"""Runnable check for the control loop's cadence. `python3 test_loop.py`
|
|
|
|
SAFETY-12: the loop must evaluate on a clock as well as on a change. Before the
|
|
fix, `run_control()` ran `cycle()` only when the meter value differed from the
|
|
previous poll, so a meter that repeats a value ran NO control cycles while the
|
|
heartbeat kept re-emitting the last command - measured on the rig during TEL-05
|
|
as 70 s at a literally constant 350.0 W with 14 arrivals and zero cycles.
|
|
|
|
⚠️ THIS TEST TAKES ~95 SECONDS OF WALL CLOCK (measured 93 s), on purpose, and
|
|
that figure is the only thing standing between it and a future developer who
|
|
decides a slow test is a broken one. The thing under test is a wall-clock floor
|
|
inside a loop that sleeps 1 s; mocking the clock would leave the assertion
|
|
testing the mock. It drives the real `run_control()` and counts what actually
|
|
happened. Eight runs of the real loop is what the eight scenarios cost.
|
|
|
|
⚠️ If you shorten the windows, re-measure and update this number and the one in
|
|
HANDOVER.md. An understated runtime reads as a hang.
|
|
|
|
`cycle_floor_s` is read from options with no lower bound in code, so a huge
|
|
value reproduces the pre-fix behaviour exactly. Every claim below is therefore
|
|
an A/B on one binary, not a comparison against a remembered old one.
|
|
|
|
⚠️ MUTATING THE MODULE THIS FILE GRADES? PURGE `__pycache__` FIRST - or run
|
|
`tools/mutation_run.sh`, which does. `python3 -B` alone does NOT save you: it
|
|
stops bytecode being WRITTEN, not a stale one being READ, and a size-preserving
|
|
edit reverted inside one second is invisible to CPython's staleness test. That
|
|
is TEST-15, and it has already turned one live mutation into a false survivor.
|
|
Read MUTATION.md before you report a survivor.
|
|
"""
|
|
|
|
import asyncio
|
|
import sys
|
|
import time
|
|
|
|
from app.main import Controller
|
|
|
|
fails = []
|
|
NEVER = 1e9 # cycle_floor_s so large the floor can never elapse: pre-fix
|
|
|
|
|
|
def check(name, cond):
|
|
print(f" {'ok ' if cond else 'FAIL'} {name}")
|
|
if not cond:
|
|
fails.append(name)
|
|
|
|
|
|
class FakeHass:
|
|
"""A scripted meter and a plant that tracks the command instantly."""
|
|
|
|
def __init__(self, meter, soc_dies_at=None):
|
|
self.meter = meter
|
|
self.soc_dies_at = soc_dies_at
|
|
self.batt = 0.0
|
|
self.writes = []
|
|
self.t0 = time.monotonic()
|
|
|
|
async def limits(self, entity):
|
|
return (-5000.0, 5000.0, 1.0)
|
|
|
|
async def number(self, entity, invert=False):
|
|
now = time.monotonic() - self.t0
|
|
if entity == "sensor.grid":
|
|
return self.meter(now)
|
|
if entity == "sensor.batt":
|
|
return self.batt
|
|
if entity == "sensor.soc":
|
|
if self.soc_dies_at is not None and now >= self.soc_dies_at:
|
|
return None
|
|
return 50.0
|
|
return None
|
|
|
|
async def set_number(self, entity, value):
|
|
self.writes.append(float(value))
|
|
self.batt = float(value)
|
|
return True
|
|
|
|
|
|
class _Store:
|
|
data = {}
|
|
|
|
def set(self, *a):
|
|
pass
|
|
|
|
|
|
class _Pub:
|
|
enabled = False
|
|
|
|
def publish(self, *a, **k):
|
|
pass
|
|
|
|
def close(self):
|
|
pass
|
|
|
|
|
|
BASE = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
|
|
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
|
|
"meter_source": "off", "max_w": 2000, "gain": 0.6, "slew_w": 1000,
|
|
"deadband_w": 15, "target_grid_w": -10, "step_w": 10,
|
|
"heartbeat_s": 10, "stale_input_s": 15}
|
|
|
|
|
|
def drive(meter, floor, seconds, soc_dies_at=None, **over):
|
|
"""Run the real control loop for `seconds`; return (cycle times, writes)."""
|
|
async def go():
|
|
hass = FakeHass(meter, soc_dies_at)
|
|
c = Controller(dict(BASE, cycle_floor_s=floor, **over), hass, _Store(),
|
|
_Pub(), stop=asyncio.Event())
|
|
c.auto = True
|
|
stamps = []
|
|
real = c.cycle
|
|
|
|
async def counted():
|
|
stamps.append(time.monotonic() - hass.t0)
|
|
await real()
|
|
|
|
c.cycle = counted
|
|
task = asyncio.create_task(c.run_control())
|
|
await asyncio.sleep(seconds)
|
|
c.stopping = True
|
|
await asyncio.wait_for(task, timeout=10)
|
|
return stamps, hass.writes, c.target, c.reason
|
|
return asyncio.run(go())
|
|
|
|
|
|
def worst_gap(stamps, seconds):
|
|
"""Longest stretch with no cycle, including the tail after the last one."""
|
|
edges = [0.0] + list(stamps) + [seconds]
|
|
return max(b - a for a, b in zip(edges, edges[1:]))
|
|
|
|
|
|
# --------------------------------------------------------------------------- #
|
|
print("a meter that repeats the same value")
|
|
FLAT = lambda t: 350.0 # noqa: E731
|
|
FLOOR, SECONDS = 3.0, 12.0
|
|
|
|
pre_stamps, pre_writes, _, _ = drive(FLAT, NEVER, SECONDS)
|
|
# The defect itself, demonstrated rather than described: one cycle at startup
|
|
# and then nothing for the rest of the window, while writes keep happening.
|
|
check("pre-fix: a constant meter runs exactly one cycle, at startup",
|
|
len(pre_stamps) == 1)
|
|
check("...while the heartbeat keeps writing anyway, so nothing looks wrong",
|
|
len(pre_writes) >= 2)
|
|
|
|
post_stamps, post_writes, _, _ = drive(FLAT, FLOOR, SECONDS)
|
|
check("post-fix: the same constant meter runs cycles throughout",
|
|
len(post_stamps) >= int(SECONDS / FLOOR) - 1)
|
|
# The actual acceptance criterion: a BOUND on the gap, not a count.
|
|
gap = worst_gap(post_stamps, SECONDS)
|
|
check(f"...with no gap longer than the floor ({gap:.1f}s <= {FLOOR + 1.5:.1f}s)",
|
|
gap <= FLOOR + 1.5)
|
|
check("...and the loop actually corrected, instead of holding a stale command",
|
|
len(post_writes) > len(pre_writes))
|
|
|
|
# --------------------------------------------------------------------------- #
|
|
print("a meter that changes normally - nothing may move")
|
|
# ⚠️ THE REGRESSION GUARD, and the more important half. The floor is a deadline
|
|
# on the gap between cycles, reset by every cycle whichever trigger fired - not
|
|
# a second scheduler. On a healthy meter it must never elapse, so the cycle
|
|
# count, the write count and the commanded values must be IDENTICAL either side
|
|
# of the fix. Anything else is a new write cadence, which SAFETY-12 forbids:
|
|
# the deadband, step_w and the 10 s force-write decide what reaches the wire,
|
|
# and this change is only allowed to alter when the loop thinks.
|
|
STEPS = [0.0, 300.0, 850.0, -400.0, 120.0, -900.0, 60.0]
|
|
LIVE = lambda t: STEPS[int(t // 2) % len(STEPS)] # noqa: E731
|
|
|
|
a_stamps, a_writes, _, _ = drive(LIVE, NEVER, 12.0)
|
|
b_stamps, b_writes, _, _ = drive(LIVE, FLOOR, 12.0)
|
|
check("a changing meter runs the same number of cycles as before the fix",
|
|
len(a_stamps) == len(b_stamps))
|
|
check("...commanding exactly the same sequence of values", a_writes == b_writes)
|
|
|
|
# --------------------------------------------------------------------------- #
|
|
print("a meter parked at the target - the converged operating point")
|
|
# The case TEL-05 warned about: at the converged target the power figure
|
|
# legitimately repeats for minutes. The loop must still run, and must still
|
|
# write nothing but the heartbeat, because the deadband - not the arrival
|
|
# trigger - is what holds the command still.
|
|
AT_TARGET = lambda t: -10.0 # noqa: E731
|
|
c_stamps, c_writes, _, _ = drive(AT_TARGET, NEVER, 12.0)
|
|
d_stamps, d_writes, _, _ = drive(AT_TARGET, FLOOR, 12.0)
|
|
check("the loop evaluates at the converged point too", len(d_stamps) > len(c_stamps))
|
|
check("...and the deadband still holds the command, so writes are unchanged",
|
|
d_writes == c_writes)
|
|
|
|
# --------------------------------------------------------------------------- #
|
|
print("an input dies while the meter repeats - the safety claim must still fire")
|
|
# ⚠️ THE STRONGEST PROPERTY IN SAFETY-12, and the one that makes it a safety fix
|
|
# rather than a latency fix. The `inputs missing -> 0 W` claim lives INSIDE
|
|
# cycle() (main.py, the stale_input_s branch and the P_SAFETY claim below it).
|
|
# Pre-fix, on a meter whose value happened to repeat, cycle() was never called
|
|
# again - so that claim could not fire AT ALL. The controller held its last
|
|
# command through an input outage of unbounded length with the status line still
|
|
# reading "loop -> N W".
|
|
#
|
|
# Layer 1 does not cover this either on a `meter_source: off` install: no P1 age
|
|
# sensor is published (see Controller.publish), so the firmware has nothing to
|
|
# veto on, and the heartbeat keeps its watchdog fed the whole time.
|
|
#
|
|
# stale_input_s is shortened to 3 s here so the outage resolves inside a test
|
|
# rather than inside a quarter of a minute. The mechanism is the default one.
|
|
c2_stamps, c2_writes, pre_target, pre_reason = drive(
|
|
FLAT, NEVER, 10.0, soc_dies_at=4.0, stale_input_s=3)
|
|
check("pre-fix: a dead input during a constant meter never reaches the safety claim",
|
|
pre_target != 0.0 and "safety" not in pre_reason)
|
|
check(f"...so it holds its last command instead ({pre_target:g} W, {pre_reason!r})",
|
|
pre_target == 220.0)
|
|
|
|
d2_stamps, d2_writes, post_target, post_reason = drive(
|
|
FLAT, FLOOR, 10.0, soc_dies_at=4.0, stale_input_s=3)
|
|
check("post-fix: the same outage commands 0 W", post_target == 0.0)
|
|
check(f"...through the safety claim, not by accident ({post_reason!r})",
|
|
"safety" in post_reason)
|
|
check("...and the 0 W actually reached the device", 0.0 in d2_writes)
|
|
|
|
# --------------------------------------------------------------------------- #
|
|
print()
|
|
if fails:
|
|
print(f"{len(fails)} FAILED: " + "; ".join(fails))
|
|
sys.exit(1)
|
|
print("all checks passed")
|