DEV-02: per-instance inverter objects, so nothing is graded against a sibling
Every piece of per-device state in the Controller was a scalar, and several of
them are safety inputs. app/inverter.py introduces an `Inverter` that owns its
entities, its rating, its device range, its SignWatchdog, its last_write and
its last_beat, under store keys namespaced by unit name. The Controller holds a
list of them and keeps only what is genuinely site-level: the P1 reading, the
site integrator, and the tariff quarter.

WHAT THE SCALARS WERE SILENTLY ASSERTING

  dev_min/dev_max   one pair, read from one setpoint_entity. A second
                    inverter's rating was NEVER READ AT ALL, so its clamp, its
                    freeze rail and the peak guard's achievable_w were the
                    first one's numbers.
  soc               one reading into the maintenance FSM, SAFETY-24's pack
                    floor and arbitrage's bounds. An average lets the emptier
                    pack be driven below its own floor.
  sign_wd           ONE SignWatchdog, whose own docstring says "one instance
                    per actuator", latched under FLAT store keys - so a trip
                    caused by B latched A across restarts and one operator
                    press cleared both.
  last_beat         one deadline and one serialised hass.call(), so a hung
                    write to A ate B's 30 s layer-1 budget.

actual_w BECAME SITE LEVEL WHILE THE READINGS BECAME PER-INSTANCE, and those
are opposite directions on purpose. compute()'s anti-windup test is
`abs(prev_w - actual_w) > saturation_w` with prev_w the SITE target, so feeding
it one inverter's power compares a site number against a unit number, trips the
saturation freeze permanently and leaves a standing grid error. Measured on
admin/goodwe's two-master rig (tools/alloc_sim.py --splits, 2 kW load, 40
cycles), worst |delta| between splits at the meter:

    gain    one unit's power      the site sum
    0.2           510 W                0 W
    0.4           250 W                0 W
    0.6            50 W                0 W

That was ALLOC-01's disclosed finding; test_alloc.py part 8 kept its stimulus
and now grades the other row.

THE STORE MIGRATION IS GRADED, NOT MERELY PERFORMED. sign_tripped/sign_reason
move to unit/<name>/... once, verified by READING BACK what was written, and
the version marker is set only when nothing that carried state was lost. The
flat keys stay in the file so a rollback still finds its latch. And __init__
compares the pre-migration flat latch against what unit A actually came up
with: if the latch did not survive it is RE-ARMED from the legacy value and
shouted about. A latch that silently fails to migrate is a disarmed safety
guard on an install whose state file says it is protected - which is strictly
worse than never persisting it, because now there is evidence saying it is
fine. test_inverter.py part 2 breaks the migration and watches the guard fire.

HEARTBEATS ARE INDEPENDENT AND THE BUDGET IS DERIVED. Each inverter owns its
deadline, the refreshes go out concurrently, and each write is bounded by
WRITE_BUDGET_S = 4 s. The inequality is graded rather than asserted: 4 +
heartbeat_s's schema maximum of 25 < 30, validate.FIRMWARE_INGEST_VETO_S.
Verified by injecting a transport that accepts and never answers.

live_units() ANSWERS HONESTLY. A unit whose every write has been rejected for a
whole layer-1 window is not commandable; the allocator drops it, the survivors
carry its share, the action log names it, and the dropped unit is commanded
0 W rather than left standing on its last share. A roster entry with NO
setpoint_entity is deliberately not handled there - that is a configuration
that cannot be delivered, and it reaches main.py's refusal branch, which is how
that branch keeps a live trigger after this card removed its old one.

AT N=1 NOTHING MOVES. The removed scalars survive as read/write properties of
the sole inverter, so every existing replay runs unmodified - and they REFUSE
at N>=2 rather than answering for the first inverter, which is the tripwire on
a consumer that was never made per-instance.

EVIDENCE. 19 files green. test_inverter.py is new (82 checks). Eighteen
mutations were applied to the shipped modules on a purged tree via
tools/mutation_run.sh and each was observed RED. Two of them SURVIVED first
time and the checks were changed rather than the table: the serialised dispatch
and the shared last_beat both passed while part 6 gathered its own writes and
computed its own `due` list. send_heartbeats() was extracted from run_control()
so the shipped dispatch is reachable by a check at all.

INVERTER B STILL DOES NOT EXIST. build_roster() returns exactly one inverter
from the flat options and is the one function CFG-04 changes; every two-unit
figure here is architecture, and the second rating in the checks is marked a
hypothesis.

Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-02 14:50:43 +02:00

535 lines
24 KiB
Python

"""Runnable check for the sign-disagreement watchdog. `python3 test_watchdog.py`
Every case here is either a fault this must catch or a piece of NORMAL behaviour
it must not mistake for one. The second list is the longer one on purpose: an
alarm that fires on ordinary operation is worse than no alarm, because the next
person switches it off.
The headline validation is not here - it is `sim/replay_sign.py` in the infra
repo, which drives this module over the two captured bus days. This file is the
table-driven half: boundaries, timers, the latch, and the arming gate.
⚠️ MUTATING THE MODULE THIS FILE GRADES? PURGE `__pycache__` FIRST - or run
`tools/mutation_run.sh`, which does. `python3 -B` alone does NOT save you: it
stops bytecode being WRITTEN, not a stale one being READ, and a size-preserving
edit reverted inside one second is invisible to CPython's staleness test. That
is TEST-15, and it has already turned one live mutation into a false survivor.
Read MUTATION.md before you report a survivor.
"""
import sys
from datetime import datetime, timedelta, timezone
from app.watchdog import (
SignWatchdog, SignWatchdogConfig, loop_is_following,
)
fails = []
T0 = datetime(2026, 8, 20, 15, 0, 0, tzinfo=timezone.utc)
def check(name, cond):
print(f" {'ok ' if cond else 'FAIL'} {name}")
if not cond:
fails.append(name)
def drive(samples, cfg=None, following=True):
"""Feed (offset_s, commanded_w, grid_w) tuples. Returns (wd, trip_offset)."""
wd = SignWatchdog(cfg)
trip_at = None
for item in samples:
offset, cmd, grid = item[0], item[1], item[2]
f = item[3] if len(item) > 3 else following
if wd.evaluate(cmd, grid, f, T0 + timedelta(seconds=offset)) and trip_at is None:
trip_at = offset
return wd, trip_at
def opposed(duration_s, step=5, cmd=-1000, grid=1500, following=True, start=0):
return [(start + t, cmd, grid, following)
for t in range(0, int(duration_s) + 1, step)]
print("the fault it exists to catch")
wd, at = drive(opposed(300))
check("charging into an importing house trips", wd.tripped)
check("and trips at 180 s, not before", at == 180)
check("the reason names both signals", "-1000" in wd.reason and "+1500" in wd.reason)
print(f" e.g. {wd.reason!r}")
wd, at = drive(opposed(300, cmd=2000, grid=-2000))
check("discharging into an exporting house trips too", wd.tripped and at == 180)
print()
print("the boundaries")
wd, _ = drive(opposed(600, cmd=-300, grid=1500))
check("300 W exactly does NOT qualify (strictly greater)", not wd.tripped)
wd, _ = drive(opposed(600, cmd=-301, grid=1500))
check("301 W does", wd.tripped)
wd, _ = drive(opposed(600, cmd=-1000, grid=300))
check("a 300 W meter does not qualify either", not wd.tripped)
wd, _ = drive(opposed(175))
check("175 s of disagreement does not trip", not wd.tripped)
wd, _ = drive(opposed(180))
check("180 s does (>= hold_s)", wd.tripped)
print()
print("continuity - the rule that produced zero false positives on real data")
broken = opposed(175) + [(180, -1000, -1500)] + opposed(175, start=185)
wd, _ = drive(broken)
check("179 s, one agreeing sample, then 175 s more: no trip", not wd.tripped)
check("and the window really was reset", wd.disagree_since is not None)
long_enough = broken + opposed(200, start=365)
wd, _ = drive(long_enough)
check("but a full 180 s after the reset does trip", wd.tripped)
print()
print("things that are NOT faults")
# The load-step transient. Measured on the healthy capture: longest 30 s.
wd, _ = drive(opposed(30) + [(35 + t, 800, 900) for t in range(0, 300, 5)])
check("a 30 s load-step crossover does not trip", not wd.tripped)
# SoC 10 %, Standby, declining a 1350 W discharge. The battery does nothing, so
# the meter stays where it was and the command agrees with it.
wd, _ = drive([(t, 1350, 1350) for t in range(0, 900, 5)])
check("a battery refusing a discharge command cannot trip it", not wd.tripped)
# A frozen meter drives command and reading into agreement, not disagreement.
wd, _ = drive([(t, 800, 800) for t in range(0, 900, 5)])
check("a frozen meter cannot trip it", not wd.tripped)
# Maintenance grid charge: 2500 W of charge against an importing house, for
# hours. Opposed, both huge - and entirely correct.
wd, _ = drive(opposed(7200, cmd=-2500, grid=3000, following=False))
check("two hours of maintenance grid charge does not trip", not wd.tripped)
check("and the timer never even started", wd.disagree_since is None)
wd, _ = drive([(t, -1000, None) for t in range(0, 900, 5)])
check("a missing meter reading does not trip", not wd.tripped)
wd, _ = drive(opposed(175) + [(180, -1000, None)] + opposed(600, start=185))
check("a missing reading mid-window RESETS it rather than accumulating",
wd.tripped and wd.disagree_since is not None)
wd, at = drive(opposed(175) + [(180, -1000, None)] + opposed(600, start=185))
check("...so the trip lands 180 s after the gap, not after 180 s total",
at == 365)
wd, _ = drive([(t, 0.0, 3000) for t in range(0, 900, 5)])
check("a 0 W command is not a wrong-direction command", not wd.tripped)
print()
print("the latch")
wd, _ = drive(opposed(200))
check("tripped after the fault", wd.tripped)
# The trip commands 0 W, which removes the command side of the comparison.
for t in range(200, 900, 5):
wd.evaluate(0.0, 3000, True, T0 + timedelta(seconds=t))
check("stays tripped once the command is zeroed", wd.tripped)
for t in range(900, 1500, 5):
wd.evaluate(1000, 1000, True, T0 + timedelta(seconds=t))
check("stays tripped even once everything looks healthy again", wd.tripped)
wd.reset()
check("reset() is the only way out", not wd.tripped and wd.disagree_since is None)
check("and the reason is cleared with it", wd.reason == "")
print()
print("the thresholds are configuration, not constants")
cfg = SignWatchdogConfig(min_w=800.0, hold_s=60.0)
wd, at = drive(opposed(300, cmd=-1000, grid=1500), cfg=cfg)
check("a 60 s hold trips at 60 s", wd.tripped and at == 60)
wd, _ = drive(opposed(600, cmd=-700, grid=1500), cfg=cfg)
check("an 800 W gate ignores a 700 W command", not wd.tripped)
print()
print("the configuration that would disarm it is refused")
from app.validate import validate_startup_config # noqa: E402
base = {"setpoint_entity": "number.sp", "meter_source": "off",
"meter_phases": 1, "meter_max_age_s": 30}
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 300},
-5000, 5000)
check("300 W under a 2000 W ceiling is accepted", p == [])
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 2000},
-5000, 5000)
check("a threshold AT max_w is refused", len(p) == 1 and "never fire" in p[0])
# ⚠️ maintenance_charge_w is named here only to keep this case about the SIGN
# rule. MAINT-04 added a second rule against the same ceiling, and a 500 W
# max_w is also below the 2000 W shipped maintenance charge - so without this
# the dict is refused twice, for two correct but different reasons, and the
# `len(p) == 1` below would be measuring the interaction rather than this rule.
p = validate_startup_config({**base, "max_w": 500, "sign_disagree_w": 3000,
"maintenance_charge_w": 500}, -5000, 5000)
check("a threshold above max_w is refused", len(p) == 1 and "never fire" in p[0])
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 1999},
-5000, 5000)
check("one watt under the ceiling is reachable, so accepted", p == [])
print()
print("the arming gate, derived from the REAL arbiter")
# ⚠️ THIS IS THE DECISION THE WHOLE TICKET TURNS ON, and until now it was
# asserted in three comment blocks and verified by nothing: every other case in
# this file passes `following` in as a literal. What has to hold is that the
# expression in main.py - loop won AND the emitted value points the way the loop
# asked AND is no larger - is never True for a resolution the loop did not
# actually get. So run real claims through the real resolve() and derive it.
from app.arbiter import ( # noqa: E402
P_LOOP, P_MAINT_SHAPE, P_MAINTENANCE, P_PEAK, P_SAFETY, Claim, resolve,
)
def following_from(claims, asked):
"""THE SHIPPED gate, not a copy of it.
⚠️ This used to transcribe main.py's expression with a comment saying
"keep the two in step", which is exactly the arrangement that does not keep
two things in step. Measured: editing the shipped gate alone to
`winner in ("loop", "peak")` left this suite - including the P_PEAK row below,
whose entire job is to catch that edit - completely green, while the watchdog
went blind for the duration of every peak event. Import it or the P_PEAK
assertion is decoration.
"""
r = resolve(claims)
return r, loop_is_following(r, asked)
MAXW = Claim.limit("supervised", P_SAFETY, -2000, 2000, "max_w")
DEV = Claim.limit("device", P_SAFETY, -5000, 5000, "rating")
# name, claims, what the loop asked, expected `following`
TABLE = [
("the loop alone, unopposed",
[Claim.set("loop", P_LOOP, 900)], 900, True),
("the loop bound by max_w - reduced, not redirected",
[Claim.set("loop", P_LOOP, 4000), MAXW], 4000, True),
("charging, bound by max_w on the other side",
[Claim.set("loop", P_LOOP, -4000), MAXW], -4000, True),
("maintenance owns the setpoint outright",
[Claim.set("loop", P_LOOP, 900),
Claim.set("maintenance", P_MAINTENANCE, -2500, "charge"), MAXW], 900, False),
("maintenance charge-only clamps the loop to 0 W",
[Claim.set("loop", P_LOOP, 900),
Claim.limit("maintenance", P_MAINT_SHAPE, hi=0.0, reason="charge-only"),
MAXW], 900, False),
# ⚠️ THE CASE `winner == \"loop\"` ALONE WOULD HAVE GOT WRONG. 1500 W, not
# 2500 W: at max_w 2000 a -2500 hi against a -2000 lo is an arbiter
# contradiction, not a charge. That pair was the SHIPPED default until
# MAINT-04 refused it and CFG-03 gave the default one source of truth; it is
# kept below as a case rather than as a configuration.
("cheap-window charge REDIRECTS the loop while it still 'wins'",
[Claim.set("loop", P_LOOP, 500),
Claim.limit("maintenance", P_MAINT_SHAPE, hi=-1500, reason="cheap-window"),
MAXW], 500, False),
("...and the contradiction when charge_w exceeds max_w is not following either",
[Claim.set("loop", P_LOOP, 500),
Claim.limit("maintenance", P_MAINT_SHAPE, hi=-2500, reason="cheap-window"),
MAXW], 500, False),
("a lo limit RAISES the magnitude without flipping the sign",
[Claim.set("loop", P_LOOP, 200),
Claim.limit("floor", P_SAFETY, lo=800), MAXW], 200, False),
("a safety stop wins outright",
[Claim.set("loop", P_LOOP, 900),
Claim.set("safety", P_SAFETY, 0.0, "stopped"), MAXW], 900, False),
("no claims at all - the arbiter's own failsafe",
[MAXW, DEV], None, False),
("the loop asked for zero",
[Claim.set("loop", P_LOOP, 0.0), MAXW], 0.0, False),
# The forward hazard, asserted as it stands TODAY rather than as it should
# be. When peak shaving lands, these expectations are what have to change.
("peak shaving at P_PEAK disarms the gate (loop_is_following's forward hazard)",
[Claim.set("loop", P_LOOP, 900),
Claim.set("peak", P_PEAK, 1800, "shaving"), MAXW], 900, False),
# ⚠️ AND THE ROW ABOVE CANNOT DETECT A WIDENED GATE ON ITS OWN, which was
# found by trying it: with the shipped gate edited to
# `winner in ("loop", "peak")` that case STILL comes out False, because peak
# shaving asked for MORE than the loop and the magnitude term rejects it
# anyway. The winner term is masked. This row isolates it - a peak claim
# smaller than the loop's ask and pointing the same way, so `winner` is the
# only term that can decide - and it is what actually turns red if the gate
# is widened without anyone revisiting the hazard.
("...and with peak BELOW the loop's ask, only the winner term separates them",
[Claim.set("loop", P_LOOP, 1800),
Claim.set("peak", P_PEAK, 900, "shaving"), MAXW], 1800, False),
]
for name, claims, asked, expect in TABLE:
r, got = following_from(claims, asked)
check(f"{name} -> following={expect}", got is expect)
if got is not expect:
print(f" resolution was {r.explain()!r}")
# And the gate is never True when the loop did not win, whatever else is going on.
check("no configuration above arms the gate without the loop winning",
all(not following_from(c, a)[1]
for _, c, a, _ in TABLE if following_from(c, a)[0].winner != "loop"))
print()
print("end to end: the trip is COMMAND ZERO, not alarm-only")
# ⚠️ THE FAULT INJECTED HERE IS A NEGATIVE GAIN, and that is not a contrivance -
# it is the minimal faithful model of what this watchdog is for. The check
# compares the loop's OUTPUT DIRECTION against the INPUT STATE it was regulating,
# so what it detects is a loop whose two ends have become decoupled in sign: a
# gain, a claim or a strategy with its polarity inverted, or an integrator so far
# wound up that unwinding takes minutes. (Illusmart's was the last one: it
# reached -14 768 W against a +-5000 W rail while writing once every 20-60 s, and
# that arithmetic alone is 5-15 minutes of wrong-direction command.)
#
# `gain` is float(0.05,1.0) in the schema, so this is not a reachable
# configuration - it is a stand-in for a code regression, which is the case a
# unit test can actually hold the line on.
import asyncio # noqa: E402
from app.main import Controller # noqa: E402
# ⚠️ DEV-02. THE KEY SPELLING IS IMPORTED, NEVER TRANSCRIBED. `sign_tripped` and
# `sign_reason` are now NAMESPACED PER INVERTER - flat, a trip caused by B
# latched A across every restart and one operator press cleared both. A check
# that spelled `"unit/inverter-a/sign_tripped"` by hand here would go on passing
# against a main.py that had started writing somewhere else, which is this
# repository's own named failure mode: the copy that drifts is always the
# grading one. `unit_key()` is the one definition and `Inverter.key()` calls it.
from app.inverter import UNIT_A # noqa: E402
from app.store import unit_key # noqa: E402
TRIPPED_KEY = unit_key(UNIT_A, "sign_tripped")
REASON_KEY = unit_key(UNIT_A, "sign_reason")
class _Hass:
def __init__(self):
self.writes = []
self.calls = []
# ⚠️ ADDED FOR SAFETY-03, AND THE REASON IS WORTH READING. The e2e below
# runs a DELIBERATELY INVERTED loop (gain -0.6) into a steady 2000 W import,
# which is a loop that winds straight into the rail - so the output-clamp
# alarm fires here, and the stub not having `call` is how that was
# discovered. This scenario is now a second, independent witness that the
# clamp alarm sees a real winding loop; test_clamp.py asserts it explicitly.
async def call(self, domain, service, data):
self.calls.append((domain, service, data))
async def limits(self, entity):
return (-5000.0, 5000.0, 1.0)
async def number(self, entity, invert=False):
# A house importing 2000 W, steadily, whatever the battery does.
return {"sensor.grid": 2000.0, "sensor.soc": 50.0,
"sensor.batt": 0.0}.get(entity)
async def set_number(self, entity, value):
self.writes.append(float(value))
return True
class _S:
data = {}
def set(self, *a):
pass
def get_time(self, *a):
return None
class _P:
enabled = False
def publish(self, *a, **k):
pass
def close(self):
pass
async def _e2e():
hass = _Hass()
opts = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 2000, "gain": -0.6,
"sign_disagree_w": 300, "sign_disagree_s": 1, "auto_start": True}
c = Controller(opts, hass, _S(), _P(), stop=asyncio.Event())
c.auto = True
c.dev_min, c.dev_max = -5000.0, 5000.0
seen_wrong_way = False
for _ in range(12):
await c.read_inputs()
await c.cycle()
if c.target < -300 and not c.sign_wd.tripped:
seen_wrong_way = True
await asyncio.sleep(0.25)
return c, hass, seen_wrong_way
ctrl, hass, wrong_way = asyncio.run(_e2e())
check("the broken loop really did command charge into an import first", wrong_way)
check("the watchdog tripped", ctrl.sign_wd.tripped)
check("the commanded value is 0 W", ctrl.target == 0.0)
check("0 W actually reached the device", 0.0 in hass.writes)
check("and it got there through the failsafe claim, not by accident",
"failsafe" in ctrl.reason)
print(f" status line: {ctrl.reason!r}")
check("the status page says so in words",
any("SIGN-DISAGREEMENT FAILSAFE" in c["text"] for c in ctrl.checks()))
check("the banner leads with it",
"FAILSAFE" in ctrl.status_payload()["banner"])
check("it stays at 0 W on later cycles too",
hass.writes[-1] == 0.0 and hass.writes.count(0.0) >= 1)
# ⚠️ THIS USED TO BE `check("MQTT reports the failsafe state", ctrl.sign_wd.tripped)`
# which restates the assertion three lines above and never touches the payload.
# The `status: "failsafe"` value was shipped untested. Capture what publish()
# actually hands the broker.
published = {}
ctrl.mqtt = type("P", (), {"enabled": True,
"publish": lambda _s, v: published.update(v),
"close": lambda _s: None})()
ctrl.publish()
check("MQTT's controller-status sensor reports 'failsafe'",
published.get("status") == "failsafe")
ctrl.sign_wd.reset()
ctrl.publish()
check("...and goes back to 'running' once cleared",
published.get("status") == "running")
print()
print("the latch survives a restart - it is the only thing between a tripped")
print("controller and the first thing an operator will try")
# ⚠️ THE BLOCKER THIS FILE MISSED FIRST TIME ROUND. `auto` is persisted and
# `tripped` was not, so reconstructing a Controller against the same Store -
# which is exactly what a container restart does - came back armed, into the
# fault, with no operator involved: tripped=False, banner NOT READY, and it
# resumed commanding -1000 then -2000 W before re-tripping 180 s later.
class _MemStore:
"""A Store that keeps its dict across "restarts", like the real file does."""
def __init__(self):
self.data = {"phase": "idle", "sign_tripped": False, "sign_reason": ""}
def set(self, k, v):
self.data[k] = v
def get_time(self, *a):
return None
async def _restart():
shared = _MemStore()
hass1 = _Hass()
opts = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 2000, "gain": -0.6,
"sign_disagree_w": 300, "sign_disagree_s": 1, "auto_start": True}
a = Controller(opts, hass1, shared, _P(), stop=asyncio.Event())
a.auto = True
a.dev_min, a.dev_max = -5000.0, 5000.0
for _ in range(12):
await a.read_inputs()
await a.cycle()
await asyncio.sleep(0.25)
# The restart. Same options, same store, brand new Controller and Hass.
hass2 = _Hass()
b = Controller(opts, hass2, shared, _P(), stop=asyncio.Event())
b.auto = True
b.dev_min, b.dev_max = -5000.0, 5000.0
for _ in range(6):
await b.read_inputs()
await b.cycle()
await asyncio.sleep(0.05)
return a, b, shared, hass2
pre, post, store, hass2 = asyncio.run(_restart())
check("it tripped before the restart", pre.sign_wd.tripped)
check("the trip reached the store, UNDER THE TRIPPED INVERTER'S OWN KEY",
store.data[TRIPPED_KEY] is True)
check("...with the reason beside it, so the operator is told why",
"SIGN_DISAGREEMENT" in store.data[REASON_KEY])
check("⚠️ ...AND THE FLAT PRE-DEV-02 KEY IS NOT THE ONE THAT MOVED. It was "
"written by the migration at construction, with the value the store then "
"held (untripped), and nothing has written it since. A controller that "
"went on writing the flat key would latch every OTHER inverter on this "
"site as well - which is the defect, and it is only visible as the "
"ABSENCE of a second write here",
store.data.get("sign_tripped") is False)
check("the new Controller comes back TRIPPED", post.sign_wd.tripped)
check("...and says why, restored rather than re-detected",
"SIGN_DISAGREEMENT" in post.sign_wd.reason)
check("...commands 0 W from its very first cycle", post.target == 0.0)
check("...and never commanded anything else after the restart",
hass2.writes != [] and set(hass2.writes) == {0.0})
check("the banner still leads with the failsafe",
"FAILSAFE" in post.status_payload()["banner"])
# ⚠️ TWO PRESSES, and the first one must NOT clear it. `auto` is True while
# tripped, so the first press stops control; only the transition back to True
# clears. That is the documented behaviour and it is worth an assertion, because
# a one-press clear would be reachable by an operator who never read the banner.
asyncio.run(post.handle_action("auto_toggle")) # -> stopped
check("pressing stop does not clear the failsafe",
post.sign_wd.tripped and store.data[TRIPPED_KEY] is True)
asyncio.run(post.handle_action("auto_toggle")) # -> started
check("pressing start DOES clear it, and clears the store with it",
not post.sign_wd.tripped and store.data[TRIPPED_KEY] is False
and store.data[REASON_KEY] == "")
# One more restart from the cleared store, to prove the clear persisted too.
fresh = Controller({"setpoint_entity": "number.sp", "meter_source": "off"},
_Hass(), store, _P(), stop=asyncio.Event())
check("...so the next restart comes back armed and untripped, as it should",
not fresh.sign_wd.tripped)
# ⚠️ THE WRITE ORDERING IS AN INVARIANT, SO IT GETS AN ASSERTION. main.py writes
# `sign_reason` and THEN `sign_tripped`, each one its own `save()`, so that a
# process that dies between the two leaves a reason nothing reads - harmless -
# rather than a latch with no explanation for the operator who has to decide
# whether to clear it. Documented reasoning is not enforcement: swapping those two
# lines used to pass every check in this file.
#
# The death is modelled as the second write raising. In the field it is a power
# cut or a container kill (Store.save() swallows OSError rather than raising), so
# what is asserted here is the PROPERTY - what survives on disk - not the
# mechanism.
class _CrashOnFlag(_MemStore):
def set(self, k, v):
if k == TRIPPED_KEY and v:
raise RuntimeError("power cut, mid-trip")
super().set(k, v)
async def _crash_mid_write():
store = _CrashOnFlag()
hass = _Hass()
opts = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 2000, "gain": -0.6,
"sign_disagree_w": 300, "sign_disagree_s": 1, "auto_start": True}
c = Controller(opts, hass, store, _P(), stop=asyncio.Event())
c.auto = True
c.dev_min, c.dev_max = -5000.0, 5000.0
died = False
for _ in range(12):
try:
await c.read_inputs()
await c.cycle()
except RuntimeError:
died = True
break
await asyncio.sleep(0.25)
return store, died
crashed_store, died = asyncio.run(_crash_mid_write())
check("the second write is the one that sets the flag", died)
check("a crash between the two writes leaves the REASON on disk",
"SIGN_DISAGREEMENT" in crashed_store.data.get(REASON_KEY, ""))
check("...and never a latch with nothing to explain it",
not crashed_store.data.get(TRIPPED_KEY))
print()
if fails:
print(f"{len(fails)} FAILED: {', '.join(fails)}")
sys.exit(1)