SAFETY-135 - one guard stop does not cost the night charge the whole period
Status: for review, round 2. Code: Controller._mode_roles() and
Controller._give_falling() (app/ctl_trade.py), modetrade.decide(wait=),
RESTART_S, YOUNG_S, GAVE_S, WAIT_WORDS (app/modetrade.py). Tests:
test_safety135.py. Battery modes only. No option, no change to the peak
guard.
Problem. A grid charge the peak guard stops stays off to the period's end (the OPT-11 latch). Three cases seen on TEST-23:
- A spike at a period's start (UX-77 I-1, x10): a 1-3 s spike, or a charge still at full power from the end of the last period, makes the guard project 4.3-6.6 kW and cut the charge. The cut is right, but one 2 s spike cost 15 minutes of charge, about 0.16 kWh per trip on the rig.
- A start at the tariff edge (sim, 5 s meter): a give ends at 01:00 and the cheap run starts. The battery reading drops at once, the meter a few seconds later. In between, grid + batteries reads the house too low, the room too big: the charge starts and the guard cuts it within seconds.
- An oven cycling under a cheap-hours charge (SAFETY-136 rig run C/s5b, x1): the charge started at 01:00:32 in an oven pause and the guard cut it at 01:01:31 when the oven came back on (5.3 kW projected). The cut is right, but the charge stayed off to 01:15.
Decision.
- The first guard stop in a period does not latch. A charge the peak guard
stops (or a measured headroom stops in the period's first
YOUNG_S= 60 s) may start againRESTART_S= 60 s after that stop, under the normal start rule (guard clear, headroom overSTART_W), but not in the period's last 60 s: there the room is the deficit times 900/s left, and a restart overshot by 15 W in the owner-shape night (N=2, 01:00). A second stop latches to the period's end, so there is at most one restart per period and the OPT-11 flip guard keeps its job. A measured headroom stop later in the period latches at once, and an unmeasured headroom (OPT-15) on its second stop, as before. Why only guard stops later on: all three rig cases are guard stops, while a headroom that falls to 0 W mid period is the slow loss of room the OPT-11 latch was made for (the 2026-09-09 flips), so freeing it buys no case and risks that flip. Three existing checks pinned "one start per period" and move with this:test_modes_p3.py(a house swinging 2.0/3.9 kW each minute: now at most two starts per period),test_price_run_fixes.py1c (a 1-minute 3.7 kW load: one restart after 60 s), and then1_chdigest intest_modes_p4.py(only the waiting reason word moved, "(peak)" for "(headroom)"; with this card off it is OPT-15's pin again). - No start while a give is still falling. In a period's first
YOUNG_S, while the batteries give overSTART_Wless than they did in the lastGAVE_S= 15 s, no charge starts: the meter may not show that drop yet. A smaller drop does not hold the start.
The guard is not touched (claim, floor, projection), so a real over-aim load is cut on the same cycle as before, and a running charge is never held. While a start waits, the status row says "grid charge paused, it tries again in a minute" or "grid charge waits for the meter to catch up".
Options weighed.
- Round 1: only a stop in the first 60 s does not latch. Missed the rig oven case, cut at 91 s (review M-1).
- Re-evaluation each cycle with no latch: brings back the 13 flips in 4 minutes the latch was made for (2026-09-09 replay).
- Restart at once after the first stop: two flips in 20 s with spikes at
0/20 s (
test_safety135.pypart 5 fails on it). - No start in a young period within 60 s of a give or a guard action: 0.018 kWh (N=1) and 0.003 kWh (N=2) less than base on the owner night.
- Cutting the young room by the recent give: double-counts once the meter catches up and flapped on a 1 s meter where base did not.
- A hysteresis band: the edge error is the readings' age, not a small room.
Numbers (scratch/SAFETY-135/dev/s135_sim.py, real cycle(), TEST-23-like
lag, 1 s cycle, two 2.5 kW batteries unless said, cap 3 500 W, aim 3 450 W;
the sim's grid average per period):
| Scenario | Base: paused s, kWh, flaps, top period | Head |
|---|---|---|
| (a) 4 s spike at 01:30 and 01:45, house 2.8 kW | 1 197 s, 0.330 kWh, 1, 3 458 W | 139 s, 0.537 kWh, 0, 3 458 W |
| (b) 01:00 edge after a give, 5 s meter, house 3.0 kW | 882 s, 0.006 kWh, 1, 3 009 W | 21 s, 0.119 kWh, 0, 3 464 W |
| (b) the same, house 2.4 kW | 0 s, 0.266 kWh, 0, 3 461 W | 11 s, 0.266 kWh, 0, 3 461 W |
| Rig s5b (5 kW + 4.6 kW, oven), 1 s / 5 s meter | 838 / 886 s, 0.054 / 0.035 kWh, 2 224 / 2 123 W | 793 / 793 s, 0.075 / 0.084 kWh, 2 299 / 2 286 W |
| (c) +4 kW for 5 min from 01:30:20 | cut 01:30:22, 0.387 kWh | cut 01:30:22, 0.492 kWh |
| Owner-shape night, N=1 / N=2 | 5.510 / 6.048 kWh, top 3 454 / 3 453 W | 5.510 / 6.169 kWh, 3 454 / 3 453 W |
| Owner-shape day, N=1 / N=2 | top 331 / 145 W | the same |
In s5b the restart at 01:02:32 is cut again by the oven at 01:03:17 and then
latches: one restart, as designed. A +4 kW load from second 30, 57, 59, 60 or
61 (N=1 and N=2) is cut on the same cycle as base, the charge restarts only
after the load ends, and the period lands at 3 450.0 W (base 3 037-3 350 W).
The add-on's own period averages in test_safety135.py are at or under the
aim + 2 W in every part.
Sensitivity (one constant moved, the others as shipped; head):
| Constant | Spike (a): paused s, kWh | Edge (b) 5 s meter 3.0 kW: paused s, flaps | Rig s5b 1 s: kWh, period W | Owner night N=2: kWh, top W |
|---|---|---|---|---|
RESTART_S 30 |
79, 0.541 | 21, 0 | 0.082, 2 321 | 6.206, 3 459 |
RESTART_S 60 (shipped) |
139, 0.537 | 21, 0 | 0.075, 2 299 | 6.169, 3 453 |
RESTART_S 90 |
199, 0.532 | 21, 0 | 0.061, 2 250 | 6.169, 3 453 |
RESTART_S 120 |
259, 0.528 | 21, 0 | 0.085, 2 338 | 6.169, 3 453 |
GAVE_S 5 |
- | 75, 1 | 0.075, 2 299 | 6.170, 3 453 |
GAVE_S 10 |
- | 15, 0 | 0.075, 2 299 | 6.169, 3 453 |
GAVE_S 15 (shipped) |
- | 21, 0 | 0.075, 2 299 | 6.169, 3 453 |
GAVE_S 30 |
- | 35, 0 | 0.073, 2 290 | 6.168, 3 453 |
YOUNG_S 30 / 90 |
- | 21, 0 | 0.075, 2 299 | 6.169, 3 453 |
RESTART_S 30 restarts the owner night in a period's last 30 s and lands
9 W over base's top period; 60 is the shortest value without that. In s5b
the value only moves where the restart meets the oven cycle. GAVE_S 5 s is
shorter than a 5 s meter's age and flaps again; 10-30 s only move the wait.
YOUNG_S does not move these runs: the give falls in the first seconds.
On the synthetic night where the house alone is 950 W over the aim (N=1, heat pump 4.4 kW), head's top period is 4 403 W against base's 4 401 W: a charge restarted in the period before runs into the heat pump's start (the carry-over below). Base charges 1.142 kWh there, head 1.560 kWh.
Not changed. With battery modes off, arbitrage.decide() has no period
latch and sizes the charge to the headroom each cycle (SAFETY-45). A charge at
full power in a period's last seconds still runs into the next period (the
charge side of SAFETY-124); with rule 1 that costs 60 s, not the period.