SAFETY-97: "gives nothing" is graded against each battery's idle reading
B's power reading shows -95 to -118 W at idle (standby draw), so the
|reading| < 100 W refusal band never held a refusing B: never at N=2,
and since SAFETY-94's shared rule not at N=1 either (review F1).

Each unit now learns its idle reading (app/idle.py): only while control
runs, the unit is not refused/stale/tripped and its command has stayed
within 50 W for 120 s; first value a 120 s mean, then a 30 min follow;
samples beyond 250 W dropped, value clamped to 250 W; saved per unit and
restored. The shared refusal evidence, compute()'s N=1 engage and end,
the unit refusal ends, the stale-path refusal and SAFETY-42's "parked"
test are centred on it. Until learned it is 0 W, the rule as it was.

Refusing B caught at N=1 28/28/65 s and N=2 24/24/60 s (1/2/5 s
meters), before never; refusing A unchanged. Healthy B with its offset,
SAFETY-94's scenarios, 96 runs: 0 stale, 0 refused. Live replay: 0.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019DBUfvndgHwaV339Fvd2gr
2026-10-04 12:21:24 +02:00

4.2 KiB

SAFETY-97 - "gives nothing" is graded against each battery's idle reading

Status: implemented 2026-10-04, folded into PR #171 (SAFETY-94), for review. Tests: test_safety97.py (rig: tools/safety94_rig.py). Closes SAFETY-94 review finding F1.

The defect

B's power reading (board B's inverter_ac_power, 0x0518) shows -95 to -118 W at idle: its standby draw (the GoodWe app shows 0 W). A's shows -2 to -4 W. Every "the battery gives nothing" test was |reading| < 100 W, so a refusing B sat on the band's edge and never latched:

  • N=2: never caught, before or after SAFETY-94.
  • N=1: the old one-instant check caught it in 17-105 s; SAFETY-94's shared rule (12 cycles in the band in a row) never did (review probe, 1200 s).

Design

  • Offset source: learned per unit (app/idle.py, Inverter.idle). No new option: a required one is a setup step every client gets wrong, and an optional one is a second source to reconcile. An override can be added later if a site needs one.
  • When it learns: control runs; the unit is not refused (unit or site), stale or sign-tripped; its command has been within 50 W (IDLE_ASK_W) for 120 s (IDLE_QUIET_S, 6 lags of 20 s). A refusing battery is asked more than 50 W, and while refused it does not learn, so its refusal cannot be learned as idle. A capped battery under a big ask is not sampled either.
  • How: the first value is the mean of 120 s of samples; then it follows drift with a 30 min time constant. A sample beyond 250 W (IDLE_MAX_W) is dropped (a register held at a giving value); the value is clamped to it.
  • Restart: saved per unit (unit/<name>/idle_w, on first learn and each 5 W move) and restored, clamped. Without it a battery refusing from the start is never quiet, so never learned, so never caught.
  • Until learned the idle reading is 0 W: the rule as it was.

Where it applies

Every test of "gives nothing / gives / takes" now uses reading - idle:

check change
shared refusal evidence _gave_nothing (N=1 and N>=2) centred
N=1 engage and end in compute() (idle_w, the site sum) centred
N=1 end in _refusal_update centred
N>1 unit end (probe answered, takes the other way) centred; uncentred, B's idle -100 W read as "takes 100 W" and ended a charge refusal at once
stale-path refusal (_refusal_from_stale, N=1 and N>1) centred
SAFETY-42 "parked" (small ask, gives nothing) centred
SAFETY-37 stale gate unchanged: it grades register changes against command travel, not a level
SAFETY-57 release unchanged: it reads the command only
SAFETY-30 per-unit sign unchanged: opposition needs both over 250 W; B's 100 W idle cannot make or hide one alone
SAFETY-42 shortfall unchanged: B reads ~100 W short at every power, which errs towards reporting (report only)

Bounds

  • Band: |reading - idle| < 100 W, |idle| <= 250 W.
  • A correct idle reading: a refusing B behaves as a refusing A.
  • A wrong one (worst, 250 W off): a refusing battery reading outside the band is not refused by this rule; a frozen register is still caught by the stale gate at 35 s of asking. Learning only at a ~0 W command for 2 min keeps a wrong value unlikely. Once learned, a 10 min transient moves it by 28 %; the first value (a 2 min mean) is the exposed one.
  • An idle reading beyond 250 W is never learned: such a unit keeps 0 W.

Catch times (rig, refusing from 200 s after a 400 s rest, +-4 W)

refusing meter 1 s 2 s 5 s
A, N=1 28 s (before 28) 28 (28) 65 (65)
A, N=2 28 (28) 28 (28) 110 (110)
B, N=1 28 (never) 28 (never) 65 (never)
B, N=2 24 (never) 24 (never) 60 (never)

A at N=2 on a 5 s meter is 110 s here because the rig's grid goes flat once A is cut, so the loop cycles on the 15 s floor; the same run on the PR before SAFETY-97 gives 110 s. B restored after a restart, refusing from the start: 24 s; with nothing saved: never.

Before -> after

  • Healthy B with its offset, SAFETY-94's four scenarios, N=1 and N=2, 1/2/5 s meters, both register shapes, idle learned or restored (96 runs): 0 stale, 0 refused. Reversals, lag 10/20 s, idle restored: 0.
  • Live replay (SAFETY-94 part 1): 0 trips (the gate is untouched).