Option defaults for the maintenance cycle were declared in three places that
could disagree, and MAINT-04 proved they already did. config.yaml shipped
`maintenance_charge_w: 2000`; main.py carried TWO `opts.get(..., 2500)`
fallbacks; MaintConfig's dataclass carried a third `2500.0`. So an options dict
with the key ABSENT was ACCEPTED by validate.py's rule 6 - which read 2000 -
and then built by main.py at 2500, against a 2000 W ceiling:

    options dict with maintenance_charge_w ABSENT, max_w=2000
      validate_startup_config  ->  []  (accepted, no problems)
      MaintConfig().charge_w   ->  2500.0
      arbiter.resolve()        ->  0.0 W, contradiction=True

That is the bug rule 6 exists to refuse, passing rule 6. It is unreachable on a
Supervisor install, which always supplies every key from config.yaml, and fully
reachable from sim/inject.py and from the test suite - which is where anyone
debugging maintenance actually works.

MAINT-04 shipped a TRIPWIRE and said so: test_validate.py pinned all three
literals and asserted the consequence through the real arbiter, so the
divergence could not silently widen or be half-closed. Its PASSING CONDITION
WAS THE BUG. Both it and validate.py's comment said to delete each other when
the divergence was closed. It is closed, so both are deleted.

THE DIVERGENCE WAS WIDER THAN ONE KEY. `maintenance_discharge_w` had the
identical three-way split (config.yaml 2000, MaintConfig 2500) and the card
named only the charge side. Closing one and leaving its twin would have
satisfied the numbers and left three sources of truth one line down, which is
the state that produced the bug. Both are closed, and so is the whole family:
all eight `maintenance_*` keys go through the same mechanism.

WHAT THE SINGLE SOURCE IS. config.yaml's `options:` block - it is what the
Supervisor reads and what the operator edits, so it wins by definition. There
is now exactly one in-code copy, `maintenance.MAINT_OPTION_DEFAULTS`, which is
TARIFF-02's `PRICE_OPTION_DEFAULTS` and SAFETY-24's `PEAK_OPTION_DEFAULTS`
pattern applied to the family that named the card - validate.py's rule 8 comment
already called that "CFG-03 read as a rule rather than as a complaint", so this
makes the rule hold where it was first broken rather than inventing a fourth
mechanism for one option family.

A MIRROR RATHER THAN A RUNTIME READ, and the reason is mechanical: the
Dockerfile copies `app/` and `run.sh` into the image and NOT config.yaml. The
running add-on cannot open the file it is configured by, so there is nothing to
read at 03:00 on a client's Pi, and a YAML-subset parser that could fail at
import is a new way for the add-on not to start. What makes the copy safe is
that test_maintenance.py pins every entry by READING the shipped file - drift is
a CI failure, not a comment.

EVERY OTHER SITE NOW DERIVES FROM IT OR HAS CEASED TO EXIST:

  * MaintConfig's eight dataclass defaults are indexed out of the mirror. No
    numeric literal survives in the class that held the third opinion.
  * `MaintConfig.from_options()` is the ONLY place in the add-on that reads a
    `maintenance_*` option. main.py's eight inline `opts.get(key, <literal>)`
    calls are gone: moving the read next to the mirror means the fallback cannot
    be anything but the mirror, because there is no literal in sight of it to
    disagree with. It uses `key in opts` rather than truthiness, so a shipped
    `false` or `0` is honoured instead of being quietly replaced by the default
    - this card's own bug in a different costume.
  * main.py's SECOND fallback site - the cheap-window charge floor at the
    P_MAINT_SHAPE claim - reads `self.maint.cfg.charge_w` instead of re-opening
    the options dict with its own literal. The Controller had already parsed
    this once in __init__; asking the object that owns it cannot drift from it,
    and the rate the shaping asks for can no longer be a different number from
    the rate the state machine drains at on the same install.
  * validate.py's rule 6 and its `maintenance_discharge_w` warning take their
    fallbacks from the mirror.

WHERE THE RANGE LIVES, STATED AND CHECKED. config.yaml's `schema:` block carries
`maintenance_charge_w: int(500,5000)` - a fourth declaration site of a different
kind. It is a BOUND, not a default, so it is not this bug; but leaving the
question open is how a fifth site arrives. The decision recorded in config.yaml
and in maintenance.py is: bounds live in the schema block ONLY, because the
Supervisor is what enforces them and the Supervisor reads only that file, so a
Python copy of `int(500,5000)` would be a place to disagree and nothing else.
test_maintenance.py checks both halves of that: every mirrored key must have a
schema entry - without one the Supervisor drops the option and the add-on
silently runs on the mirror instead of the operator's value - and every shipped
default must lie INSIDE its own range, since a default the schema rejects is a
config that cannot be re-entered once it is edited. What the schema grammar
cannot express is a relation BETWEEN keys (`maintenance_charge_w` against
`max_w`), which is exactly why rule 6 is written in Python and why it does not
belong in the mirror either.

THE REPLACEMENT CHECKS, AND HOW THEY WERE VERIFIED. test_validate.py's new
section exercises the same four consumers the defect ran through, the same way:
the validator ACCEPTS a dict with every maintenance key missing; a REAL
Controller built from that same dict holds 2000 W (through main.py, not through
a regex over its source); `MaintConfig()` answers 2000 W with no dict at all;
and the real arbiter emits `-2000 W, limited by supervised(max_w)` instead of
`0 W, contradiction=True`. test_maintenance.py pins the mirror to config.yaml in
both directions - equal values, and full coverage of every `maintenance_*` key
the file ships, so a ninth key cannot arrive unmirrored - and asserts the
consumers move as a RELATION rather than against numbers, reading MaintConfig's
defaults back out of `dataclasses.fields()`.

Each new check was verified by BREAKING the thing it watches and observing red,
this project's rule:

  1. config.yaml -> 1500, mirror left at 2000:  test_maintenance 1 FAILED,
     test_validate 4 FAILED.
  2. config.yaml AND the mirror -> 1500: green again, and every consumer moved
     together - MaintConfig() 1500 W, the Controller 1500 W, and the arbiter
     `-1500 W, limited by maintenance(cheap-window charge)` where it had said
     `-2000 W, limited by supervised(max_w)`. That is AC4: change the single
     source and watch the consumers follow.
  3. `charge_w: float = 2500.0` retyped into the dataclass: 2 FAILED in each of
     the two files.
  4. `opts.get("maintenance_charge_w", 2500)` restored in main.py: 1 FAILED,
     naming the file and the literal it found.
  5. `maintenance_hold_min` deleted from config.yaml's options block: 3 FAILED.

Full suite 17/17 in goodwe-addon-ci, twice, once under parallel load.

Stale prose that asserted the now-closed divergence as current is corrected in
app/watchdog.py, test_watchdog.py and test_peakguard.py - watchdog.py's example
still uses 1500 W, but because the point of the example is a charge strictly
inside the ceiling, not because 2500 is what ships.

Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
2026-09-01 06:16:54 +02:00

466 lines
23 KiB
YAML

name: GoodWe RS485 Controller
version: "0.5.2"
slug: goodwe_controller
description: >-
Drives a GoodWe ES/BP battery inverter over RS485 by emulating its smart
meter, holding net grid exchange at zero and running a monthly battery
maintenance cycle.
url: https://gittea.kammenstraatha.duckdns.org/admin/goodwe-addon
arch:
- aarch64
- amd64
- armv7
init: false
startup: application
boot: auto
# Needed to read the meter and to write the ESPHome setpoint number.
homeassistant_api: true
hassio_api: true
# Own diagnostics/operations UI inside HA. This is what a field tech and a
# remote supporter both look at, so it is not optional.
ingress: true
ingress_port: 8099
panel_icon: mdi:battery-sync
panel_title: GoodWe
# Optional: publish status entities by MQTT discovery. `want` rather than
# `need` - the add-on runs fine with no broker, it just publishes nothing.
services:
- mqtt:want
options:
# --- sources (required) ---------------------------------------------------
meter_entity: sensor.p1_meter_active_power
meter_invert: false
soc_entity: ""
batt_entity: ""
batt_invert: false
setpoint_entity: ""
# --- P1 meter ingestion (specs §5.2 / §14 `meter:`) -------------------------
# `off` keeps the original single meter_entity path above, so an existing
# install is untouched until it opts in. ha_dsmr subscribes to the DSMR
# integration's entities over the HA WebSocket; mqtt_p1 reads the topic below;
# ha_signed reads ONE signed HA entity (+ import / - export), which is what a
# HomeWizard P1 publishes and what ha_dsmr cannot consume.
# homewizard_local skips Home Assistant entirely and polls the meter's own
# local API. ⚠️ It is the ONLY mode whose sensor.p1_sample_age_s measures when
# the meter REPORTED rather than when the value last CHANGED - HA emits
# nothing at all for a repeated reading - so it is the only mode a firmware
# watchdog may threshold. See DOCS.md.
meter_source: "off"
meter_phases: 1
meter_max_age_s: 30
meter_mqtt_topic: ""
# homewizard_local only. The meter's own address, `host` or `host:port`.
p1_host: ""
# homewizard_local only. Seconds between polls. Must be well under
# meter_max_age_s - the age is never fresher than this interval - and there is
# nothing to gain below the meter's own ~5.0 s update rate (NOTES.md:640).
meter_poll_s: 5
# The two UNSIGNED Belgian registers. The EMS derives net power from them
# (import - export); do NOT point these at a signed template sensor.
p1_import_entity: ""
p1_export_entity: ""
# Optional, in L1..L3 order. Required for the capacity-tariff peak on a
# three-phase connection; the list length must equal meter_phases.
p1_phase_import_entities: []
p1_phase_export_entities: []
# ha_signed only. ONE signed net-power sensor: positive = import from the
# grid, negative = export to it. Do NOT split it into two template sensors -
# the split is done in the add-on (p1.split_signed) precisely so the sign
# convention is tested rather than living in unreviewed YAML.
p1_net_entity: ""
# Optional, in L1..L3 order, each one signed the same way. Same role as
# p1_phase_import_entities: the capacity-tariff peak on a three-phase
# connection. The list length must equal meter_phases.
p1_phase_net_entities: []
# --- control ---------------------------------------------------------------
max_w: 2000
gain: 0.6
slew_w: 1000
deadband_w: 15
target_grid_w: -10
step_w: 10
saturation_w: 500
saturation_cycles: 3
integrator_max_w: 0
heartbeat_s: 10
stale_input_s: 15
cycle_floor_s: 15
auto_start: false
# --- SAFETY-02 sign-disagreement watchdog ----------------------------------
# Trips when the emitted setpoint and the P1 net figure point OPPOSITE ways,
# both over sign_disagree_w, continuously for sign_disagree_s. Action: 0 W and
# a failsafe that latches until an operator starts control again.
#
# Both defaults are measured, not chosen. On the captured healthy day
# (2026-08-23) the longest legitimate opposed run - a load step the loop has
# not caught up with - is 30 s, and sign agreement over the gated samples is
# 93.4 %. On the captured fault day (2026-08-20) the clusters run 0.0-10.5 %
# agreement with opposed runs up to 1752 s. 300 W / 180 s sits in the middle of
# a very wide gap: at 60 s the healthy day still trips nothing, at 300 s the
# fault day still trips 13 times. There is no reason to move either number
# without a capture that says so. They are options because the AC says
# thresholds are defaults rather than constants - not because they are knobs
# anyone is expected to turn.
#
# ⚠️ sign_disagree_w must stay BELOW max_w or the watchdog can never fire (the
# arbiter bounds the command to +-max_w). validate.py refuses that config.
sign_disagree_w: 300
sign_disagree_s: 180
# --- SAFETY-18 frozen-but-fresh meter detector -----------------------------
# Seconds the meter may keep answering with an UNCHANGED measurement while the
# command stands at the rail before the add-on raises an alarm. Both halves
# are required: neither one alone is safe, and app/freeze.py carries why.
#
# ALARM ONLY. It does not command 0 W and does not latch. A false trip parks
# the battery; a false notification costs an alert.
#
# ⚠️ Only `meter_source: homewizard_local` can see this at all - it is the
# only transport that reads the meter's own document. On every other source
# the status page says NOT COVERED rather than "armed".
#
# 300 s is measured, not chosen. Over 2399 s of the live house at the
# converged operating point (sim/scenarios/p1-age-2026-08-26.jsonl.gz, mean
# grid -14.2 W, 1194 polls, 735 of them repeating the previous reading) the
# LONGEST run without a distinct reading is 15.4 s (the largest unchanged_s any
# sample observes is 8.0 s). 300 s is 19.5x the pessimistic figure, and
# still inside the 900 s quarter that bills the capacity tariff.
meter_freeze_s: 300
# --- maintenance -----------------------------------------------------------
# ⚠️ CFG-03. THESE EIGHT LINES ARE THE SOURCE OF TRUTH FOR THE MAINTENANCE
# DEFAULTS. The Supervisor reads this file and the operator edits this file,
# so nothing else in the add-on gets an opinion about what a missing
# `maintenance_*` key means. There is exactly ONE in-code copy -
# `app/maintenance.py`'s `MAINT_OPTION_DEFAULTS` - because the Dockerfile does
# not put this file in the image and the running add-on therefore cannot read
# it; test_maintenance.py pins that copy by READING these lines, so a drift
# goes red in CI rather than shipping. main.py and validate.py both read the
# mirror and type no number of their own.
#
# Before this card the same defaults were written down three times and had
# already disagreed: this block said 2000 while main.py and MaintConfig said
# 2500, so an options dict with the key ABSENT passed validation at 2000 and
# then ran at 2500 against a 2000 W ceiling - a silent 0 W arbiter
# contradiction. Changing one of these numbers now moves every consumer.
maintenance_enabled: false
maintenance_interval_days: 28
maintenance_start_hour: 10
# ⚠️ BOTH MUST STAY AT OR BELOW max_w, and that is why they are 2000 rather
# than the 2500 they shipped as. The cheap-window charge shaping asks the
# arbiter for `hi = -maintenance_charge_w` against the supervised `lo =
# -max_w`: above the ceiling that is `lo > hi`, a contradiction resolved to
# 0 W, so maintenance would SILENTLY NEVER CHARGE in a cheap window on a
# default install. validate.py refuses that config (rule 6), so these
# defaults had to become self-consistent with the max_w above rather than
# ship a configuration the validator rejects.
#
# The discharge side is clamped rather than contradicted - it drains at max_w
# and the arbiter says so - so it is only warned about; it is 2000 here for
# symmetry and to keep the shipped config warning-free.
#
# Raising max_w (the live reference install runs 5000) is what unlocks a
# faster maintenance cycle. Raise max_w FIRST, then these.
maintenance_discharge_w: 2000
maintenance_charge_w: 2000
maintenance_soc_floor: 11
maintenance_soc_target: 99
maintenance_hold_min: 120
# --- tariff / capacity tariff (all optional) ------------------------------
peak_forecast_entity: ""
peak_cap_w: 3500
# --- SAFETY-24: the energy backstop under SAFETY-07's forced discharge -----
# The peak guard can COMMAND a discharge to hold a billed quarter under
# peak_cap_w. Until this card it was bounded from below by nothing but the
# pack's own BMS cut-out - a real floor, but the PACK's protection rather than
# the OPERATOR's. On the 2026-08-20 replay the guard asks for 878 Wh in a day.
#
# peak_soc_floor is the percent below which that discharge is not sized. When
# it binds the guard reports FLOOR-LIMITED, keeps charging blocked (a 0 W
# floor), and the add-on raises ONE notification saying the quarter will be
# exceeded - failing to shave is never silent, because the euro figure is the
# whole point of the guard.
#
# ⚠️ THIS IS NOT maintenance_soc_floor AND MUST NOT BE MERGED WITH IT.
# maintenance_soc_floor is the DRAIN TARGET of the monthly recalibration: the
# depth the cycle deliberately goes to, once a month, on purpose. This is the
# depth a money-saving discharge may never reach on any day. The right values
# differ, and sharing one key would couple two features that want to move
# independently.
#
# ⚠️ 20 IS DERIVED, NOT PICKED. The reference pack is 13.8 kWh usable and the
# worst modelled guard day is 878 Wh, i.e. 6.4 % - so 10 points above the
# pack's own cut-out leaves the guard ~1.6 of its worst observed days of room
# and still never reaches the BMS.
#
# ⚠️⚠️ SAFETY-25 - WHAT THIS DOES NOT BOUND, AND IT IS THE HALF THE NAME HIDES.
# peak_soc_floor BOUNDS THE PEAK GUARD ONLY. IT IS NOT A PACK-WIDE RESERVE.
# Ordinary self-consumption - the grid-following loop that holds the meter at
# zero - has no SoC floor of any kind, so on a sustained-load evening it will
# discharge STRAIGHT PAST this number and go on until the pack's own BMS
# cut-out (bms_soc_floor) stops it. Replayed on the committed 2026-08-20
# capture, 19:00-22:00 UTC: a 13.8 kWh pack starting at 21 % ends the evening
# at 10.0 %, and 343 of 587 control cycles deliver discharge with the pack
# already below this floor. Setting this key higher does not change that by
# one tenth of a percent - the same replay at every value the schema accepts
# (5..60) ends at the same 10.0 %.
#
# The reason is structural, not an oversight: the peak guard files a `lo`
# limit (a LOWER bound on the setpoint), which is what makes it provably
# unable to cap a discharge or contradict the arbiter - and therefore also
# unable to stop one the loop itself wants. See peakguard.py's module note and
# DECISIONS/SAFETY-25-loop-soc-floor.md, which records the options for a
# loop-side reserve and is waiting on the product owner. Until that is
# answered, the BMS is the only floor under self-consumption.
peak_soc_floor: 20
# The pack's OWN cut-out percent - what the BMS enforces whatever is set
# above. Register 0x0560 reads 10 on the reference GW5000S-BP, consistent with
# DoD 90. It is here so validate.py can REFUSE a peak_soc_floor at or below
# it: such a floor can never bind, the BMS wins, and the status page would
# report an energy backstop that does not exist.
bms_soc_floor: 10
# ⚠️ THE OLD PRICE PATH, AND IT IS NOT DEAD YET. These two entities are the
# add-on delegating the whole price question to Home Assistant: main.py reads
# both and derives ONE BOOLEAN, `cheap = now <= avg`, which is consumed by
# nothing except the maintenance cycle's cheap-window charge floor. That is
# all they have ever done. They are kept, because retiring them would take
# the maintenance cycle's only price signal away on a live install before
# anything replaces it - TARIFF-03 (static profile) and OPT-04 (arbitrage)
# are the cards that replace it, and neither has landed.
#
# ⚠️ They may NOT be combined with price_provider below. Two price sources on
# one site, one of which silently wins, is exactly the "double up" the PM
# named; validate.py rule 7 refuses that configuration at startup rather than
# letting an operator believe the provider they configured is driving
# something. See app/validate.py.
price_now_entity: ""
price_avg_entity: ""
# --- price providers (TARIFF-02, specs §9.3 / §14 `tariffs:`) --------------
# `off` is the shipped default and means the §11.4 no-price-data row applies:
# static profile, plan provisional, NO ARBITRAGE. Nothing in 0.5.x consumes
# the series yet - OPT-04 is the consumer - so turning this on today fetches,
# validates and publishes prices and changes no energy decision.
#
# ⚠️ THESE DEFAULTS ARE MIRRORED ONCE, IN app/price.py's
# PRICE_OPTION_DEFAULTS, and test_price.py reads THIS FILE and asserts the two
# agree key for key. Do not add a third copy in main.py - CFG-03 is open
# because that has already happened three times.
#
# markup/taxes are the §14 `tariffs.energy_price.*` figures and are added by
# the FRAMEWORK, only for the components the chosen plugin declares its feed
# does not already contain. engie_dynamic, totalenergies_dynamic, eneco_eddy
# and manual_csv publish a figure that already carries the markup, so setting
# it under those is ignored - and logged as ignored, never applied twice.
price_provider: "off"
price_markup_eur_kwh: 0.03
price_taxes_eur_kwh: 0.06
price_csv_path: "/share/goodwe_prices.csv"
price_feed_url: ""
price_horizon_h: 48
price_timeout_s: 10
# --- static / fully-fixed tariffs (TARIFF-03, specs §9.2 / §11.4) ----------
# §14's `tariffs.static_profile`, and "" is its `null`. §9.2: "a large share
# of the installed base is on [a static profile]" - this is what makes those
# sites first-class rather than "price_provider: off, good luck".
#
# A JSON object, on one line, whose periods must tile every day type exactly
# once - no gap and no overlap. A gap is REFUSED at startup rather than
# defaulted, because an invented price is one an optimiser would trade on.
# A fully-fixed tariff is ONE period covering 00:00-24:00, all days; the
# add-on derives "fixed" from there being one distinct price, so there is no
# box to tick and none to tick wrongly.
#
# {"periods": [
# {"name":"day", "from":"07:00","to":"22:00","days":"mon-fri","eur_per_kwh":0.34},
# {"name":"night","from":"22:00","to":"07:00","days":"mon-fri","eur_per_kwh":0.26},
# {"name":"night","from":"00:00","to":"24:00","days":"sat,sun", "eur_per_kwh":0.26}]}
#
# ⚠️ A window written "22:00-07:00 mon-fri" does NOT cover Saturday morning -
# a period applies on the day the CLOCK reads, so the weekend row above is
# required, not decorative. See DOCS.md.
#
# eur_per_kwh is ALL-IN (energy + markup + taxes, §9.3), the same basis the
# dynamic providers are assembled onto. price_markup_eur_kwh and
# price_taxes_eur_kwh are NOT added to it.
#
# ⚠️ RECOMMENDED EVEN ON A DYNAMIC SITE. §11.4's degradation row is "no price
# data -> fall back to the static profile"; with this empty there is nothing
# to fall back to and a dead feed leaves the site with no tariff at all.
# validate.py warns about exactly that.
static_profile: ""
# §9.3: injection is priced SEPARATELY, and in Belgium it is often near zero -
# which by itself strongly favours self-consumption over export. A scalar, not
# a second series: no shipped supplier publishes a dynamic injection curve.
export_price_eur_kwh: 0.04
# --- price arbitrage (OPT-04, specs §10.1 priority 3 / §17) ---------------
# Charge in the cheapest published hour, discharge in the dearest, and ONLY
# when the spread covers what the round trip costs. Off in the shipped
# configuration: this is the first strategy in the add-on that moves energy
# against the meter on purpose, so it is armed deliberately or not at all.
#
# ⚠️ IT NEEDS A PRICE SOURCE AND A P1 METER, and validate.py refuses the
# combinations that cannot work rather than letting them look armed. With
# `price_provider: off` and no `static_profile` there is no series to trade
# on; with `meter_source: off` the capacity-tariff peak guard never runs, and
# §9.1 puts peak shaving above arbitrage - a charge nothing measures is the
# exact failure that guard exists to prevent.
#
# ⚠️ AT THE SHIPPED THRESHOLD A STATIC DAY/NIGHT SITE DOES NOT TRADE. The
# realistic Belgian day/night spread is about 0.08 EUR/kWh and the threshold
# below is 0.10, so the verdict is "the firm spread does not cover this
# cycle's cost" and nothing happens - correctly. That is a product decision
# (this number, and app/price.py's widening factors) and it is open with the
# owner; the code is correct at any value and no number was picked to make a
# trade appear.
arbitrage_enabled: false
# §10.1's `cycle_cost_threshold_eur`: what one full round trip costs per kWh
# - the wear on the pack plus the conversion losses. A spread below this is
# a cycle that loses money and pack life, so it is not taken.
cycle_cost_threshold_eur: 0.10
# The reserve arbitrage may not spend, and the headroom it may not overfill.
# Deliberately NOT the maintenance_soc_* keys: those describe a monthly
# balancing cycle, and pointing a trading strategy at them would couple two
# unrelated policies through one number.
arbitrage_soc_floor: 20
arbitrage_soc_ceiling: 95
# --- site ------------------------------------------------------------------
estop_fitted: false
log_level: info
schema:
meter_entity: str
meter_invert: bool
soc_entity: str
batt_entity: str
batt_invert: bool
setpoint_entity: str
meter_source: list(off|ha_dsmr|mqtt_p1|ha_signed|homewizard_local)
# ⚠️ 2 is accepted by this range but is not a real Belgian connection. A
# telegram whose phase count disagrees is rejected at ingest and logged, so a
# mis-set 2 shows up immediately as "0 telegrams accepted" rather than as a
# quietly wrong number.
meter_phases: int(1,3)
meter_max_age_s: int(5,300)
meter_poll_s: int(1,60)
meter_mqtt_topic: str?
p1_host: str?
p1_import_entity: str?
p1_export_entity: str?
p1_phase_import_entities:
- str
p1_phase_export_entities:
- str
p1_net_entity: str?
p1_phase_net_entities:
- str
max_w: int(100,5000)
gain: float(0.05,1.0)
slew_w: int(50,5000)
deadband_w: int(0,500)
target_grid_w: float(-200,200)
step_w: int(1,100)
saturation_w: int(100,2000)
saturation_cycles: int(1,10)
integrator_max_w: int(0,15000)
heartbeat_s: int(2,25)
stale_input_s: int(5,120)
cycle_floor_s: int(5,60)
auto_start: bool
# No "off" value, deliberately: this is a P0 safety check and the schema is
# not the place to make disarming it a supported configuration.
sign_disagree_w: int(50,5000)
sign_disagree_s: int(30,1800)
# No "off" value, for SAFETY-02's reason: disarming a safety alarm is not a
# supported configuration. ⚠️ THE FLOOR OF 60 IS NOT A RECOMMENDATION. At 300 s
# the slowest a HEALTHY meter's 1 Wh register can tick and still look unchanged
# is 12 W, which is inside the 15 W deadband, so the two terms of the
# conjunction are mutually exclusive rather than merely far apart. At 60 s that
# figure is 60 W and the argument is gone - only the margin is left. See
# app/freeze.py.
meter_freeze_s: int(60,3600)
# ⚠️ CFG-03 - THIS IS WHERE A RANGE LIVES, AND THE ONLY PLACE IT LIVES. The
# `options:` block above holds the DEFAULT; this block holds the BOUNDS, and
# `MAINT_OPTION_DEFAULTS` deliberately mirrors the former and not the latter -
# the Supervisor is what enforces a range and the Supervisor reads only this
# file, so a second copy of `int(500,5000)` in Python would be a place to
# disagree and nothing else. What is NOT expressible here is a relation
# BETWEEN keys: `maintenance_charge_w` must also stay at or below `max_w`, the
# schema grammar has no way to say so, and that is why validate.py's rule 6 is
# written in code instead. Add a ninth maintenance option in three places -
# options:, schema:, MAINT_OPTION_DEFAULTS - and in no fourth.
maintenance_enabled: bool
maintenance_interval_days: int(1,90)
maintenance_start_hour: int(0,23)
maintenance_discharge_w: int(500,5000)
maintenance_charge_w: int(500,5000)
maintenance_soc_floor: int(5,30)
maintenance_soc_target: int(50,100)
maintenance_hold_min: int(5,480)
peak_forecast_entity: str?
peak_cap_w: int(500,15000)
# SAFETY-24. No "off" value: a guard that can command a discharge does not get
# a supported way to have no energy bound at all. The ranges OVERLAP on
# purpose - the schema cannot express "above bms_soc_floor", so validate.py
# rule 8 is what refuses the pair, with a message naming both numbers.
peak_soc_floor: int(5,60)
bms_soc_floor: int(0,50)
price_now_entity: str?
price_avg_entity: str?
# ⚠️ The provider list is written out rather than left as `str`, so the
# Supervisor rejects a typo in the UI. validate.py ALSO refuses an unknown id
# against app/price.py's PROVIDERS registry, because sim/inject.py and the
# checks reach validate_startup_config() with a dict the Supervisor never saw.
# Adding a sixth plugin means adding it here and to PROVIDERS - and nowhere
# else, which is AC2.
price_provider: list(off|generic_dayahead|engie_dynamic|totalenergies_dynamic|eneco_eddy|manual_csv)
price_markup_eur_kwh: float(0,1)
price_taxes_eur_kwh: float(0,1)
price_csv_path: str?
price_feed_url: str?
price_horizon_h: int(1,72)
price_timeout_s: int(2,60)
# A JSON string rather than a nested schema, deliberately: it is ONE option
# key (§14 has one), it survives config.yaml's flat options block, and
# parse_static_profile() accepts an already-parsed dict too, so a future
# nested schema is a config.yaml change and no code change at all.
static_profile: str?
# ⚠️ The lower bound is NEGATIVE on purpose. Belgian injection tariffs have
# gone below zero (you pay to export at midday in summer), and a schema that
# bottoms out at 0 would make that site inexpressible.
export_price_eur_kwh: float(-1,1)
# OPT-04. ⚠️ The threshold's lower bound is 0 and not negative: it is a COST,
# and a negative one is a threshold every spread clears - arbitrage with the
# brake removed. app/arbitrage.py refuses it in code too, because
# validate_startup_config() is also sim/inject.py's entry point and can be
# handed any dict at all.
arbitrage_enabled: bool
cycle_cost_threshold_eur: float(0,1)
arbitrage_soc_floor: int(5,95)
arbitrage_soc_ceiling: int(10,100)
estop_fitted: bool
log_level: list(trace|debug|info|warning|error)