 768 W against a ±5000 W inverter.

Validated against that day. sim/replay_sign.py in the infra repo drives this module over the committed RS485 captures of both 2026-08-20 (the four episodes) and 2026-08-23 (healthy): 18 trips on the fault day, every one inside a window NOTES.md §4.7 accounts for, and 0 on the healthy day. The four episodes do share one signature rather than merely resembling each other — sign agreement runs 0.3 / 0.9 / 10.5 / 0.0 % inside them against 93.4 % on the healthy day.

Three decisions worth knowing about:

  • It is disarmed whenever the grid-following loop is not what is driving. Sign agreement is a property of a loop that follows the meter. A maintenance grid charge opposes the meter by design — 2500 W of charge into a house drawing 500 W is +3000 W on the meter against a −2500 W command, for hours — and armed unconditionally this would trip on every maintenance cycle. The gate tests the emitted number, not the winning claim's name: a limit claim can let the loop "win" and still replace its value with one pointing the other way.
  • The trip latches. Commanding 0 W removes the command side of the comparison, so the disagreement always clears the moment the trip works. Un-latched, this would trip, clear, and hand the actuator back to the loop that was driving the wrong way, every three minutes forever.
  • sign_disagree_w at or above max_w is refused at startup (validator rule 5). The arbiter never lets a command exceed max_w, so such a threshold makes the watchdog incapable of firing while the status page still reports it armed. A disarmed guard that advertises itself as armed is the failure mode this project keeps refusing to ship.

What it does not catch, stated so nobody assumes otherwise: an inverter that acts opposite to what it was told moves the meter further the same way, so command and meter agree while everything runs away. That is the saturation freeze's job, which compares the command against the battery's actual power.

test_validate.py's "the smallest sane max_w still starts" case now names a reachable sign threshold, because a 1 W ceiling genuinely does disarm the 300 W default and is now correctly refused.

0.4.0

CFG-01. The add-on now refuses to start on a configuration it cannot honour, instead of logging a line and carrying on. validate_startup_config() runs in amain() before the broker, the web server or any task exists, so a refusal cannot leave half a controller running behind a UI.

It refuses only where continuing produces one of two outcomes: (a) a stated limit is untrue - the operator configured a bound and a lower layer silently enforces a different one - or (b) the add-on is inert and indistinguishable from healthy. (b) is not a special case of (a): with no setpoint_entity, layer 1 pinning the inverter at 0 W is the failsafe working. The system does not become unsafe, it becomes a convincing impression of a working controller.

Four things qualify:

  • max_w above (or below) the setpoint device's own rating. This is the one that changed behaviour. It used to warn the device wins and run anyway, with write_setpoint() silently clamping, so the configured ceiling was never the real one and the only evidence had scrolled off the log. The refusal names the configured value, the device's value, and which wins.
  • No setpoint_entity. A controller with no actuator: every write is a no-op, the device rating is never read, and the ESP32 heartbeat that holds off the layer-1 failsafe never happens. It ran, looked healthy, and moved nothing.
  • A meter_source that can never produce a reading - missing p1_host, missing p1_net_entity, a blank MQTT topic, a phase list disagreeing with meter_phases, an unknown source name, or a meter_poll_s at or past meter_max_age_s. These were already caught, but they only disabled ingestion, which leaves the grid reading None forever: permanent "inputs missing", 0 W, and a status page indistinguishable from a healthy meter nobody has sent anything to yet.
  • meter_max_age_s above the firmware's ingest veto. The schema accepts int(5,300); the ESP32's threshold is a compile-time max_age_s: "30" and it trips layer 1 at p1_age_s >= 30. Set 120 and the add-on treats a 119 s reading as fresh and keeps commanding, while the firmware has already vetoed and is holding the inverter at 0 W - healthy meter, running controller, nothing moving, and no line anywhere saying the number you set was overruled. Structurally the same fault as the max_w case. Only above the veto is refused: below it the add-on gives up first, which is fail-safe and visible on its own status page. Mirrored as validate.FIRMWARE_INGEST_VETO_S - it cannot be imported from a compile-time YAML substitution, so it carries a note about the one direction in which it can go stale.

max_w at or below zero is refused too. Schema-blocked on a real install, but validate_startup_config() is now also the simulation suite's entry point, and a non-positive max_w inverts the arbiter's supervised bounds into a contradiction that resolves to 0 W - i.e. it would read as a safety trip rather than as the typo it is.

The predicates for the meter group still live in p1.validate_meter_options(), which build_source() also calls - one definition, two callers, not two competing validators. Two transports gained a check they never had: ha_dsmr with only one of its two entities, and mqtt_p1 with a blank topic, both of which previously built a transport that could never read.

Deliberately not refused, because it is untidy rather than unsafe: integrator_max_w above max_w (the arbiter still bounds the wire to ±max_w, so the cost is unwind latency, not amperage - warned), a missing soc_entity / batt_entity (fail-safe, and already a red NOT READY banner naming it), a setpoint_entity that has not appeared on the Core API yet (ESPHome is routinely late; refusing would make a slow boot need a human - re-checked once the real rating arrives), and a thin-but-nonzero meter_poll_s margin.

A refusal is legible as a refusal: a banner that says in words that this is a configuration problem and nothing is broken, the numbered problems, no traceback, and exit status 78 (EX_CONFIG).

SAFETY-12. The control loop now evaluates on a clock as well as on a change. run_control() ran cycle() only when the meter value differed from the previous poll, so a meter that repeated a value ran no control cycles at all - while the heartbeat went on re-emitting the last command and the firmware went on putting it on the wire every 2 s. Layer 1 stayed fed, every indicator read healthy, and a command computed from an old reading kept being executed through whatever the load did next. Measured on the rig during TEL-05: 70 s at a literally constant 350.0 W with 14 arrivals and zero cycles.

It was worse than a latency limit: it was a safety claim that could not fire. stale_input_s and the inputs missing -> 0 W claim both live inside cycle(). Pre-fix, if the meter value happened to be constant, cycle() was never called again - so that claim had no way to run. Constant meter, SoC entity dying at t=4 s, same binary:

pre-fix    writes: [(0.0, 220.0), (0.0, 220.0), (10.1, 220.0)]
           final target: 220.0 W   reason: 'loop -> 220 W'
post-fix   writes: [(0.0, 220.0), (0.0, 220.0), (3.0, 430.0), (9.1, 0.0), (10.1, 0.0)]
           final target: 0.0 W     reason: 'safety -> 0 W'

The pre-fix controller held 220 W through the entire input outage with its status line still reading loop -> 220 W, and layer 1 does not cover that case on a meter_source: off install: no P1 age sensor is published, so the firmware has nothing to veto on, while the heartbeat keeps its watchdog fed. So the old behaviour was not "holds a stale command safely" - it was a failsafe that a repeating meter switched off. test_loop.py asserts both halves.

cycle_floor_s (default 15 s) is a deadline on the gap between cycles, not a second scheduler: every cycle resets it, whichever trigger fired. On a healthy meter it never elapses, so the cycle rate, the write sequence and therefore the per-cycle gain the tuning was measured against are unchanged - asserted in test_loop.py by driving the real loop twice on one binary (a huge cycle_floor_s reproduces the old behaviour exactly) and comparing the commanded values.

The reset is not the only thing holding that up, and the other argument is the sturdier one: the combined cycle rate is max(arrival rate, 1/floor), never the sum. At 1/15 s the floor is strictly slower than the ~1/5 s arrival rate, so even a hypothetical floor racing the arrivals could not exceed the nominal healthy rate. The re-tune is unreachable by construction. ⚠️ That holds only while cycle_floor_s stays above the meter's update interval, and the schema minimum is 5 s - which is exactly the reference meter's interval. Nothing enforces the relationship; validate.py is the obvious home for it and does not have it yet.

Observed over six real minutes on the same rig, one binary, meter held at a literally constant 350.0 W: before, 1 cycle (at startup) and then nothing, the command stuck at 220 W against a 350 W import for the rest of the window. After, 24 cycles, worst gap 15.14 s, and the ordinary PI ramp doing its job - 220, 430, 650, 860, 1080, 1300, 1510, 1730, 1940, 2000 W, one step per cycle, rail at t=136 s and flat after. Three minutes with the meter parked at the target instead: 1 cycle before, 12 after, and 19 writes either way - the same 19. Three minutes on a normally-changing meter: 36 cycles and 49 writes on both sides, the same values in the same order. The heartbeat write count never moves; the only writes the fix adds are the ten the loop was supposed to be making all along.

15 s is bracketed, not round.

Below it, ~11 s, and it arises more routinely than a dropped poll. HomeWizardLocalSource polls at 5.0 s against a meter that updates every 4.97 s (NOTES.md:640). Two near-equal periods beat, so roughly once every ~14 minutes the poller steps over an update entirely - a ~10 s gap between changed values on a perfectly healthy meter, plus up to 1 s for the 1 s tick to notice. A failed HTTP poll (retried on the next tick, no backoff) adds another 5 s. The floor sits above the beat-skip so it does not fire on that alone; what it takes to reach 15 s is a beat-skip and a failed poll coinciding.

Above it, 30 s. meter_max_age_s is 30 s, past which there is no reading to evaluate, and the firmware's ingest veto is also 30 s - so the loop is guaranteed to have re-decided at least twice inside any window in which layer 1 might otherwise be the only thing deciding. ⚠️ The default is therefore not independently justified at 15: if the firmware's veto ever moves, this moves with it. Noted beside the constant in main.py.

It is also exactly stale_input_s, this system's existing answer to "how long may we hold without re-deciding".

A floor cycle runs the full law on the same inputs, integrator included. In P1 mode the freshness question is already answered upstream and answered harder

  • past meter_max_age_s the reading is None, which is "inputs missing", which is a P_SAFETY 0 W claim - so a floor cycle there can only ever run on a reading this system already calls fresh. ⚠️ That is transport-conditional: with meter_source: off, read_inputs() takes the grid figure straight from hass.number() with no age gate at all, so a Home Assistant entity that has gone quiet reads as current on that path, with or without this change. Running the full law is still right there - the alternative is a degraded second law reasoning about an age nobody measured - but the floor does not make that path fresh. The integrator advances per cycle, not per second, so bounding the gap bounds the accumulation; integrator_max_w bounds it after that. A gentler second law for floor cycles would be a second set of dynamics nobody can test on this hardware.

⚠️ This is not a freeze detector, and TEL-05 established one cannot be built here: at the converged -10 W target a 1 Wh register needs ~6 minutes to move while the power figure legitimately repeats, so any threshold on unchanged_s false-trips at the exact operating point we run at. Nothing in this change decides whether a repeated reading is true. It stops "the number is the same" from meaning "do not think". The consequence, stated plainly: against a meter genuinely frozen at a wrong value the loop will now correct toward that wrong value rather than hold a stale command, bounded by max_w, the arbiter and the device rating. That was already what happened to a lying meter whose value merely jittered; bit-exact repetition was never a safety property.

DOCS.md's "Saturation is counted in cycles, not seconds" section documented the old behaviour as an accepted deviation. It is qualified, not deleted: the deviation survives (the window is still counted in cycles, and 3 x 15 s is still not the specification's 10 s) but it is now bounded at 45 s instead of open-ended, and the passage's second justification - "nothing accumulates while it is stalled" - is called out as having covered integrator windup and not staleness, which was the actual hazard. The same wrong argument in control.py's saturation comment is corrected too.

TEL-04. meter_source: ha_signed reads a single signed power entity, which is the shape a HomeWizard P1 publishes. Both transports 0.3.0 shipped require two unsigned registers and refuse negatives, so neither fits the meter installed here.

TEL-05. meter_source: homewizard_local polls the meter's own local API directly. This exists because of something the HA paths cannot do: Home Assistant fires no state change for a repeated reading and exposes no arrival signal at all, so sensor.p1_sample_age_s on those transports measures time since the value changed, not since the meter reported. Real captured data has gaps of 42 s and 97 s between changes on a perfectly healthy meter - long enough for a 30 s staleness threshold to command 0 W for no reason. Every HTTP response to the local API is a genuine arrival, so the age means what it says.

Verified on the rig against a literally constant 350.0 W for 70 s - the exact state where the HA path recorded zero samples in 45 s - with 14 arrivals and the age never exceeding the poll cadence.

Set p1_host to the meter's address and meter_poll_s (default 5 s, matching the meter's own ~5 s update). Still defaults to off; nothing changes for an install that does not opt in.

Freeze detection is separate and deliberately not thresholded: a meter answering 200 OK with a stale number is arriving, so no arrival stamp can flag it. The energy registers carry that as unchanged_s, surfaced on the status line for a human to read rather than alarmed on - at a converged -10 W a 1 Wh register needs about six minutes to move, so any threshold would false-trip at the target operating point.

Unreleased

TEL-05. A fourth meter_source, homewizard_local, which polls a HomeWizard P1's own local API (GET /api/v1/data) instead of watching a Home Assistant entity. Set p1_host to the meter's address; meter_poll_s (default 5 s, the meter's own update rate) sets the cadence.

✅ This is the first transport whose sensor.p1_sample_age_s measures when the meter reported, and therefore the first one a firmware watchdog may threshold. Every HTTP response is an arrival: the meter answered, now, with its current reading, and whether the number moved is not consulted. Home Assistant cannot express that at all — a repeated reading emits no state_changed, advances last_reported on neither serialiser, and state_reported is not subscribable ("Event filter is required"). On ha_signed that made a healthy meter under a flat load indistinguishable from a dead one, and our own capture of this house's meter goes 42.2 s and 97.0 s between changes — both past the default meter_max_age_s of 30, i.e. a false trip to 0 W on a meter that is fine. If you have a HomeWizard P1, move to this mode.

Everything TEL-01 established is reused, not re-implemented: ingest timestamping, meter_max_age_s, the clock-recomputed age, the plausibility bounds and the §20 unsigned-decode rejection, and the same split_signed sign convention ha_signed uses. A failed or timed-out poll submits nothing, so it is a missing reading — never 0 W — and it does not reset the age.

Verified on the ENV-01 rig against sim/hwsim.py, steady and with --fault freeze injected. Still defaults to off.

⚠️ An arrival stamp still cannot see a frozen meter, and no arrival detector can: a meter answering 200 OK forever with a stale number is arriving. The local API does expose what the HA path never had — the total_power_*_kwh registers stop advancing — and the transport tracks it as unchanged_s, but that is deliberately not folded into the age and not thresholded: this controller regulates grid power toward ~0 W, and at a converged −10 W the export register needs six minutes to move by its 1 Wh resolution while the power figure legitimately repeats. Thresholding it at 30 s would rebuild the false-trip limit cycle at the exact operating point we aim for. Freeze detection needs the low-power case solved first, separately. It is shown on the status page's P1 line instead — leaving it unthresholded only holds up if a human can read it, so now they can.

TEL-04. A third meter_source, ha_signed, reading one signed Home Assistant entity: positive = import, negative = export. That is the shape a HomeWizard P1 publishes (sensor.p1_meter_active_power), and it is the meter actually fitted here - which neither TEL-01 transport can read, because ha_dsmr needs two unsigned registers and refuses a negative one, i.e. every exporting telegram. Set p1_net_entity, and p1_phase_net_entities for the per-phase capacity-tariff figures on a three-phase connection.

Everything TEL-01 established is inherited rather than re-implemented - the new transport is a subclass of the ha_dsmr one overriding only which entities it wants and how they become a sample. So ingest timestamping, meter_max_age_s, sensor.p1_sample_age_s recomputed against the clock and republished once a second, the plausibility bounds, and unavailable / unknown treated as a missing reading and never 0 W all behave identically across the three sources.

Still defaults to off; an existing install is unaffected until it opts in.

⚠️ sensor.p1_sample_age_s is published on ha_signed, but must not yet be thresholded by the ESP32 stale-input watchdog. On the HA WebSocket paths the age is stamped from state_changed, so it measures time since the value changed, not since the meter reported - and Home Assistant exposes no arrival signal for a repeated reading (no state_changed, no last_reported movement on either serialiser, and state_reported is not subscribable over the WebSocket). Measured on the ENV-01 rig against the real HomeWizard integration. ha_dsmr mostly escapes it because a telegram moves several entities at once; ha_signed has one, so a healthy meter under a flat load is indistinguishable from a dead one. Our own capture has the house meter going 42.2 s and 97.0 s between changes. Raising meter_max_age_s does not fix that, it only chooses which error you get; the fix is an arrival stamp from the meter itself and is a separate ticket. Full detail in DOCS.md.

0.3.0

SAFETY-04. The control law's integrator is now an explicit accumulator, bounded independently of the output clamp instead of inheriting whatever headroom the clamp happened to leave. It also freezes while the inverter is not tracking, rather than continuing to wind up against a command nothing is acting on. integrator_max_w (default 0) governs the bound; 0 means "follow max_w", which is the existing behaviour.

Behaviour is unchanged at the defaults - a 4,928-case equivalence sweep against the previous control law confirms it decides identically at integrator_max_w: 0.

TEL-01. P1 meter ingestion, so a Belgian P1's two unsigned registers (consumption, injection) no longer need a hand-written signed template sensor: the subtraction moves into the add-on, done once and tested. Two transports, chosen with the new meter_source option: ha_dsmr subscribes to the DSMR integration over the HA WebSocket, mqtt_p1 reads a topic. Defaults to off, which keeps the existing meter_entity path untouched - nothing changes for an install that does not opt in.

Enabling it publishes sensor.p1_sample_age_s: seconds since the newest accepted telegram, recomputed against the clock and republished roughly once a second rather than only when a telegram lands. That is deliberate - Home Assistant only pushes a state on change, so a meter sitting at a genuinely constant reading would otherwise look identical to a dead one. Watching the age instead means a frozen meter shows a climbing age, not a flat line. The firmware watchdog subscribes to this exact entity id.

Known limits, both already in DOCS.md: on mqtt_p1, a bridge stuck republishing its last telegram still "arrives", so the age cannot detect that particular failure - prefer ha_dsmr where both are available. And a dead P1 meter takes 45 s to reach 0 W commanded (30 s for meter_max_age_s to call the reading stale, then 15 s of stale_input_s on top), which is meter_max_age_s and stale_input_s stacking, not either one alone.

0.2.1

target_grid_w (default -10 W): what the meter should rest at. The deadband holds any resting point inside it indefinitely, and the meter bills import and export on separate registers, so resting at +14 W import costs 0.34 kWh/day with the loop behaving perfectly. Biasing the target slightly negative moves that residue onto the export register. Configurable in the Configuration tab; see DOCS.md for the trade-off table.

Behaviour is unchanged at target_grid_w: 0.

0.2.0

Precedence between strategies is now a first-class object instead of an if/else ladder, ahead of there being more than three of them.

Every strategy returns a CLAIM each cycle - set ("I want X") or limit ("the result must stay within these bounds") - and arbiter.py resolves them by one rule:

  1. Highest-priority set wins; no claim at all means 0 W.
  2. Then every limit whose priority is >= that set's priority applies, most restrictive first.
  3. Contradictory limits are a BUG: command 0 W and say so.

Clause 2 is why "money outranks maintenance" is now a consequence of the priorities rather than a special case in a Jinja template: the maintenance charge-only limit binds the loop, but will not bind a higher-priority peak shaving claim when one exists.

  • Maintenance shaping (charge-only, cheap-window floor) moved out of the control law. control.py is once again only a controller that tracks the meter.
  • The loop computes from the ARBITER's last output, not its own last wish. If something outranked it, that is what the hardware actually did, and tracking anything else makes it jump when it regains control.
  • Every decision is explainable: "loop -> 0 W, limited by maintenance (charge-only)" now appears in the UI and the log, instead of a bare number.
  • Safety limits (device rating, supervised max_w) bind every strategy including the highest, and are still enforced a second time at the point of writing.

0.1.6

Findings from installing this on a live system, replacing a working YAML implementation. Every one of these was silent - the add-on looked healthy while being completely unable to do its job.

  • run.sh must use #!/usr/bin/with-contenv sh. The HA base images run s6-overlay, which starts services with a SANITISED environment. With a plain shebang, SUPERVISOR_TOKEN is simply absent and every Home Assistant call returns 401 - while homeassistant_api: true makes the permissions look correctly granted. Startup now logs the token length and probes the Core API, so the next person sees it in one line.
  • Bump version: for every change. Supervisor keys the built image by version, so editing source and rebuilding silently reuses the old image. Two fixes appeared not to work because of this.
  • Dependencies come from apk, not pip. Alpine is musl and there are no musl wheels for aiohttp; pip would compile it on the client's Pi.
  • paho-mqtt 1.x and 2.x are both supported. Alpine ships 1.x, which has no CallbackAPIVersion; that raised and took the whole add-on down with it.
  • MQTT can no longer take down control. Publisher construction is wrapped - observability must never stop the controller.
  • MQTT discovery is published from on_connect. paho drops QoS-0 publishes issued before the CONNACK, so announcing straight after connect() published nothing at all while logging "MQTT connected".
  • Repeated failures log at most once a minute. The control loop retries every second; unthrottled warnings rolled the log buffer and destroyed the startup diagnostics needed to debug the 401 above.
  • auto_start works. The store's defaults supplied auto: False, so the fallback to the option could never fire.

Known issue: after deleting the MQTT entities from the registry during development, Home Assistant would not re-adopt them from retained discovery - not even after clearing the retained topics and reconnecting. The add-on publishes correct discovery and live state (verified on the broker); this is an HA-side adoption problem and affects status entities only, never control.

0.1.0

First packaged release. Ports the control loop and the monthly maintenance cycle from the reference Home Assistant implementation into an add-on.

  • Grid-following control: gain/slew/clamp/deadband with anti-windup, all tuned against measured hardware behaviour (see FIELD-GUIDE.md §14).
  • Saturation freeze with the duration term — three consecutive diverging cycles, not one. The instantaneous test fires on every large correction, because the plant itself needs 3-6 s to settle.
  • Monthly maintenance cycle as an ownership state machine: drain / charge / hold, with exactly one writer of the setpoint at any moment.
  • Capacity-tariff awareness: the maintenance charge is capped by quarter-hour peak headroom, and peak shaving outranks the maintenance schedule.
  • Failsafe behaviour: commands 0 W on missing inputs, on stop, and on shutdown. Never replays a stale setpoint - the reference implementation did, and the hardware watchdog cannot catch that.
  • Ingress UI with a commissioning checklist that names problems in words.
  • Optional MQTT discovery for status entities.

Known limits:

  • Home Assistant OS / Supervised only (add-ons cannot run on Container/Core).
  • The inverter protocol is reverse-engineered; no vendor contract.
  • Without the optional RS485 e-stop, nothing covers the host machine dying.