EV-51: Solar decides every meter-age rule on the writer step's own age; DEBUG line per step
The writer step took the meter age from the snapshot of the previous cycle
(silent / unknown_s / hold), so in production order the silent-meter pause
came one cycle late (C21) and a start or raise could still be written at an own
age of 31-39 s (C22, N8). The step now judges its own age: the pause timing and
held_pause, the non-zero write block (nz_block), and the late-readings hold with
its stale rule. Meter values stay from the snapshot; car.held / car.reading and
the arrival sources' spare-unknown check are unchanged.

Also: one DEBUG line per Solar writer step (time, meter age, decision, write);
tools/ev20_sun.drive takes cyc / phase / jitter / cset (default unchanged);
test_ev51.py (T1-T43, N1-N12); DECISIONS states the rule once.

Co-Authored-By: Claude <noreply@anthropic.com>
Co-Authored-By: Claude Sonnet 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01VSY9UpTaUYnjJF5oVtbM1w
2026-11-24 17:26:03 +01:00

12 KiB

EV-20 — Solar mode: spare sun to the car (charging only)

Part 1 of the split of cancelled EV-05 (owner 2026-11-19). The design is reports/EV-01-design-report.md sections 2-5 and decision 5; the rules are EV-20's brief (Expected 1-15, D1-D4). EV-21 (the car cut first for the peak) and EV-22 (another writer's phase change) are separate cards. This record keeps what the code had to decide.

Where it lives

app/carmode.py: SolarPlan (pure: the spare, the room, the dwells, the auto phases) and SolarWriter, a subclass of EV-04's ManualWriter. It writes only through ManualWriter._write and _advance, so the two write call sites stay exactly two (test_ev04 / test_ev20 T55). app/ctl_car.py builds the inputs (car_spare_w, car_room_w), runs the step beside the cycle, the release at shutdown and today's solar kWh.

One rule for every write (EV-05 review rounds 2-9)

EV-05 needed nine review rounds, mostly on exits and other writers. EV-20 keeps one small set of facts and derives every path from them:

  • sent_a: the current Solar last decided, recorded BEFORE the write goes out; taken: the charger confirmed it. A write cancelled while it waits is never trusted (round 2, T37).
  • A value is written when Solar DECIDES a new one. One the charger did not take is tried again after 60 s, three times, then the gave-up row and one CHARGER_REFUSED warning (EV-04's rule; round 2's Critical, T36). A new 0 A gets its own three tries and never waits.
  • A read-back that shows what Solar sent confirms it, however late (round 9's second Major, T48).
  • A read-back that differs from what Solar sent is never written over: EV-04's _watch judges it, and while the difference stands Solar writes nothing in its running state. After 30 s the hold (amber row, one CHARGER_OTHER warning) stops every write, the way-out 0 A and the shutdown's included (N16; rounds 5-7). Only pressing Solar lifts it.
  • live: Solar's own current may stand on the charger (a non-zero value it sent, or a 0 A not yet confirmed). A way out (Off, Stop, shadow, a safety stop, a charger error or stuck reading, no car, shutdown) writes 0 A only then. So a start in shadow writes nothing, and once the way-out 0 A is confirmed nothing more is written, shutdown included (rounds 6 and 7).
  • The start-up and a charger (or Home Assistant) that comes back write 0 A first whatever the charger shows, with the read-back references cleared, so its own value is never "another writer" (D2; round 9's first Major, T29, T30, T61).

Choices the brief left open

  • Writes over an unexplained read-back stop at once, not after 30 s: the plan goes on, the next decision waits. A way out still writes its 0 A inside those 30 s (T39 (b)): 0 A is the safe side.
  • The phases follow the charger. Solar's arithmetic uses the phases the charger reports (1 for a one-phase car); its plan adopts them whenever it is not switching. It selects only by its own dwells (and a start from a pause in auto, on 1 phase), never "back" over a change it did not make (D4: EV-22). A lower current is never blocked by the 10-minute phase gap (round 8, T46).
  • An interrupted phase change ends at its 0 A. Manual's restore of the old current stays Manual's.
  • Pressing Solar lifts another writer's hold and takes the charger as it is; Solar's own value is then decided and written afresh. Choosing Solar from another mode starts paused: 0 A, then the start rule.
  • Stale and unknown. The spare is unknown with a meter older than stale_input_s (P1's own bound may be longer), readings late past it, a missing or NaN battery or grid figure, or a charging car whose figure is stale, stuck or not corroborated. A paused or idle car counts as 0 W. Unknown holds the current for ev_pause_min, then 0 A. A cycle that returns early for missing or late readings still steps Solar (Manual is left as it was).
  • The guard treats a Solar car exactly as a Manual car (Expected 8): every alarm-path test that said "Manual" says "Manual or Solar" (car_controlled). Solar's own phase change gets EV-15's grace as Manual's; its own 0 A pause gets it from the send, at most OWN_PAUSE_MAX_S, and only while the read-back still shows that 0 A (round 8's second Major).
  • D1 wording. The card's Why says "Solar charges the car at {a} A. This sets the peak."; STYLE.md allows a grey note and a grey row one sentence, so they say "Solar charges the car at {a} A, which sets the peak." {a} is the charger's read-back, never Manual's stored current.
  • D3 at shutdown. In Solar the charger's 0 A goes out before the inverters' 0 W: up to three tries 5 s apart, each waiting 4 s for its read-back (write_current(took_s=...)), all inside RELEASE_WAIT_S (15 s, also a wall-clock bound for a charger that hangs). Not taken: one CHARGER_RELEASE warning, the notice Car may still be charging after the inverters are released, and the next start writes 0 A first (D2) and takes the notice down.
  • A charger error sets 0 A (while owed) with one CHARGER_ERROR warning and the card's Why; the existing grey error row shows it. No new notification.
  • Solar kWh is counted per cycle in Solar only: min(car, max(0, spare - room)) Batteries first, min(car, max(0, spare)) Car first; never above today's kWh; stored with its day, reset at the day's change.
  • Rollback. An older build reads a stored car_mode = solar as Off (start_mode) and writes nothing; no state migration.

SPIKE-05 decisions (brief v4/v5)

  • C1. An own 0 A that is out and not read back is kept in the store with the mode (car_exit_0a_pending). A start in Off with that flag writes the 0 A (when it may write), retried by the exit rule; Off without it writes nothing (N10). A start that will not write (shadow, control stopped) after Manual or Solar, with the charger showing a current, writes nothing and raises one warning, Charger kept its current, taken down at 0 A.
  • C5. Each shutdown try waits 4 s for its read-back (D3 above).
  • C6. One write clock: Solar's 30 s gate also counts from Manual's latest non-zero write, the start included. Solar's first write after Manual is its 0 A, which is never gated.
  • C8. A charger or HA outage ends a phase change: the return restarts the plan paused, so nothing of the sequence resumes; only a 0 A may come before the start rule.
  • C9. An exit owes its 0 A while Solar's own value may stand: by its own bookkeeping (a 0 A not read back counts) or by the read-back showing a value it sent, confirmed, tried or saw at a refused try.
  • C3 is T43-T45; C7 is EV-22's.

Rig round 1 (rig FAIL on cc8c0dc), with EV-32 and EV-36

  • The stuck-reading check (chargers.py CarTracker), for every writer (SPIKE-06 option 2, PM decision; replaces 3a17012's power rules).
    • Baseline: the signature (power, read-back) of the latest reading taken BEFORE the send, kept at begin_write; never a reading that arrived while the write waited (the rig's race, C10/C11, C13).
    • Arms: a write that moved the setpoint by STUCK_MIN_A. Accepted: at its send, on the baseline. Refused (EV-13): only with no life in TOOK_S, dated the send, on the baseline. EV-36: the first sample after the send is not life by itself; life differs from the samples before the send AND from that first one.
    • Clears: any reading whose signature differs from the baseline.
    • Stuck: armed and not cleared for STUCK_S (60 s).
    • A frozen POWER under an accepted write (the read-back moves) is no longer judged here: the energy meter (EV-18 contradicted) and the read-back cap on the trusted figure judge it.
  • Solar after a stuck verdict (C12, C14): while no current of Solar's own may stand (its own 0 A stands, or Solar was just chosen), a stuck verdict no longer holds Solar: it writes its 0 A first over a current that is not its own, then the start rule runs; at most MAX_TRIES starts per verdict, then one CHARGER_REFUSED, then one more start after 15 min and one every 30 min (PM decision: no hold until a press). The episode ends when the reading follows a start, on a press of Solar, Off, Manual, shadow or a stop (_stuck_end). Its write moves the reading (the verdict clears) or is refused (EV-04's retries, then CHARGER_REFUSED).
  • No amp ping-pong: after a step down, a step back up needs UP_HYST_W (100 W) past the amp boundary.
  • The meter's age: Solar's own stale_input_s gate applies where the age measures arrival (HomeWizard local, MQTT, DSMR). On ha_signed the age is the time since the value changed (Home Assistant publishes changes only), so a healthy meter at a flat load would read as stale; there the source's own meter_max_age_s is the bound (a silent meter: 0 A at meter_max_age_s + ev_pause_min).

Rig round 2 (rig FAIL on 09b6af9), PM rulings

  • A short charger read gap (chargers.py CarTracker.observe, shared by Solar, Manual and the peak guard): a reading missing for less than stale_input_s keeps the last trusted reading (held). A gap is a read that got no answer, or every required entity unavailable; one entity missing, a wrong power unit or the login off stay readings of their own (EV-03 round 4, unchanged); nothing is decided or written in that cycle: no writer steps (ctl_car.car_step returns), no plan count moves (start, phase change, hold, set_at) and a decision due then runs on the next real reading (review r3, PM design). The one exception is Solar's pause by the meter's age (C18, held_pause). A held read neither arms nor clears the stuck check. At stale_input_s the missing reading is taken as before (the safe path: the charger is gone, 0 A first on its return). This also ends the false PEAK_GUARD_FLOOR_LIMITED after one gap (EV-18 T10(b) changed accordingly).
  • Silent meter on ha_signed: Solar's unknown-sun pause is timed from the meter's age: unknown since the age passed meter_max_age_s, so 0 A on the first car step whose own meter age (now minus the last reading, at that step) is >= meter_max_age_s + ev_pause_min (330 s), held steps included. Arrival sources are unchanged.
  • EV-51: decided at the step's own meter age. Every decision that rests on the meter's AGE is taken at the writer step's own age, not at the age the cycle saw one step earlier: the pause above, the write block while the meter is silent (no non-zero current, C17), the held-read pause (C18) and the late-readings hold with its stale rule (a spare read while the hold was on is not used once the step's own late time reaches stale_input_s). The meter's VALUES (spare, target) stay the cycle's, one cycle of sensor latency being normal; car.held and car.reading are unchanged. Arrival sources keep the cycle's age for their "spare unknown" check. At log level debug each Solar step logs one line: time, the meter age at the step, the decision and the write.
  • No non-zero write while the meter is silent (SPIKE-06 C17, N8 strict): while the meter's age is past meter_max_age_s, Solar sends no non-zero current: no retry, no raise, no phase change begun, and a phase change under way ends at its 0 A (no select after that, no closing current); the plan pauses. 0 A is always allowed. Also on a held read (nz_block).
  • The age pause on a held read (C18): on a held cycle Solar does not step (review r3, PM design); only held_pause runs: while the meter is silent and its age has reached meter_max_age_s + ev_pause_min, the plan pauses and a NEW 0 A goes out (no retry to a charger that is not answering). No phase change, start, hold pause or other count moves on a held cycle.
  • Accepted (PM, P9g): a frozen charger that also stops answering is flagged only once it answers again; the 15 s safe path covers the gap.
  • A held read during a phase change (SPIKE-06 C19): a phase change under way does nothing on a held read (no write, no pause) and goes on at the next real reading; it ends at its 0 A only while the meter is silent (C17). No phase change begins on a held cycle; a gap of stale_input_s or more takes the safe path unchanged. Accepted by design (PM): a one-sample partial reading (only power unavailable, say) still gives the D2 0 A.