SAFETY-39: slew_w is a ratio to the rail, and gain is what is still wrong
`slew_w: 1000` was derived on 2026-08-22 against a clamp of 1500 W, where
"capping how far the loop can jump ahead of the inverter" was true because the
rail itself bounded the excursion. The live install went to max_w 5000 and the
constant did not move, so the loop crosses its whole output range in 10 s
against a plant NOTES.md §5.10 measured at ~18 s. Measured on the owner's system
2026-09-05 11:43-11:46: a 3.4 kW export drove the setpoint 380 -> 5000 W in five
2 s ticks, the battery to -5154 W past a 5000 VA rating, and the grid from
3.4 kW of EXPORT to 2.8 kW of IMPORT. Nothing was broken; the rail moved.

REPRODUCED FIRST, and one half of it is not reproducible at all. On
plantsim.Plant and on an independent in-repo model: the setpoint stepping a full
1000 W per tick to the rail (48 of 51 export steps), and the meter crossing from
export into import. The -5154 W figure is NOT reproducible in either model,
because both clamp the plant at its rating - so the card's AC "battery no longer
exceeds max_w in simulation" is unfalsifiable and was rewritten rather than met.

THE DELIVERABLE IS THE RELATIONSHIP.
  SLEW_RAIL_FRAC = LOOP_TICK_S / PLANT_SETTLE_S = 2 s / 18 s = 1/9
  slew_w = 0 now means FOLLOW THE RAIL - SLEW_RAIL_FRAC * max_w - exactly as
  integrator_max_w = 0 already means follow max_w. It is the shipped default:
  222 W at max_w 2000, 556 W at 5000, 1067 W at a ~9600 W two-inverter site.
  validate.py rule 10 refuses an explicit value faster than that, graded against
  sum(unit_caps(opts)) - the roster sum, i.e. Controller.site_max_w - so a
  second inverter moves the bound with no operator action.

VERIFIED BY BREAKING IT: restoring slew_w 1000 at max_w 5000 is refused, and the
refusal names the rail, the crossing time, the measurement and what to do.
Equality, one watt of slack, the live interim 400 and slew_w 0 at every rating
all still start.

GAIN IS THE CONSTANT THAT IS STILL WRONG, and it is NOT changed here. Over 51
export steps the over-absorption is FLAT in slew (958 W at 1000, 1081 W at 250)
and monotone in gain (987 W at 0.6, 876 at 0.3, 435 at 0.2): slew_w bounds the
OUTPUT, while the integrator moves gain*error per cycle and reaches a 5000 W
rail in under three ticks whatever the slew is. Two control-law constants moving
in one release on a running house makes the next measurement uninterpretable.

⚠️ N=2: the site rail becomes sum(max_w) ~ 9600 W (inverter B FROM DATASHEET AND
SERIAL, not measured, and sim/plantsim.py's INVERTER_B is A copied), and the
enforced ratio produces 1067 W there automatically. But a growing rail LOOSENS
this bound, and the >= 900 W symptom goes stale at N=2 the same way the constant
did - both stated in the record rather than left to be discovered.

Nothing reached the inverter. The live install still runs the interim slew_w 400
applied by hand on 2026-09-05, which rule 10 accepts unchanged.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-06 01:10:15 +02:00

221 lines
9.3 KiB
Python

"""Runnable check for the control loop's cadence. `python3 test_loop.py`
SAFETY-12: the loop must evaluate on a clock as well as on a change. Before the
fix, `run_control()` ran `cycle()` only when the meter value differed from the
previous poll, so a meter that repeats a value ran NO control cycles while the
heartbeat kept re-emitting the last command - measured on the rig during TEL-05
as 70 s at a literally constant 350.0 W with 14 arrivals and zero cycles.
⚠️ THIS TEST TAKES ~95 SECONDS OF WALL CLOCK (measured 93 s), on purpose, and
that figure is the only thing standing between it and a future developer who
decides a slow test is a broken one. The thing under test is a wall-clock floor
inside a loop that sleeps 1 s; mocking the clock would leave the assertion
testing the mock. It drives the real `run_control()` and counts what actually
happened. Eight runs of the real loop is what the eight scenarios cost.
⚠️ If you shorten the windows, re-measure and update this number and the one in
HANDOVER.md. An understated runtime reads as a hang.
`cycle_floor_s` is read from options with no lower bound in code, so a huge
value reproduces the pre-fix behaviour exactly. Every claim below is therefore
an A/B on one binary, not a comparison against a remembered old one.
⚠️ MUTATING THE MODULE THIS FILE GRADES? PURGE `__pycache__` FIRST - or run
`tools/mutation_run.sh`, which does. `python3 -B` alone does NOT save you: it
stops bytecode being WRITTEN, not a stale one being READ, and a size-preserving
edit reverted inside one second is invisible to CPython's staleness test. That
is TEST-15, and it has already turned one live mutation into a false survivor.
Read MUTATION.md before you report a survivor.
"""
import asyncio
import sys
import time
from app.main import Controller
fails = []
NEVER = 1e9 # cycle_floor_s so large the floor can never elapse: pre-fix
def check(name, cond):
print(f" {'ok ' if cond else 'FAIL'} {name}")
if not cond:
fails.append(name)
class FakeHass:
"""A scripted meter and a plant that tracks the command instantly."""
def __init__(self, meter, soc_dies_at=None):
self.meter = meter
self.soc_dies_at = soc_dies_at
self.batt = 0.0
self.writes = []
self.t0 = time.monotonic()
async def limits(self, entity):
return (-5000.0, 5000.0, 1.0)
async def number(self, entity, invert=False):
now = time.monotonic() - self.t0
if entity == "sensor.grid":
return self.meter(now)
if entity == "sensor.batt":
return self.batt
if entity == "sensor.soc":
if self.soc_dies_at is not None and now >= self.soc_dies_at:
return None
return 50.0
return None
async def set_number(self, entity, value):
self.writes.append(float(value))
self.batt = float(value)
return True
class _Store:
data = {}
def set(self, *a):
pass
class _Pub:
enabled = False
def publish(self, *a, **k):
pass
def close(self):
pass
BASE = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 2000, "gain": 0.6, "slew_w": 0,
"deadband_w": 15, "target_grid_w": -10, "step_w": 10,
"heartbeat_s": 10, "stale_input_s": 15}
def drive(meter, floor, seconds, soc_dies_at=None, **over):
"""Run the real control loop for `seconds`; return (cycle times, writes)."""
async def go():
hass = FakeHass(meter, soc_dies_at)
c = Controller(dict(BASE, cycle_floor_s=floor, **over), hass, _Store(),
_Pub(), stop=asyncio.Event())
c.auto = True
stamps = []
real = c.cycle
async def counted():
stamps.append(time.monotonic() - hass.t0)
await real()
c.cycle = counted
task = asyncio.create_task(c.run_control())
await asyncio.sleep(seconds)
c.stopping = True
await asyncio.wait_for(task, timeout=10)
return stamps, hass.writes, c.target, c.reason
return asyncio.run(go())
def worst_gap(stamps, seconds):
"""Longest stretch with no cycle, including the tail after the last one."""
edges = [0.0] + list(stamps) + [seconds]
return max(b - a for a, b in zip(edges, edges[1:]))
# --------------------------------------------------------------------------- #
print("a meter that repeats the same value")
FLAT = lambda t: 350.0 # noqa: E731
FLOOR, SECONDS = 3.0, 12.0
pre_stamps, pre_writes, _, _ = drive(FLAT, NEVER, SECONDS)
# The defect itself, demonstrated rather than described: one cycle at startup
# and then nothing for the rest of the window, while writes keep happening.
check("pre-fix: a constant meter runs exactly one cycle, at startup",
len(pre_stamps) == 1)
check("...while the heartbeat keeps writing anyway, so nothing looks wrong",
len(pre_writes) >= 2)
post_stamps, post_writes, _, _ = drive(FLAT, FLOOR, SECONDS)
check("post-fix: the same constant meter runs cycles throughout",
len(post_stamps) >= int(SECONDS / FLOOR) - 1)
# The actual acceptance criterion: a BOUND on the gap, not a count.
gap = worst_gap(post_stamps, SECONDS)
check(f"...with no gap longer than the floor ({gap:.1f}s <= {FLOOR + 1.5:.1f}s)",
gap <= FLOOR + 1.5)
check("...and the loop actually corrected, instead of holding a stale command",
len(post_writes) > len(pre_writes))
# --------------------------------------------------------------------------- #
print("a meter that changes normally - nothing may move")
# ⚠️ THE REGRESSION GUARD, and the more important half. The floor is a deadline
# on the gap between cycles, reset by every cycle whichever trigger fired - not
# a second scheduler. On a healthy meter it must never elapse, so the cycle
# count, the write count and the commanded values must be IDENTICAL either side
# of the fix. Anything else is a new write cadence, which SAFETY-12 forbids:
# the deadband, step_w and the 10 s force-write decide what reaches the wire,
# and this change is only allowed to alter when the loop thinks.
STEPS = [0.0, 300.0, 850.0, -400.0, 120.0, -900.0, 60.0]
LIVE = lambda t: STEPS[int(t // 2) % len(STEPS)] # noqa: E731
a_stamps, a_writes, _, _ = drive(LIVE, NEVER, 12.0)
b_stamps, b_writes, _, _ = drive(LIVE, FLOOR, 12.0)
check("a changing meter runs the same number of cycles as before the fix",
len(a_stamps) == len(b_stamps))
check("...commanding exactly the same sequence of values", a_writes == b_writes)
# --------------------------------------------------------------------------- #
print("a meter parked at the target - the converged operating point")
# The case TEL-05 warned about: at the converged target the power figure
# legitimately repeats for minutes. The loop must still run, and must still
# write nothing but the heartbeat, because the deadband - not the arrival
# trigger - is what holds the command still.
AT_TARGET = lambda t: -10.0 # noqa: E731
c_stamps, c_writes, _, _ = drive(AT_TARGET, NEVER, 12.0)
d_stamps, d_writes, _, _ = drive(AT_TARGET, FLOOR, 12.0)
check("the loop evaluates at the converged point too", len(d_stamps) > len(c_stamps))
check("...and the deadband still holds the command, so writes are unchanged",
d_writes == c_writes)
# --------------------------------------------------------------------------- #
print("an input dies while the meter repeats - the safety claim must still fire")
# ⚠️ THE STRONGEST PROPERTY IN SAFETY-12, and the one that makes it a safety fix
# rather than a latency fix. The `inputs missing -> 0 W` claim lives INSIDE
# cycle() (main.py, the stale_input_s branch and the P_SAFETY claim below it).
# Pre-fix, on a meter whose value happened to repeat, cycle() was never called
# again - so that claim could not fire AT ALL. The controller held its last
# command through an input outage of unbounded length with the status line still
# reading "loop -> N W".
#
# Layer 1 does not cover this either on a `meter_source: off` install: no P1 age
# sensor is published (see Controller.publish), so the firmware has nothing to
# veto on, and the heartbeat keeps its watchdog fed the whole time.
#
# stale_input_s is shortened to 3 s here so the outage resolves inside a test
# rather than inside a quarter of a minute. The mechanism is the default one.
c2_stamps, c2_writes, pre_target, pre_reason = drive(
FLAT, NEVER, 10.0, soc_dies_at=4.0, stale_input_s=3)
check("pre-fix: a dead input during a constant meter never reaches the safety claim",
pre_target != 0.0 and "safety" not in pre_reason)
check(f"...so it holds its last command instead ({pre_target:g} W, {pre_reason!r})",
pre_target == 220.0)
d2_stamps, d2_writes, post_target, post_reason = drive(
FLAT, FLOOR, 10.0, soc_dies_at=4.0, stale_input_s=3)
check("post-fix: the same outage commands 0 W", post_target == 0.0)
check(f"...through the safety claim, not by accident ({post_reason!r})",
"safety" in post_reason)
check("...and the 0 W actually reached the device", 0.0 in d2_writes)
# --------------------------------------------------------------------------- #
print()
if fails:
print(f"{len(fails)} FAILED: " + "; ".join(fails))
sys.exit(1)
print("all checks passed")