SAFETY-39: correct the gain figures, which were not the measured ones
Review found validate.py:288-289 carrying numbers that appear nowhere
else in the PR's evidence and could not be reproduced: over-absorption
"1233 W at slew 1000 and 1344 W at slew 250 ... 1495 W at 0.6, 961 W at
0.3, ~0 W at 0.2". A grep for 1233/1344/1495 found them ONLY in that
comment - the DECISIONS record, the PR body, test_control.py's audit
table and slew_sim's own output all carried the correct ones.

The measured values, from re-running tools/slew_sim.py on the real plant
model at the stated conditions (max_w 5000, 2 s tick, 51 export steps
1.0-4.2 kW): slew column 958 (slew 1000) and 1081 (slew 250); gain column
987 (0.6), 876 (0.3), 435 (0.2).

⚠️ "~0 W at 0.2" WAS WRONG IN THE UNSAFE DIRECTION. It invited a future
reader to conclude that dropping gain to 0.2 removes over-absorption. It
does not: 435 W remains, which is 44 % of the figure at 0.6, not zero.
The corrected text says so at the line rather than leaving a round number
to be trusted.

The conclusion the paragraph draws is unchanged and still holds on the
measured figures: over-absorption is flat in slew_w and falls in gain, so
`gain` is the constant that would have to move, and SAFETY-39
deliberately does not move it.

No behaviour change; comment only. Full suite: 21 passed, 0 failed.