Review B1: the meter fit took repeating house loads (ovens, a heat pump)
for late readings on healthy 1-2 s sites, about 9 % of the recorded
house. B2: at a 5 s meter it never ran. M1: no hysteresis. M2: an
unbounded check.
lateness.Delay now fits how long each battery's reading takes to show
its own request, which the house does not move, from the 1 s reads
(read_inputs -> Answer.watch). The meter fit stays for speed at 1-3 s
meters, but counts only when an ask was slow to start and no battery
fit said on time. Late from 9.5 s after 2 fits, on time under 6.5 s,
dropped after 120 s without a fit. Fits are bounded (a few ms).
Readings on time: no verdict in any reviewer scenario (22 shapes at
1/2/5 s meters, 7 harm runs) nor in 2 days of the recorded house at
1, 2 and 5 s ticks; digests equal to 77fe31b. Late: found 36-68 s after
the start at 1-2 s, about 3 min at 5 s. The row gives the batteries'
delay, or no figure while only the meter has shown it.