SAFETY-20: measure the freeze rail against the reachable ceiling, not max_w
SAFETY-18's conjunction needs `abs(commanded_w) >= 0.95 * max_w`, but the
emitted command is clipped to the setpoint device's own [dev_min, dev_max]
range as well as to max_w - in clamp_to_rating()'s second stage and again as
the arbiter's `device` P_SAFETY limit claim. Measured on the shipped predicate
at the ticket's numbers, max_w 5000 on a +-4700 W inverter:

    looks_frozen(unchanged_s=3600, commanded_w=4700, max_w=5000)  ->  False

The command is pinned at the hardware's rail, the meter has been frozen for an
hour, and term 2 is unsatisfiable by construction because 4700 < 4750. Any
device rating at or below 0.95 * max_w disarms the conjunction outright, and
the status page then printed `armed (... command is over 4750 W)` - a guard
that cannot fire, advertising that it can, which is the failure SAFETY-15,
SAFETY-19 and validate.py rule 5 all exist to prevent.

The rail is now measured against min(max_w, |dev_min|, |dev_max|), through a
new `rail_ceiling_w()` threaded into looks_frozen(), FreezeWatchdog.evaluate()
and both call sites in main.py. An unread rating leaves the old behaviour
exactly, and correctly: hass.limits() returns None whenever ESPHome is not up,
and on that path no device clamp is applied either, so max_w really is the
ceiling. A rating larger than max_w cannot raise the rail - this is a min(),
not a swap.

THE DELIBERATE CHOICE, since SAFETY-03 has landed. The arithmetic was kept
rather than substituting Decision.i_clamped / Decision.clamped. i_clamped is
the integrator bound (control.py:208, `bounded != i_w`), not "the command is
at the device rating", and `clamped` is the max_w output bound, unreachable on
a default install - neither is the device rail. More decisively, both answer
"did the LOOP ask for more than a bound", while the rail term asks "is the
command standing at the ceiling", and those coincide only when the loop is the
claimer that won. A maintenance SET or a peak-guard floor reaches the ceiling
through arbiter LIMIT claims with no clamp engaging at all, so a boolean rail
would go False exactly during a maintenance phase running against a frozen
meter - which freeze.py's own docstring names as the same fault with a worse
actuator behind it. The predicate is also public with two call sites that pass
DIFFERENT command values (self.target, and `standing` = last_write); a
per-cycle boolean cannot be passed per call site, so substituting it would
have silently decided the pre-clamp-versus-wire question that PM recorded as
still open. AC 1 governs, and it is satisfied literally.

The smaller of the two device bounds, not a per-sign pair. A per-sign rail is
tighter and is not wrong, but it is two rails needing two coverage verdicts on
a status row that carries one number, and the only configuration that
distinguishes them is refused at startup anyway. The symmetric ceiling can only
lower the rail, which widens term 2 rather than disarming it; term 1 carries
the whole no-false-positive argument and is untouched.

A ceiling of 0 W is NOT COVERED, not "armed at 0 W". A device that can command
nothing in one direction would make `abs(command) >= 0` true of every command
including a parked one - term 2 degenerately TRUE, collapsing the conjunction
into the bare unchanged_s > N threshold TEL-05 refused for false-tripping at
this controller's own operating point. rail_unreachable() returns the reason,
looks_frozen() stays silent, and the page uses the NOT COVERED row the
unsupported-transport case already has - a second reason to use that surface,
not a new mechanism.

AC 4, decided rather than assumed: NO NEW validate.py RULE. The configuration
is max_w above the device rating, which rule 2 (CFG-01) already refuses on the
identical predicate, re-run by run_control() once the real rating is known:

    validate_startup_config({... max_w: 5000}, -4700, 4700)
      -> ['max_w is 5000 W but number.sp accepts at most 4700 W - THE DEVICE
          WINS ...']

A rail-specific rule would fire on a strict subset of that (0.95 * max_w >
dev_max implies max_w > dev_max) and could never be the rule that stopped a
start. The residue is the state where hass.limits() answered (None, None) -
ESPHome not up at boot, range checks skipped rather than guessed at, rating
never re-read - and there is nothing to refuse there by construction, which is
why the answer is a runtime row. Recorded in validate.py's "deliberately not
refused" list and pinned by four checks in test_validate.py, so the decision's
premise goes red if rule 2 is ever softened back to a warning.

HOW REACHABLE THIS IS, stated rather than glossed. Because rule 2 refuses the
configuration whenever the rating is known, min(max_w, dev_max) IS max_w on
every install that reaches the control loop with a rating it could read, and
this change is arithmetically dead there. That is clamp.py's argument for its
own second stage word for word: the case where it bites is the case where the
startup gate did not run or no longer holds, and a guard that quietly assumes
the gate ran is a guard that reports armed in exactly the state it cannot fire
in.

Verified by breaking it, per this project's rule. Reverting rail_w() to bare
max_w fails nine checks; deleting the NOT COVERED handling fails five. The one
that mattered: shipping the corrected predicate while NOT passing the rating
from check_meter_frozen() left the entire suite green, because nothing graded
the caller - so test_freeze.py part 5b now drives the real cycle() on a +-4700 W
device and asserts on the notification that leaves the process, and the
unwiring mutation fails three checks there. The peak-guard call site's wiring
is still ungraded (behind p1_enabled, needs a fed averager for `frozen` to have
any observable consequence) and that gap is named in the file rather than
implied.

Full suite: 15/15 in goodwe-addon-ci.

Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
2026-09-01 02:14:07 +02:00

295 lines
14 KiB
Python

"""SAFETY-03 - the output clamp, and the alarm that makes it audible.
WHAT IT CATCHES, in one sentence: a control law that computes a setpoint the
actuator cannot deliver, which every layer below it will happily clip to
something legal-looking while the thing that produced it goes on winding.
THE CLAMP IS NOT THE DELIVERABLE. specs.md 10.3 is explicit that this project
already clipped, and that the clipping is what hid the defect:
with the inverter switched off entirely, an unclamped integrator climbed
~130 W per 4 s to over 10 kW and, pinned at the 5 kW rail, reported
14 768 W
A clamp alone turns that into a silent, perfectly flat 5000 W hold. Every
dashboard reads "commanded 5000 W", which is a legal number, and nothing
anywhere says the loop asked for three times it. 11.2's watchdog row says
"Clamp AND ALARM - the loop is winding"; the second verb is this module.
------------------------------------------------------------------------------
WHAT "THE RATING" IS HERE, AND WHY IT IS ONE NUMBER AND NOT A MIN()
The card names two bounds and warns against choosing between them:
- `DriverCapabilities.setpoint_limit_w` (3.2), the inverter's own magnitude
rating. In this add-on that arrives as the setpoint entity's `min`/`max`
from `hass.limits()` - `Controller.dev_min` / `dev_max`.
- `optimizer.loop.clamp_w` (14), the configured loop clamp. In this add-on
that is the `max_w` option, which `Tuning.max_w` and the arbiter's
`supervised` limit both already use.
14 says these two must AGREE, validated at startup with a refusal on
mismatch - and that gate already ships: `validate_startup_config()` refuses
`max_w > dev_max` and `-max_w < dev_min` (validate.py, problem 1), and
run_control() re-runs it once ESPHome is up and the real rating is known.
So this guard clamps to `max_w`, THE VALIDATED VALUE, and does not `min()` it
with the device rating at runtime. That is the card's instruction and it is also
the only reading that keeps `max_w` meaningful: a silent runtime `min()` is
precisely the "helper bounded to +-500 W under a loop clamped to 1500 W" failure
the 14 warning box is about.
WARNING - THE DEVICE BOUND IS STILL APPLIED, SECOND, AND IT IS NOT REDUNDANT.
After a successful validation `+-max_w` lies inside `[dev_min, dev_max]`, so the
second stage is arithmetically a no-op and can never engage. If it DOES engage,
the validation did not run or no longer holds - `hass.limits()` returns
(None, None) whenever ESPHome is not up yet, and the range checks are skipped
rather than guessed at - and that is a louder fault than the first stage, not a
quieter one. It therefore alarms too, through the same channel, with the bound
named.
⚠️ SAFETY-20 UPDATED THE SECOND HALF OF THAT SENTENCE. It used to read "this is
NOT SAFETY-20; nothing here changes what `freeze.py` measures its rail against",
and that was true of this module and false of the system: this stage is exactly
what clips the emitted command below `RAIL_FRAC * max_w`, which is how a device
rating disarmed the freeze detector while the page said `armed`. `freeze.py` now
takes `dev_min`/`dev_max` and measures its rail against
`min(max_w, |dev_min|, |dev_max|)`. THE CLAMP ITSELF IS UNCHANGED - it still
clamps to `max_w` first and to the device range second, for the reasons above,
and it still does not `min()` the two. What changed is only that the detector
downstream now knows this stage exists.
------------------------------------------------------------------------------
WHERE THE WIND ACTUALLY SHOWS UP - READ THIS BEFORE "SIMPLIFYING" THE CALLER
`control.compute()` bounds the integrator to `integrator_max_w or max_w` and
THEN derives the command from it, so on a default install (`integrator_max_w`
unset, i.e. following `max_w`) the command can never exceed `max_w` and the
actuator-side clamp below IS UNREACHABLE. control.py says so in as many words:
SAFETY-03 ... must watch for THIS, not for "clamped" below.
An alarm wired only to this module's `ClampResult.engaged` would therefore be
silent on the exact configuration the whole ticket is about. The winding is
visible one layer up, at the integrator bound, and that is why `Decision` now
carries `i_clamped` / `clamped` BOOLEANS and the caller ORs them in here.
AND WHY BOOLEANS RATHER THAN `Decision.reason`. `reason` is a single string that
later stages overwrite: a cycle that clamps the integrator and is then slew
limited reports "slew-limited", and one that clamps while saturated reports
"saturated-freeze". Both are exactly the winding-into-a-rail case, and on the
string the clamp signal is destroyed before anything can alarm on it. The two
flags are set where the clamp happens and are never overwritten. A check in
test_clamp.py drives that precise combination.
------------------------------------------------------------------------------
DISTINCT FROM SATURATION - THIS IS ACCEPTANCE CRITERION 2, NOT A NICETY
clamp the COMPUTED value exceeded the rating. A software bug signal:
something upstream is winding. Alarm, every engagement.
saturation |command - inverter AC power| > `saturation_w` for
`saturation_cycles`. The HARDWARE cannot follow a perfectly legal
command. Action is "freeze the integrator" (11.2), not an alarm.
A loop can be legally saturated all day - a cold pack, a curtailed inverter, an
export limit - so a saturation-shaped alarm is one an operator learns to ignore.
Routing the clamp through it puts the bug signal inside the noise, which is the
same silence 10.3 is complaining about. They share no reason code, no
notification id, no status row and no counter.
------------------------------------------------------------------------------
ANTI-FLOOD, WITHOUT GOING SILENT
A genuinely winding loop clamps on EVERY cycle for as long as it winds. One HA
notification per cycle is how an operator learns to dismiss notifications
unread, and this add-on already made that argument once (see the fixed
`notification_id` note in main.check_meter_frozen).
So the two surfaces are split, deliberately:
- EVERY engagement is recorded, never deduplicated, and that record is what
says how hard the loop is pushing. 15's action log is this add-on's
`Controller.events`, and it gets a row from `write_setpoint()` on every
engaged WRITE; `engagements` here counts every engaged CYCLE. The two layers
are counted separately on purpose - the heartbeat re-writes an
already-clamped value between cycles, so a per-write count would inflate and
a per-cycle log would miss an out-of-cycle write.
- THE NOTIFICATION fires on the rising edge and then RE-ASSERTS every
`REASSERT_S`, so a loop pinned on the rail for an hour does not go quiet.
- It DE-ASSERTS only after `CLEAR_CYCLES` consecutive clean cycles, which is
the 10.2 hysteresis: a command sitting exactly on the rail dithers in and
out of engagement by one quantisation step, and without this the alarm
chatters.
`REASSERT_S` and `CLEAR_CYCLES` are module constants, not options, for the same
reason `freeze.RAIL_FRAC` is: they describe the event bus, not the plant, and
every knob 10.3 asked to keep exposed is a LOOP TUNING knob and is untouched by
this module. No new config key is added anywhere - CFG-03 already has three
places a default has to be kept in step and this ticket does not earn a fourth.
------------------------------------------------------------------------------
NOT A TRIP
Clamping does not stop the loop and does not command 0 W. The clamped value is
written and control continues, which is what 11.2 asks for ("Clamp and alarm")
and what distinguishes this from SAFETY-01/02, whose action is 0 W. It follows
that this must NOT drive the failsafe status - `publish()` keeps reporting
"running", because the controller is.
"""
import math
from dataclasses import dataclass
from datetime import datetime
# The reason code, distinct from any saturation-freeze code by construction:
# nothing else in this add-on uses it. See "DISTINCT FROM SATURATION".
REASON_CODE = "OUTPUT_CLAMP"
# Re-assert the notification this often while the clamp stays engaged. 30 s is
# the planning cadence (2.3), i.e. slow enough not to flood and fast enough
# that a pinned loop is never quiet for a whole billing quarter.
REASSERT_S = 30.0
# Consecutive clean cycles before the alarm de-asserts (10.2 hysteresis).
CLEAR_CYCLES = 3
@dataclass(frozen=True)
class ClampResult:
"""What the guard did, with the RAW value preserved.
AC 2 turns on "the raw computed value differed from the clamped one", so the
raw value has to survive the call - a guard that returns only the applied
number cannot be asked the question the acceptance criterion asks.
"""
requested_w: float
applied_w: float
limit_w: float
engaged: bool
bound: str = "" # "" | "max_w" | "device" - which stage bit
def describe(self) -> str:
return (f"{REASON_CODE}: the computed setpoint {self.requested_w:+.0f} W "
f"was clamped to {self.applied_w:+.0f} W by the {self.bound} "
f"bound (rating {self.limit_w:.0f} W) - something upstream is "
f"winding")
def is_commandable(value) -> bool:
"""False for None, NaN and the infinities.
A non-finite setpoint is LOSS OF INPUT, not an out-of-range value, and
11.1 rule 1 says loss of input means command zero and keep commanding. It
must not reach the clamp arithmetic: `min(limit, nan)` returns nan on
CPython, so a nan would sail straight through a naive clamp and then report
`engaged` True on the `applied != requested` test - because nan != nan - i.e.
a transport bug filed in the winding-loop counter, with a nan on the wire.
"""
if value is None:
return False
try:
return math.isfinite(float(value))
except (TypeError, ValueError):
return False
def clamp_to_rating(requested_w, limit_w, dev_min=None, dev_max=None) -> ClampResult:
"""Bound a computed setpoint to the validated rating. The ONLY clamp.
`limit_w` the validated magnitude bound - `max_w`. Symmetric, because
3.2 calls `setpoint_limit_w` a MAGNITUDE clamp: it binds import
(+) and export (-) identically.
`dev_min` / `dev_max` the device's own asymmetric range, applied second and
expected never to bite. See the module note.
Public, and the predicate lives here rather than in the test, for the reason
`freeze.looks_frozen()` gives: a safety expression transcribed into its own
check is one copy plus a future disagreement about what the check means.
EXACTLY +-`limit_w` IS NOT AN ENGAGEMENT. The bound is inclusive; a loop
resting on the rail is doing what it was told, and alarming there would fire
on every healthy full-power hour.
"""
requested = float(requested_w)
limit = abs(float(limit_w))
# ⚠️ BOTH STAGES ALWAYS RUN. THIS USED TO `return` FROM THE FIRST ONE, AND
# THAT WAS A REGRESSION AGAINST THE CODE IT REPLACED. `write_setpoint()`
# previously clamped to the device range unconditionally, under the comment
# "never send a value the device will reject outright"; short-circuiting here
# meant the device bound was applied only when the rating bound had NOT
# fired, i.e. THE BIGGER THE OVERSHOOT THE LESS THE GUARD DID. Measured on
# the shipped function at max_w 5000 against a device of +-4000:
#
# +9999 -> +5000 bound='max_w' <- outside the device range
# +4500 -> +4000 bound='device'
#
# It also undercut this module's own argument for clamping to `max_w` rather
# than a runtime `min()`, which rests entirely on this stage catching the
# case where the startup validation did not run.
applied = max(-limit, min(limit, requested))
bound = "max_w" if applied != requested else ""
# Second stage. Arithmetically dead after a successful startup validation -
# and therefore worth alarming on precisely BECAUSE it fired.
if dev_min is not None and dev_max is not None:
bounded = max(float(dev_min), min(float(dev_max), applied))
if bounded != applied:
bound = "device" if not bound else "max_w+device"
applied = bounded
return ClampResult(requested, applied, limit, applied != requested, bound)
class ClampWatchdog:
"""One instance per controller. Counts every engagement, alarms sparsely.
`note()` is called once per write with whether the clamp bit; the caller ORs
in the loop's own `i_clamped` / `clamped` flags, which is where the winding
is actually visible on a default install (see the module note).
"""
def __init__(self):
self.active = False
self.engagements = 0 # every engagement, never deduplicated
self.episodes = 0 # rising edges
self.since: datetime | None = None
self.last_alarm: datetime | None = None
self.reason = ""
self.clean_cycles = 0
def note(self, engaged: bool, reason: str, now: datetime) -> bool:
"""Advance one cycle. True when the caller should raise the alarm.
`now` is the caller's clock, the same discipline as
`SignWatchdog.evaluate()` and `FreezeWatchdog.evaluate()`.
"""
if engaged:
self.engagements += 1
self.clean_cycles = 0
self.reason = reason
if not self.active:
self.active = True
self.since = now
self.episodes += 1
self.last_alarm = now
return True
# Still engaged: re-assert on the slow cadence, not every cycle.
if (self.last_alarm is None
or (now - self.last_alarm).total_seconds() >= REASSERT_S):
self.last_alarm = now
return True
return False
if not self.active:
return False
self.clean_cycles += 1
if self.clean_cycles >= CLEAR_CYCLES:
self.active = False
self.since = None
self.last_alarm = None
self.reason = ""
self.clean_cycles = 0
return False