TEL-14: PV sign declared per entity (pv_invert_entities)
Some PV entities (kWh meters, ESPHome clamps in the PV circuit) read positive
for consumption and negative for production. `pv_invert_entities` lists the
ones to flip; the flip is applied per member inside pv.total(), before the sum,
so the MQTT `pv` row and the status page carry the corrected figure. Default []
is byte-identical to 0.12.0.

Shape measured in supervisor_shape_probe.py section H (Supervisor 2026.08.0):
a parallel list validates the 0.12.0 blob unchanged and renders as its own
translated repeatable field; dicts on pv_entities refuse 0.12.0's stored
strings; a prefix is invisible syntax; a global bool cannot describe a mixed
roster. Status page marks flipped entities and cautions per entity below
-50 W, saying ADD or REMOVE. Telemetry only: control documents unchanged.

Record: DECISIONS/TEL-14-pv-sign.md (reverses TEL-11 section 2).

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-25 00:25:24 +02:00

303 lines
44 KiB
YAML

# Home Assistant add-on translations - ENGLISH (UX-01)
#
# ⚠️ WHAT THIS FILE IS FOR, AND WHAT HOME ASSISTANT ACTUALLY DOES WITH IT.
# Without a `translations/` directory the Configuration tab renders the raw
# option KEYS - `unit_sign_disagree_w`, `saturation_cycles`, `integrator_max_w`.
# The frontend keeps a field when `e.name in options || e.required`, and all 72
# keys are in `options:` (59 of them are `required` as well), so ALL SEVENTY-TWO are
# rendered, always, in `schema:` order, with no description. This file is what
# turns that into sentences.
#
# HOW IT IS READ, measured on the Supervisor image this site runs
# (ghcr.io/home-assistant/amd64-hassio-supervisor:2026.08.0):
#
# * `supervisor/store/data.py:_read_app_translations()` reads every
# `.yaml`/`.yml`/`.json` in this directory, keyed by FILE STEM (so this file
# is the `en` translation), and validates each through
# `SCHEMA_APP_TRANSLATIONS`: `configuration: {str: {name (required),
# description, fields}}` plus `network: {str: str}`. ⚠️ A FILE THAT FAILS
# THAT SCHEMA IS DROPPED WITH A LOG WARNING AND NOTHING ELSE - the add-on
# goes on rendering raw keys and nobody is told twice. tools/
# supervisor_shape_probe.py section F is what says it loaded.
# * The frontend resolves each label as
# `translations[<user's language>]?...name || translations["en"]?...name ||
# schema.name`, and the helper text the same way with `description`. ⚠️ THE
# FALLBACK IS PER KEY, so a key missing from nl.yaml degrades to this file,
# while a key present but wrong does not degrade at all.
#
# ⚠️ ORDER IS NOT SET HERE. `App.schema_ui` is `UiOptions(...)(data["schema"])`,
# so the Configuration tab renders in the order of config.yaml's `schema:`
# block. The order below only mirrors it so the two files read alike.
#
# ⚠️ ADD-ON OPTIONS ARE A FLAT LIST. There is no section-header primitive, no
# per-option "advanced" flag, no units on the input and no sliders, so grouping
# is approximated by ORDER plus the `Group · ` prefix in each label. Do not
# promise the operator visual sections; there are none.
#
# ⚠️ EVERY DERIVED CONSTANT SAYS WHERE IT CAME FROM. The Configuration tab
# presents a number read off 1890 closed-loop test runs and the operator's own
# inverter rating as the same kind of field. The descriptions are the only place
# that difference can be stated, so a derived value names its campaign and says
# "do not change without re-deriving", and a value that is genuinely the
# operator's says so too.
configuration:
setpoint_entity:
name: "Hardware · Inverter setpoint entity"
description: "The ESPHome number entity this add-on writes the power setpoint to, normally number.*_goodwe_setpoint_w. This is the only thing the add-on commands. Leave it empty if you fill in the inverter list below: a site with a roster must not also name one loose actuator, and the add-on refuses to start when both are set."
soc_entity:
name: "Hardware · Battery charge level entity (%)"
description: "The sensor that reports the pack's state of charge in percent. Use the ESP32's own reading, not a figure computed somewhere else. The maintenance cycle and every charge-level floor read this."
batt_entity:
name: "Hardware · Battery power entity (W)"
description: "The sensor that reports this inverter's own battery power, positive while discharging. On this installation that is holding register 0x0518, read by the ESP32. The sign watchdog and the circulating-power alarm both grade the inverter against this reading."
batt_invert:
name: "Hardware · Battery power sign is reversed"
description: "Only switch this on if your battery power sensor reports discharging as a negative number. The add-on expects positive to mean discharging."
inverters:
name: "Hardware · Inverter list (leave empty if you have one inverter)"
description: "Leave this empty unless the site really has more than one inverter. EMPTY DOES NOT MEAN 'not configured yet': it means the four entity settings above, together with the inverter rating and the battery cut-out under Limits, describe the one inverter you have. That is what every existing installation reads, and nobody has to touch anything. Filling this in REPLACES those settings instead of extending them, and nothing is inherited: each entry has to name its own actuator, its own rating and its own battery cut-out, so that no inverter is ever judged against another unit's numbers. The flat setpoint entity above must then be left empty."
fields:
name:
name: "Name"
description: "A short identifier for this inverter, for example inverter-a. It gives this unit its own namespace for its safety latch, heartbeat and write bookkeeping in the add-on's state file, so two units may not share one."
setpoint_entity:
name: "Setpoint entity"
description: "This inverter's own ESPHome number.*_goodwe_setpoint_w. Two entries may not name the same one - two writers on one actuator is refused at startup."
max_w:
name: "Inverter rating (W)"
description: "The supervised ceiling on what may be written to THIS inverter; the site's ceiling is the sum over the list. Required of every entry: an entry without one would have to borrow a rating, and judging one inverter against another unit's numbers is exactly the fault this per-entry list exists to remove."
bms_soc_floor:
name: "Battery cut-out level (%)"
description: "The percent at which THIS pack's own battery management system cuts out. Read it off the pack that is actually installed (register 0x0560) before that pack is ever commanded; do not copy another unit's figure. Required of every entry, deliberately: an optional one would be a defaulted one, and one default for two batteries of different models protects the shallower pack with the deeper pack's number."
soc_entity:
name: "Battery charge level entity (%) (optional)"
description: "This pack's own state of charge. Leave it empty if this unit reports none - that is what it means, and it never falls back to another unit's sensor."
batt_entity:
name: "Battery power entity (W) (optional)"
description: "This unit's own battery power, positive while discharging. Leave it empty if this unit reports none; nothing is inherited from another entry."
batt_invert:
name: "Battery power sign is reversed (optional)"
description: "Only for this entry: switch it on if this unit's battery power sensor reports discharging as a negative number."
capacity_kwh:
name: "Usable battery capacity (kWh) (optional)"
description: "THIS pack's usable capacity in kilowatt-hours, from its datasheet or its label. It is read for one purpose: dividing the site's target between the inverters by how much ENERGY each pack has left rather than by how many watts it is rated for. The two packs at the reference site are 5000 W with 15.36 kWh and 4600 W with 20.48 kWh, so those two ways of dividing the work hand it to different batteries, and the energy one is the question worth asking. Optional: leave it empty and the add-on has no opinion, dividing the target evenly exactly as it did before. State it on EVERY inverter or on none of them - a pack measured in kWh next to one that is not is not a comparison, and the add-on refuses to start rather than ignore half of what you filled in."
estop_fitted:
name: "Hardware · RS485 emergency stop is fitted"
description: "Whether the RS485 emergency stop is physically installed. It only drives the warning banner on the status page; it changes no control behaviour."
pv_entity:
name: "Hardware · PV production entity (W)"
description: "Optional, and MEASUREMENT ONLY - it changes no control behaviour whatsoever. Point it at your solar inverter's own power sensor (any brand Home Assistant reads; it does not have to be on the RS485 bus) and the add-on records production beside the grid and battery figures, so a day of unstored surplus can be told apart from a day with no sun. POSITIVE MUST MEAN PRODUCING - if yours reads negative while producing, list it under 'sign is reversed' below. The unit is read from the entity itself - W, kW and the rest of Home Assistant's power units - so a sensor with no unit is refused rather than guessed at, and the status page says so. Leave it empty and nothing is read, nothing is published and nothing is shown."
pv_entities:
name: "Hardware · PV production entities, one per inverter (W)"
description: "Optional, and MEASUREMENT ONLY - it changes no control behaviour whatsoever. Use this instead of the single entity above when your roof has SEVERAL solar inverters: add one row per inverter, pointing at each one's own power sensor, and the add-on records the SITE total. Each entity's own unit is read, so a kW inverter beside a W one adds up correctly. ⚠️ SETTING THIS IGNORES THE SINGLE ENTITY ABOVE - clear that one when you fill this in, or you will see a caution on the status page saying so. ⚠️ AND IF ANY ONE OF THESE STOPS REPORTING THERE IS NO SITE TOTAL: the sensor goes to 'unknown' and the history records a gap, rather than publishing the sum of the ones that did answer. Two inverters out of three add up to a smaller number that looks exactly like a real one, and a week later that reads as 'there was less sun than there was' - which is the one conclusion this recording exists to test. The status page names which entity is missing, why, and what the others reported. Leave it empty and nothing is read, nothing is published and nothing is shown."
pv_invert_entities:
name: "Hardware · PV entities whose sign is reversed"
description: "Optional, MEASUREMENT ONLY. Some sensors - typically a kWh meter or a power clamp in the PV circuit - read NEGATIVE while producing and a few watts POSITIVE at night. Add each such entity here, spelled exactly as it is above, and its sign is flipped before it is added up; leave the others out. The status page marks every flipped entity. History recorded before you set this keeps the old sign."
meter_source:
name: "Meter · Where the meter reading comes from"
description: "'off' keeps the single Home Assistant entity below, which is what an existing installation runs on until you choose otherwise. ha_dsmr subscribes to the DSMR integration; mqtt_p1 reads an MQTT topic; ha_signed reads one signed entity, which is what a HomeWizard P1 publishes; homewizard_local polls the meter's own local API and skips Home Assistant entirely. ⚠️ Only homewizard_local can tell 'the meter has not answered' apart from 'the value has not changed', so it is the only source on which the frozen-meter alarm means anything."
meter_entity:
name: "Meter · Grid power entity (W)"
description: "The net grid power sensor, used when the meter source is 'off'. POSITIVE MUST MEAN DRAWING FROM THE GRID. Get this the wrong way round and the loop drives the battery in the wrong direction; use the sign switch below rather than a template sensor."
meter_invert:
name: "Meter · Grid power sign is reversed"
description: "Switch this on if your grid sensor reports drawing from the grid as a negative number."
meter_phases:
name: "Meter · Number of phases (1 or 3)"
description: "Must match your connection. A telegram whose phase count disagrees is rejected as it arrives and logged, so a wrong value shows up straight away as 'no telegrams accepted' rather than as a quietly wrong number. The range accepts 2, but that is not a real Belgian connection."
p1_host:
name: "Meter · HomeWizard P1 address"
description: "For meter source homewizard_local only: the meter's own address on your network, as host or host:port, for example 192.168.2.250."
meter_poll_s:
name: "Meter · Seconds between meter polls"
description: "For meter source homewizard_local only. 5 s is the meter's own update rate, so there is nothing to gain below it. It must stay well under the staleness limit below - the reading is never fresher than this interval - and the add-on refuses to start if it is at or above that limit."
meter_max_age_s:
name: "Meter · A reading counts as stale after (s)"
description: "Beyond this the grid figure counts as missing. On its own it does not command 0 W: the 'inputs missing' timer under Advanced starts only after this one has expired, and the two stack. 30 s is six polls of headroom at the default poll interval."
meter_mqtt_topic:
name: "Meter · MQTT topic"
description: "For meter source mqtt_p1 only: the topic the P1 readings are published on."
p1_import_entity:
name: "Meter · Import register entity (W)"
description: "The UNSIGNED consumption register. Do not point this at a signed template sensor: the add-on works out net power itself as import minus export, so the sign convention lives in tested code rather than in unreviewed YAML."
p1_export_entity:
name: "Meter · Export register entity (W)"
description: "The UNSIGNED injection register, the counterpart of the import register above. Same rule: no signed template sensor."
p1_net_entity:
name: "Meter · Signed net power entity (W)"
description: "For meter source ha_signed only. ONE signed sensor: positive is drawn from the grid, negative is fed back into it. Do not split it into two template sensors - the add-on does that split itself, so that it is tested."
p1_phase_import_entities:
name: "Meter · Per-phase import entities (L1, L2, L3)"
description: "Optional, in L1..L3 order. Needed for the capacity-tariff quarter-hour peak on a three-phase connection. The number of entries must equal the number of phases above."
p1_phase_export_entities:
name: "Meter · Per-phase export entities (L1, L2, L3)"
description: "Optional, in L1..L3 order, alongside the per-phase import entities above. The number of entries must equal the number of phases."
p1_phase_net_entities:
name: "Meter · Per-phase signed net entities (L1, L2, L3)"
description: "For meter source ha_signed only. Optional, in L1..L3 order, each signed the same way as the net entity above. Same job as the per-phase import and export entities: the capacity-tariff quarter-hour peak on a three-phase connection. The number of entries must equal the number of phases."
max_w:
name: "Limits · Inverter rating (W)"
description: "THIS IS YOUR NUMBER, not a derived one: the hard ceiling on what may ever be commanded, in watts. Set it to what your inverter is actually rated for, start low and raise it once the site has been commissioned. It is not read at all when the inverter list is filled in - each entry then carries its own, and the site ceiling is their sum. Several safety thresholds must stay below it, and the add-on refuses to start if one does not."
bms_soc_floor:
name: "Limits · Battery cut-out level (%)"
description: "MEASURED, not chosen: the percent at which the pack's OWN battery management system stops discharging, whatever this add-on is set to. Register 0x0560 reads 10 on the reference GW5000S-BP. Read it off the pack you actually have rather than copying this figure. It is here so the add-on can refuse a capacity-guard floor at or below it: such a floor could never bind, the BMS would win first, and the status page would report an energy backstop that does not exist. Not read when the inverter list is filled in - each entry then states its own pack's cut-out."
peak_cap_w:
name: "Limits · Capacity-tariff target (W)"
description: "THIS IS YOUR NUMBER: the quarter-hour average demand the peak guard tries to stay under. Take it from your grid contract - in Belgium it is the capacity-tariff peak your distribution charge is billed on."
peak_forecast_entity:
name: "Limits · Quarter-hour demand forecast entity (W)"
description: "Optional. A forecast of the current billing quarter's average demand. Leave it empty and there is no capacity cap at all."
peak_soc_floor:
name: "Limits · Peak guard will not discharge below (%)"
description: "DERIVED, not picked (SAFETY-24): the reference pack holds 13.8 kWh usable and the worst modelled peak-shaving day asks for 878 Wh, which is 6.4 %, so 20 % sits ten points above the pack's own cut-out and still leaves the guard about 1.6 of its worst observed days of room. ⚠️ IT BOUNDS THE PEAK GUARD ONLY. It is not a reserve for the whole pack: ordinary self-consumption discharges straight past it and goes on down to the battery cut-out, and raising this number does not change that by a tenth of a percent. It must stay strictly above the battery cut-out or the add-on refuses to start. Do not change it without re-deriving it."
price_provider:
name: "Tariff · Dynamic price source"
description: "Where day-ahead or real-time prices come from. 'off' is what ships, and means this site runs on the static tariff below with no trading. ⚠️ SWITCHING THIS ON IS WHAT STARTS THE PRICE FETCH - not the trading switch further down. With a source selected the add-on fetches the feed every half hour, checks it, records the day and shows what it holds on the Price history row, whether or not price trading is armed. On its own it still moves no energy: trading is the separate switch, and the cheap window the monthly maintenance cycle uses comes from the fixed or day/night tariff below. It may not be combined with the two legacy Home Assistant price entities further down: two price sources on one site, one of which silently wins, is refused at startup rather than left looking armed. ⚠️ THREE IDS IN THIS LIST ARE WITHDRAWN AND WILL NOT START: engie_dynamic, totalenergies_dynamic and eneco_eddy. Their endpoints do not exist and never did, so those plugins never once fetched a price - a site set to one of them has silently been running on the fixed or day/night tariff below, or on nothing, since the day it was set. They are still offered here only so that such a site gets that explanation at startup instead of an unreadable schema error. Choose generic_dayahead for the wholesale curve with a flat markup, custom_formula to enter your own contract's B x index + A coefficients off your tariff card, manual_csv for a file you write yourself, or off."
price_markup_eur_kwh:
name: "Tariff · Supplier markup (EUR/kWh)"
description: "Your supplier's margin. The add-on adds it ONLY when the chosen price source does not already include it - under manual_csv, whose figures are all-in, it is ignored, and logged as ignored, never applied twice."
price_taxes_eur_kwh:
name: "Tariff · Distribution, levies and VAT (EUR/kWh)"
description: "Everything on your bill that is not the energy itself - distribution, levies, excise and VAT - per kWh, added under the same rule as the supplier markup: only when the chosen price source does not already carry them. ⚠️ THIS NUMBER IS NOT A PREFERENCE AND IT IS NOT YOUR INVERTER'S. It ships at 0.11736, DERIVED in TARIFF-18 from the Eneco residential card for Flanders of September 2026 including 6% VAT: Fluvius distribution for Antwerpen 5,35 plus bijzondere accijns 4,876 plus bijdrage groene stroom en WKK 1,51 c/kWh. The energiebijdrage is 0 since 1 August 2026 - it was merged into the excise, so a figure copied from an older guide would count it twice. ⚠️ CHECK IT AGAINST YOUR OWN DSO. Only the distribution row moves: across the eight Fluvius DSOs it runs from 5,28 c/kWh in Midden-Vlaanderen to 6,70 in West-Vlaanderen, so the Flemish total runs from about 0.117 to 0.131. In Wallonia or Brussels the distribution tariff has a separate day and night rate and does not belong in this field at all - use the levies-by-time-of-day option below instead. ⚠️ CHANGING IT MOVES NO TRADING DECISION: the same amount is added to every hour, so it cancels out of both the cheapest hour and the spread. What it does move is every price you are shown, and the rule that refuses to discharge into an hour whose all-in price is below zero."
export_price_eur_kwh:
name: "Tariff · Injection price (EUR/kWh)"
description: "What you are paid for feeding a kWh back into the grid, all in. One number rather than a series: no supplier here publishes a dynamic injection curve. In Belgium it is often close to zero, which on its own strongly favours using your own production over exporting it. It may be negative - at midday in summer you can be paying to export."
static_profile:
name: "Tariff · Fixed or day/night tariff (one line of JSON)"
description: "Your fixed or day/night contract, written as a single line of JSON. RECOMMENDED EVEN ON A DYNAMIC CONTRACT: this is what the add-on falls back to when the price feed dies, and with it empty a dead feed leaves the site with no tariff at all. The periods must cover every day type exactly once, with no gap and no overlap - a gap is refused at startup rather than filled in, because an invented price is one a strategy would trade on. A fully fixed tariff is one period covering 00:00-24:00 on all days. Prices are ALL IN; the markup and levies above are not added to them. Note that a window written 22:00-07:00 for mon-fri does NOT cover Saturday morning, so a weekend row is required rather than decorative."
price_taxes_profile:
name: "Tariff · Levies and VAT by time of day (one line of JSON)"
description: "Leave this empty unless your network tariff really does charge a different day and night rate - in Flanders it does not, Fluvius distribution is one rate, and the flat figure above is correct. In Wallonia and Brussels it does: ORES charges 13,27 c/kWh by day against 7,39 at night, AIESH 15,17 against 8,21, Sibelga 9,39 against 7,10. Written as a single line of JSON in exactly the same shape as the fixed or day/night tariff above, with the same rule that the periods must cover every day type once with no gap and no overlap. ⚠️ THE NUMBERS HERE ARE THE LEVIES ALONE, NOT A FULL PRICE - the add-on adds them to whatever your price source publishes, exactly as it adds the flat figure. Why it matters: a flat figure is the same in every hour, so it moves every hour equally and cannot change which hour is cheapest - and a night network rate is cheap in the same hours the market is cheap, so flattening it makes the add-on think the day is flatter than it is and turn down battery cycles that would have paid for themselves. Set this or the flat figure above, not both: the add-on refuses to start if the two disagree."
price_formula:
name: "Tariff · Your own tariff formula (one line of JSON)"
description: "For price source custom_formula only: your own contract's two coefficients, written as a single line of JSON. Your supplier's tariff card prints the formula as B x index + A - those two numbers exist only on your card, there is no public index of them anywhere, and you are the only person who can read them. Type what the card prints, IN THE UNITS THE CARD PRINTS: every unit conversion and the VAT step are the add-on's job, because those are the two places a human silently loses a factor of 10, 100 or 1.06. Example: {\"index\":\"epex_be\",\"resolution\":\"hourly\",\"factor\":0.102,\"offset\":1.00,\"units\":\"c_eur_per_kwh\",\"vat_pct\":6,\"card\":{\"month\":\"2026-09\",\"index_eur_per_mwh\":133.9905,\"expect_incl_vat\":15.55}}. ⚠️ THE card BLOCK IS REQUIRED AND IT IS WHAT MAKES THIS SAFE: your card also prints the reference index it assumed and the price that comes out, so the add-on recomputes that price from your numbers and REFUSES TO START if it does not come out, telling you by how much. That catches a wrong unit, VAT left out or counted twice, a transposed digit, and the expensive one - network charges folded into the offset, which the add-on would then bill you for a second time. ⚠️ AND ITS LIMIT, IN THE SAME BREATH: it checks your coefficients against your card, not your card against reality, so two numbers copied off the wrong product agree with each other and pass. Fixed numbers only - no expression of any kind is evaluated, and an unrecognised field is refused rather than ignored."
price_export_formula:
name: "Tariff · Your own INJECTION formula (one line of JSON)"
description: "Optional, and only if your supplier pays you a price that moves with the market. Your tariff card has a SECOND formula for what you are paid for the electricity you export, and it is not the first one with a minus in front: Eneco prints `0,1 x BELPEX-H - 1,188` c/kWh for injection against `0,102 x ...` for consumption, and Aspiravi `0,07 x Belpex - 2`. Written in exactly the same shape as your own tariff formula above. ⚠️ INJECTION IS EXEMPT FROM VAT in Belgium while consumption is at 6%, so vat_pct here is normally 0 - that is the one field people copy across from the other formula and get wrong. ⚠️ THE PRICE THIS GIVES CAN BE NEGATIVE, and that is not an error: Eneco pays below zero whenever BELPEX-H is under 11,88 EUR/MWh, which is the middle of a sunny day - you can be charged to export. The add-on accepts that rather than hiding it. The card block is OPTIONAL here and required above, because Eneco prints the injection formula with NO example price beside it and there would be nothing to check your numbers against; if your card does print one, fill it in and the add-on will refuse to start unless your numbers reproduce it. ⚠️ WHAT THIS DOES NOT DO: no part of the add-on trades on an injection price today - it charges cheap to avoid buying dear, and both sides of that comparison are consumption prices. This is what you are shown, and what a future export strategy would read. Leave it empty and the flat injection price above is used, which is what every installation does now."
price_csv_path:
name: "Tariff · Price CSV file"
description: "For price source manual_csv only: where in /share the add-on reads your own price file from."
price_feed_url:
name: "Tariff · Price feed URL override"
description: "Leave empty to use the chosen source's own feed. Only a host that source itself declares is accepted, so this cannot be pointed anywhere. WHAT YOU TYPE IS SENT EXACTLY AS WRITTEN: the add-on adds nothing to it, not even the date range it normally asks its own feed for, so an override gets whatever horizon that URL returns - often a single day, with the rest of the plan carried over from yesterday and excluded from price arbitrage. A warning in the log says so on every price refresh. Clear this option to get the full horizon back."
price_horizon_h:
name: "Tariff · How far ahead to fetch prices (hours)"
description: "How many hours of prices to ask the source for."
price_timeout_s:
name: "Tariff · Price request timeout (s)"
description: "How long a single request to the price source may take before it is given up on."
price_now_entity:
name: "Tariff · Current price entity (older price path)"
description: "The older way of getting a price, kept because retiring it would take the maintenance cycle's only price signal away from a live installation. The add-on reads this and the average below and derives exactly one thing from them - whether now is cheaper than average - which only the maintenance cycle's cheap-window charging uses. It may not be combined with a dynamic price source."
price_avg_entity:
name: "Tariff · Average price entity (older price path)"
description: "The average the current price is compared against. Only meaningful together with the current-price entity above, and like it, may not be combined with a dynamic price source."
arbitrage_enabled:
name: "Tariff · Trade on the price spread"
description: "Charge in the cheapest published hour and discharge in the dearest, but only when the spread covers what the round trip costs. OFF in the shipped configuration, deliberately: this is the first strategy in the add-on that moves energy against the meter on purpose, so it is armed on purpose or not at all. ⚠️ LEAVING IT OFF DOES NOT TURN THE PRICE FEED OFF. A price source selected above is fetched, checked and recorded either way; this switch decides only whether the add-on ACTS on those prices. It needs both a price source and a P1 meter, and the add-on refuses the combinations that cannot work rather than letting them look armed."
cycle_cost_threshold_eur:
name: "Tariff · Cost of one full charge/discharge cycle (EUR/kWh)"
description: "What one full round trip costs per kWh: wear on the pack plus conversion losses. A price spread smaller than this loses money and battery life, so it is not traded. ⚠️ THIS ONE IS NOT DERIVED FROM A MEASUREMENT. 0.10 is a product decision and it is still an open question with the owner (OPT-08). At this value a fixed day/night site does not trade at all - the realistic Belgian day/night spread is about 0.08 EUR/kWh - and that is the correct verdict at this number, not a fault."
arbitrage_soc_floor:
name: "Tariff · Trading may not discharge below (%)"
description: "The reserve price trading may not spend. Deliberately not the same key as the maintenance floor: pointing a trading strategy at the monthly balancing cycle's numbers would couple two unrelated policies through one setting."
arbitrage_soc_ceiling:
name: "Tariff · Trading may not charge above (%)"
description: "The headroom price trading may not fill. The counterpart of the trading floor above, and kept separate from the maintenance target for the same reason."
maintenance_enabled:
name: "Maintenance · Run the monthly battery cycle"
description: "A deliberate deep discharge followed by a full recharge and a hold, so the battery management system can recalibrate its charge estimate and balance the cells. Off by default."
maintenance_interval_days:
name: "Maintenance · Minimum days between cycles"
description: "The shortest gap between two maintenance cycles."
maintenance_start_hour:
name: "Maintenance · Hour of day a due cycle starts"
description: "Local hour, 0 to 23, at which a cycle that has become due begins."
maintenance_discharge_w:
name: "Maintenance · Discharge rate (W)"
description: "How fast the cycle drains the pack; the surplus is exported. Above the inverter rating it is CLAMPED to the rating rather than refused - the cycle still completes, just more slowly, and the status page says so. It ships at 2000 to match the shipped rating; raise the rating first, then this."
maintenance_charge_w:
name: "Maintenance · Recharge rate (W)"
description: "⚠️ MUST STAY AT OR BELOW the inverter rating, and the add-on refuses to start otherwise. Above it, the cheap-window charge shaping asks for more than the supervised limit allows, the arbiter resolves that contradiction to 0 W, and maintenance would silently never charge in a cheap window on a default installation. It is also capped again by whatever headroom the peak guard leaves."
maintenance_soc_floor:
name: "Maintenance · Discharge down to (%)"
description: "The depth the monthly recalibration deliberately goes to, once a month, on purpose. ⚠️ THIS IS NOT THE PEAK GUARD'S FLOOR: that one is the depth a money-saving discharge may never reach on any day. The right values genuinely differ - 11 here against 20 there - which is why they are two separate settings and must not be merged."
maintenance_soc_target:
name: "Maintenance · Recharge up to (%)"
description: "The level the recharge phase aims for before the hold begins."
maintenance_hold_min:
name: "Maintenance · Hold at full for (minutes)"
description: "How long to sit at the target so the battery management system can finish balancing the cells."
sign_disagree_w:
name: "Safety · Sign watchdog threshold (W) — measured, do not change"
description: "MEASURED, NOT CHOSEN (SAFETY-02). Both the setpoint being emitted and the grid reading must exceed this before their opposite signs count as a disagreement at all. On the captured healthy day (2026-08-23) sign agreement over the gated samples is 93.4 %; on the captured fault day (2026-08-20) the clusters run 0.0-10.5 % with opposed runs up to 1752 s. There is no reason to move this without a new capture that says so. It must stay below the inverter rating or the watchdog can never fire, and the add-on refuses that configuration."
sign_disagree_s:
name: "Safety · Sign watchdog hold (s) — measured, do not change"
description: "MEASURED, NOT CHOSEN (SAFETY-02). How long the setpoint and the meter must stay opposed, continuously, before the add-on commands 0 W and latches until an operator starts control again. 180 s sits in the middle of a very wide measured gap: the longest legitimate opposed run on the healthy day is 30 s, while the fault day still trips 13 times at 300 s. Do not change it without a new capture."
unit_sign_disagree_w:
name: "Safety · Per-inverter sign threshold (W) — derived, do not change"
description: "TWO OR MORE INVERTERS ONLY; with one inverter this setting does nothing at all. DERIVED FROM 1890 CLOSED-LOOP TEST RUNS on the two-master rig (SAFETY-30), in which nothing was faulty, swept across the whole range this add-on accepts for loop gain and slew rate. 250 W is exactly half the saturation threshold, so the smallest divergence this can see is precisely the gap at which the control law itself already says the inverter is not following. Do not change it without re-deriving it. It must stay below the inverter rating or it can never fire."
unit_sign_disagree_s:
name: "Safety · Per-inverter sign hold (s) — derived, do not change"
description: "TWO OR MORE INVERTERS ONLY. DERIVED FROM 1890 CLOSED-LOOP TEST RUNS (SAFETY-30): 85 s is 8.5 times the worst legitimate opposition those runs produce (10.0 s), 2.8 times the firmware's own 30 s link veto, and under half the 180 s the site-wide check takes. Do not change it without re-deriving it."
site_sign_disagree_w:
name: "Safety · Site-wide sign threshold (W) — measured, do not change"
description: "TWO OR MORE INVERTERS ONLY. The same 300 W as the single-inverter threshold, CARRIED ACROSS DELIBERATELY (SAFETY-30): the argument behind it does not depend on how many inverters there are - near zero the sign is noise, the deadband is 15 W, and there is one meter whatever is behind it. Do not change it without a capture that says so."
site_sign_disagree_s:
name: "Safety · Site-wide sign hold (s) — derived, do not change"
description: "TWO OR MORE INVERTERS ONLY. DERIVED FROM 1890 CLOSED-LOOP TEST RUNS (SAFETY-30), and deliberately NOT carried across from the single-inverter 180 s. On those runs the worst legitimate opposition at 300 W is 110 s with one inverter and 215 s with two, because the command has to travel the whole site rail at a slew rate that is not the site's - so carrying 180 s across would have shipped a false trip reachable at the lowest gain and slew with an ordinary 2.2 kW load reversal. 325 s is 1.51 times that, still inside the 900 s billing quarter, and still inside every episode of the captured fault day. Do not change it without re-deriving it."
meter_freeze_s:
name: "Safety · Frozen-meter alarm after (s) — measured, do not change"
description: "MEASURED, NOT CHOSEN (SAFETY-18). How long the meter may keep answering with an UNCHANGED reading, while the command stands at the rail, before the add-on raises an alarm. Over 2399 s of this house at its settled operating point - 1194 polls, 735 of them repeating the previous reading - the longest run without a distinct reading is 15.4 s; 300 s is 19.5 times that and still inside the 900 s billing quarter. ALARM ONLY: it does not command 0 W and does not latch. ⚠️ Only the homewizard_local meter source can see this at all; on every other source the status page says NOT COVERED rather than armed. Do not change it without re-deriving it."
circulation_w:
name: "Safety · Circulating-power threshold (W) — measured, do not change"
description: "TWO OR MORE INVERTERS ONLY; with one inverter the quantity is identically zero. Two inverters pushing against each other net out to zero at the meter and are invisible to every other guard in this add-on. MEASURED ON 924 CLOSED-LOOP TEST RUNS in which nothing was faulty (SAFETY-31): the worst legitimate opposition collapses from 505 s at a 100 W threshold to 5 s at 400 W, and 400 W is the sharp knee this add-on will not let you go below - under it, ordinary operation holds the sensor over the threshold for minutes and nothing shorter than the billing quarter could tell that from a fault. 700 W is 1.75 times the knee, and the extra margin is there because the second inverter's ramp and lag are still copied from the first one rather than measured. Do not change it without re-deriving it."
circulation_hold_s:
name: "Safety · Circulating-power hold (s) — derived, do not change"
description: "TWO OR MORE INVERTERS ONLY. DERIVED (SAFETY-31): 75 s is fifteen control cycles - 15 times the worst legitimate episode the rig can produce, 2.5 times the firmware's own 30 s link veto, and twelve times inside the 900 s billing quarter. It is deliberately not a round 60 or 120, which would be a guess wearing a measurement's clothes. Do not change it without re-deriving it."
delivery_hold_s:
name: "Safety · Not-delivering report after (s) — derived, do not change"
description: "TWO OR MORE INVERTERS ONLY; with one inverter this check cannot fire at all, and that is deliberate rather than a limitation. How long ONE inverter may stand at a discharge share it is not producing - short by more than the saturation threshold, with nothing this add-on can read to explain it - while at least one sibling is NOT in that state, before it is named. REPORTS ONLY (SAFETY-42): nothing is commanded differently, the loop is untouched, and the site goes on running short by that unit's share until you look. DERIVED FROM 2640 CLOSED-LOOP TEST RUNS in which nothing was faulty (SAFETY-42, plus a one-inverter arm as the control, which reports nothing at any threshold): the worst legitimate episode those runs produce is 35.0 s, and the ceiling is the 900 s quarter that bills the capacity tariff. 185 s is 5.29 times that. ⚠️ The schema lets you set this as low as 30 s, which is BELOW that measured 35.0 s - at 30 s you should expect reports on legitimate saturation. The second inverter in those tests is a COPY OF THE FIRST, because the second inverter does not exist yet: what a unit four times slower would produce (75.0 s) is a sensitivity study on that idea, not a measurement of any real second inverter. Do not change it without re-deriving it - and it can be re-derived now: admin/goodwe sim/delivery_window.py --campaign --blag (TEST-21). A pack at or below its own bms_soc_floor is never reported: an empty pack and a wedged one are identical watt for watt, and that setting is the only thing that tells them apart - so if this fires on a pack you believe is empty, that setting does not describe your battery."
shadow_mode:
name: "Safety · Shadow mode — run every decision, command nothing"
description: "Runs the whole decision path — strategies, arbiter, clamps and guards — and sends NOTHING to the inverter. Every inverter is held at 0 W, refreshed on the ordinary heartbeat, and the status page says plainly that the battery is not being controlled; the decision it WOULD have commanded, and why, is on the status page and in the action log. This is how you watch a site for a day before letting it trade. 'auto' (the shipped value) means shadow mode while control is stopped and ordinary control once you press Start — so a NEW install observes before it ever commands anything, and an install that is already controlling is not changed by one watt. 'on' means shadow mode always, whatever the Start / stop button says: that is the setting to pick when you want the loop and the strategies running on a live site with nothing reaching the battery. 'off' is ordinary control. ⚠️ While this is on the battery is NOT being regulated — the grid is not held at zero, no arbitrage trade is executed and no capacity peak is shaved. ⚠️ A failsafe latch that was already up stays up: shadow mode does not clear it, and the banner names it."
auto_start:
name: "Advanced · Start controlling automatically on boot"
description: "Off by default. Leave it off until the site has been commissioned: with it off, somebody has to press Start after every restart of the add-on, which is what you want while you are still checking signs and entities."
gain:
name: "Advanced · Loop gain"
description: "How much of the remaining error the loop corrects each cycle. MEASURED ON REAL HARDWARE and already at the limit - do not raise it. Lower is slower and safer."
slew_w:
name: "Advanced · Largest change per cycle (W)"
description: "How far the setpoint may move in one control cycle. ⚠️ 0 MEANS FOLLOW THE INVERTER RATING and is the recommended setting: the limit becomes about a ninth of the rating, so the loop takes the plant's own MEASURED settling time to cross its whole output range and the number cannot be left behind when the rating changes. DERIVED (SAFETY-39) from an ~18 s measured step response against a 2 s meter tick. A fixed number is accepted and is never silently reduced, but a number faster than the rating allows is refused at startup - at 1000 W against a 5000 W rating this loop drove the meter from 3.4 kW of export to 2.8 kW of import on 2026-09-05. Lower is always accepted."
deadband_w:
name: "Advanced · Deadband (W)"
description: "Errors smaller than this are ignored. ⚠️ The deadband is a one-way ratchet: any resting point inside it holds forever, and the meter's import register counts every positive watt with no export to cancel it - which is exactly why the resting point below is slightly negative."
target_grid_w:
name: "Advanced · Resting point at the meter (W)"
description: "What the meter should sit at when nothing is happening; negative means a slight export. -10 W is deliberate: resting at 0 W leaks about half the deadband in billed import all day - roughly 0.2 to 0.35 kWh at a 15 W deadband - and biasing the rest point below zero moves that leak into the export register, which is not billed. It costs about this many watts of given-away export, so keep it small."
step_w:
name: "Advanced · Setpoint quantisation (W)"
description: "The setpoint is rounded to a multiple of this before it is written, so the inverter is not handed a new number for every watt of noise."
saturation_w:
name: "Advanced · Saturation threshold (W)"
description: "The gap between what was commanded and what the inverter delivers that counts as 'this inverter is at a limit'. ⚠️ The per-inverter sign threshold under Safety is derived as exactly half of this, so moving this moves that measurement's argument with it."
saturation_cycles:
name: "Advanced · Saturated cycles before freezing (count)"
description: "How many consecutive saturated cycles before the loop stops winding up. ⚠️ Do not set this to 1: a single noisy cycle would then freeze the loop."
integrator_max_w:
name: "Advanced · Integrator bound (W, 0 means the same as the rating)"
description: "Caps how much stale error can be waiting to unwind when the sign flips. MEASURED on the closed-loop simulator with a 4000 W load dropped to zero: at a bound equal to the rating the command is 1000 W two cycles later, at 1.5 times the rating it is 1800 W. ⚠️ Do not raise it above the inverter rating - the output clamp already bounds what reaches the wire, so extra headroom buys nothing but wrong-direction watts after every saturation event. Lowering it below the rating is the useful direction, and the only reason this is a separate setting."
heartbeat_s:
name: "Advanced · Setpoint refresh interval (s)"
description: "How often the setpoint is rewritten even when it has not changed. It must stay well under the firmware's own watchdog, which vetoes a link that has been quiet for 30 s."
stale_input_s:
name: "Advanced · Command 0 W after inputs missing for (s)"
description: "How long the inputs may be missing before the add-on commands 0 W. With a P1 meter this clock starts only AFTER the meter staleness limit has already expired, so the two stack: the total is longer than this number on its own."
cycle_floor_s:
name: "Advanced · Longest gap between control cycles (s)"
description: "A deadline on the gap between cycles, reset by every cycle. On a healthy meter it never elapses and changes nothing. Raise it only if your meter is slower than about 10 s, and keep it under the meter staleness limit - past that there is no reading left to evaluate anyway."
log_level:
name: "Advanced · Log level"
description: "How much detail the add-on writes to its log. 'info' is the shipped setting; 'debug' and 'trace' are for diagnosing a problem and are noisy."