SAFETY-96 review: keep the refusal count over a refused write; test a fast board
F1: resetting the count on each refused write hid a battery that really
refuses behind a link refusing 1 write in 3 (never learned; learned at
358 s with the count kept). F2: a board at 0 W before its link is stale
learned no refusal untested (mutation R7 survived); now a 1 s-lag case.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-06 05:46:32 +02:00

574 lines
24 KiB
Python

"""Runnable check for SAFETY-96: a battery the loop cannot move does not
freeze the loop. `python3 test_safety96.py`
At N=2, after A's link went stale the site sum still counted A's power, so
`compute()` saw the site "not following" and froze B (SAFETY-93 rig test:
B held at 1200 W for ~236 cycles). After a charge timeout or Off at 6000 W
it froze ~14 s while A came out of its charge. Now a battery out of the
split, with refused writes, or settling after a step the loop did not make
counts at its command; its real power reaches the loop through the meter.
Drives the REAL Controller on a lagging battery (10 s, 2 s meter).
DECISIONS/SAFETY-96-dropped-battery.md.
1. A's link drops while it discharges: A holds its last command (stuck), or
its board goes to 0 W 25 s after the first refused write.
2. A's link drops while it charges (maintenance).
3. B's link drops; both drop.
4. A drops, then comes back.
5. A's charge times out, or A is switched Off, at 6000 W.
6. N=1 is untouched; the rule's parts one by one.
Mutations (MUTATION.md, purged copies) are listed in the pull request.
"""
import hashlib
import logging
import math
import os
import sys
from datetime import datetime, timedelta, timezone
HERE = os.path.dirname(os.path.abspath(__file__))
sys.path.insert(0, HERE)
sys.path.insert(0, os.path.join(HERE, "tools"))
logging.disable(logging.WARNING)
import opt11_identity as rig # noqa: E402
import safety79_identity as s79 # noqa: E402
import safety84_identity as s84 # noqa: E402
from app import packmode # noqa: E402
from app.main import Controller # noqa: E402
from app.maintenance import CHARGE_TIMEOUT_MIN, IDLE, MaintResult # noqa: E402
from app.store import unit_key # noqa: E402
from named_absence import first, present # noqa: E402
fails = []
SLEW = 400.0
FROZEN = ("saturated-freeze", "freeze-released")
OPT = dict(s84.OPT, peak_cap_w=3500)
PLAIN = dict(s79.P1, peak_cap_w=3500)
def check(name, cond):
print(f" {'ok ' if cond else 'FAIL'} {name}")
if not cond:
fails.append(name)
# None on a tree without the fix, where this file prints the base numbers
# and runs red.
fixed = getattr(Controller, "_held_out_w", None)
real_drop = getattr(Controller, "_reseed_drop", None)
def without(fn):
"""Run `fn` with SAFETY-96 taken out (the base behaviour)."""
if fixed is None:
return fn()
Controller._held_out_w = lambda self, live: 0.0
Controller._reseed_drop = lambda self, live: setattr(
self, "_live_was", frozenset(live))
try:
return fn()
finally:
Controller._held_out_w, Controller._reseed_drop = fixed, real_drop
def run(n=2, *, house=lambda t: 2400.0, dur=600.0, store=None, opt=None,
soc=None, reject=None, back=None, wd=None, before=None, lag=10.0,
blind=None, flaky=None, dead=None):
"""Rows of one run. Writes to the units in `reject` (name -> from s) are
refused from that time until `back` s; the add-on sees the refusal at
once (a heartbeat write). A refused unit holds its last command, or with
`wd` its board goes to 0 W `wd` s after the first refused write. B's
reading is missing in the `blind` (from, to) window. `flaky(u, t)`:
writes to u refused at t, each cycle's verdict seen (a heartbeat).
`dead` (u, from s): u gives nothing from then on, whatever it is told.
Each row: (t, plant commands, add-on commands, loop reason, site target,
grid, circulation tripped)."""
reject = reject or {}
real_p, real_s, real_tick = rig._Hass.power, rig._Hass.set_number, rig.TICK
def refused(u, t):
if flaky is not None:
return flaky(u, t)
return u in reject and t >= reject[u] and (back is None or t < back)
def power(self, u):
st = self.__dict__.setdefault("_plant", {})
a, tgt, tl = st.get(u, (0.0, 0.0, self.t))
for k in range(int(round((self.t - tl) / 0.1))):
now = tl + (k + 1) * 0.1
c = self.cmd[u]
if wd is not None and refused(u, now) and now - reject[u] >= wd:
c = 0.0
if dead is not None and u == dead[0] and now >= dead[1]:
c = 0.0
d = c - tgt
tgt += math.copysign(min(abs(d), 80.0), d)
a += (tgt - a) * (1 - math.exp(-0.1 / lag))
st[u] = (a, tgt, self.t)
return float(round(a))
async def set_number(self, e, v):
if refused(e[-1], self.t):
return False
self.cmd[e[-1]] = float(v)
return True
rows = []
def hook(c, t):
for inv in c.inverters:
if flaky is not None:
inv.note_write(not flaky(inv.name[-1], t),
rig.BASE + timedelta(seconds=t))
elif refused(inv.name[-1], t) and inv.rejected_since is None:
inv.rejected_since = rig.BASE + timedelta(seconds=t)
if before is not None:
before(c, t)
if blind is not None and not getattr(c.hass, "_s96", False):
read = c.hass.number
async def number(e, invert=False):
if e == "sensor.batt_b" and blind[0] <= c.hass.t < blind[1]:
return None
return await read(e, invert)
c.hass.number, c.hass._s96 = number, True
(s84.feed(True) if opt is not None else s79._feed)(c, t)
def on_cycle(c, t):
rows.append((t, tuple(sorted(c.hass.cmd.items())),
tuple(inv.target for inv in c.inverters), c.loop_reason,
c.target, c.hass.grid(), c.circ_wd.tripped,
tuple(inv.batt for inv in c.inverters)))
rig._Hass.power, rig._Hass.set_number, rig.TICK = power, set_number, 2.0
try:
_r, ctl = rig.run(n, extra=dict(opt if opt is not None else PLAIN),
dur=dur, load=house, soc=soc or (lambda u, t: 60.0),
cut=lambda u, t: False, before=hook,
on_cycle=on_cycle, store=store or rig._Store())
finally:
rig._Hass.power, rig._Hass.set_number, rig.TICK = real_p, real_s, \
real_tick
return rows, ctl
def freeze(rows, lo, hi=1e9):
return sum(1 for r in rows if lo <= r[0] < hi and r[3] in FROZEN)
def phantom(rows, k, lo, hi=1e9):
"""Freeze cycles while battery `k` (the one taking over) reads within
saturation_w (500 W) of what the loop last asked of it plus anything
unplaced (last site target less the other's command): the freeze is
then about the other battery, not about `k`'s own lag."""
return sum(1 for a, b in zip(rows, rows[1:]) if lo <= b[0] < hi
and b[3] in FROZEN
and abs(a[4] - a[2][1 - k] - b[7][k]) <= 500.0)
def ramp(rows, k, lo, hi=1e9):
"""The largest change of unit `k`'s command (0 = A) between cycles."""
return max(abs(b[2][k] - a[2][k]) for a, b in zip(rows, rows[1:])
if lo < b[0] <= hi)
def site_step(rows, lo, hi=1e9):
return max(abs(b[4] - a[4]) for a, b in zip(rows, rows[1:])
if lo < b[0] <= hi)
def grid_err(rows, lo, hi=1e9):
"""Mean |grid - aim| over [lo, hi) (aim -10 W)."""
xs = [abs(r[5] + 10.0) for r in rows if lo <= r[0] < hi]
return sum(xs) / len(xs)
def trip_at(rows):
"""When the circulation guard tripped (its own 0 W step is no ramp)."""
return next((r[0] for r in rows if r[6]), 1e9)
def tripped(rows):
return rows[-1][6]
def at(rows, t, k):
return first((r[2][k] for r in rows if r[0] == t), f"row {t}")
TABLE = []
LAST = [None] # the controller of the last run with the fix
def case(name, fn, lo, k, hi=1e9):
"""Run `fn` with and without SAFETY-96, print and record the numbers:
freeze cycles (and those not about `k`'s own lag), `k`'s largest step,
the mean grid error, a circulation trip."""
(now, LAST[0]), old = fn(), without(fn)[0]
row = (name, freeze(now, lo, hi), freeze(old, lo, hi),
phantom(now, k, lo, hi), phantom(old, k, lo, hi),
ramp(now, k, lo, min(hi, trip_at(now) - 1)),
ramp(old, k, lo, min(hi, trip_at(old) - 1)),
grid_err(now, lo, hi), grid_err(old, lo, hi),
tripped(now), tripped(old))
TABLE.append(row)
print(f" {name}: freeze {row[1]} (base {row[2]}), not about its own lag "
f"{row[3]} (base {row[4]}); step {row[5]:.0f} (base {row[6]:.0f}) "
f"W/cycle; grid error {row[7]:.0f} (base {row[8]:.0f}) W; "
f"circulation trip {row[9]} (base {row[10]})")
return now, old
STUCK, BOARD = ("stuck", None), ("board 0 W", 25.0)
# ============================================================================ #
print("1. A's link drops while it discharges (house 2400 W, each 1200 W)")
for v, w in (STUCK, BOARD):
now, old = case(f"A drop discharging, {v}",
lambda w=w: run(reject={"a": 300.0}, wd=w), 300.0, 1)
check(f"⭐ {v}: no freeze about A, B moves at most one slew step a "
f"cycle, no circulation trip", phantom(now, 1, 300) == 0
and ramp(now, 1, 300) <= SLEW and not tripped(now))
check(f"non-vacuous ({v}): without the fix the loop freezes about A, or "
f"B jumps more than a slew step at the drop",
phantom(old, 1, 300) >= 10 or ramp(old, 1, 300) > SLEW)
if w is None:
check("stuck: B stays at its share, since A still gives its 1200 W "
"(no freeze at all, grid within 15 W on average)",
freeze(now, 300) == 0 and grid_err(now, 300) < 15.0
and freeze(old, 300) >= 100)
else:
check("board 0 W: B ends up carrying the whole house (2410 W)",
abs(now[-1][2][1] - 2410.0) <= 20.0)
# ============================================================================ #
print("\n2. A's link drops while it charges (maintenance, house 1200 W)")
def charging(**kw):
return run(house=lambda t: 1200.0, dur=1500.0,
store=s79.store_charging(2), opt=dict(
OPT, maintenance_hold_min=600),
soc=lambda u, t: 90.0 if u == "a" else 60.0, **kw)
for v, w in (STUCK, BOARD):
now, old = case(f"A drop charging, {v}",
lambda w=w: charging(reject={"a": 1300.0}, wd=w),
1300.0, 1)
trip = trip_at(now)
check(f"⭐ {v}: no freeze about A, and B climbs at most one slew step a "
f"cycle and never charges (until any circulation trip)",
phantom(now, 1, 1300, trip) == 0
and ramp(now, 1, 1300, trip - 1) <= SLEW
and min(r[2][1] for r in now if r[0] >= 1300) >= 0.0)
check(f"non-vacuous ({v}): without the fix the loop freezes about A",
phantom(old, 1, 1300) >= 3)
if w is None:
check("stuck (A charges 2000 W on its own): B reaches its 2500 W "
"before the circulation trip, which still trips on the real "
"4000 W going round (as on base)",
max(r[2][1] for r in now if r[0] < trip) == 2500.0
and tripped(now) and tripped(old))
else:
check("board 0 W: B carries the house (grid within 50 W from 100 s "
"after the drop), no circulation trip",
grid_err(now, 1400) < 50.0 and not tripped(now))
# ============================================================================ #
print("\n3. B's link drops; both drop")
for v, w in (STUCK, BOARD):
now, old = case(f"B drop discharging, {v}",
lambda w=w: run(reject={"b": 300.0}, wd=w), 300.0, 0)
check(f"⭐ B drops ({v}): no freeze about B, A moves at most one slew "
f"step a cycle, no circulation trip", phantom(now, 0, 300) == 0
and ramp(now, 0, 300) <= SLEW and not tripped(now))
for v, w in (STUCK, BOARD):
now, old = case(f"both drop, {v}",
lambda w=w: run(reject={"a": 300.0, "b": 300.0}, wd=w),
300.0, 1)
check(f"⭐ both drop ({v}): no freeze; both are commanded 0 W once "
f"nothing can be placed", freeze(now, 300) == 0
and now[-1][2] == (0.0, 0.0) and not tripped(now))
# ============================================================================ #
print("\n4. A drops, then comes back")
def rejoined(rows):
return next((r[0] for r in rows if r[0] > 420 and r[2][0] != 0.0), 1e9)
for v, w in (STUCK, BOARD):
now, old = case(f"A drop and rejoin, {v}",
lambda w=w: run(reject={"a": 300.0}, back=420.0, wd=w,
dur=700.0), 300.0, 1)
back = rejoined(now)
check(f"rejoin ({v}): A is back in the split within 4 s of its link "
f"returning (no refusal was learned while its writes were refused)",
back <= 424.0 and not any("REFUSES" in e for e in LAST[0].events))
print(f" A back in the split at {back:.0f} s; A "
f"{[r[2][0] for r in now if back - 2 <= r[0] <= back + 6]}, B "
f"{[r[2][1] for r in now if back - 2 <= r[0] <= back + 6]}; grid "
f"{[round(r[5]) for r in now if back - 2 <= r[0] <= back + 6]}; "
f"base grid {[round(r[5]) for r in old if back - 2 <= r[0] <= back + 6]}")
a0 = first((r for r in now if r[0] == back - 2), "row before the rejoin")
a1 = first((r for r in now if r[0] == back), "the rejoin row")
check(f"⭐ rejoin ({v}): no freeze after it; the site target takes in only "
f"A's own reading, then moves at most one slew step a cycle; the "
f"grid stays within 250 W of its aim; no circulation trip",
present(a0) and present(a1) and freeze(now, back) == 0
and abs(a1[4] - a0[4] - a0[7][0]) <= SLEW
and site_step(now, back) <= SLEW
and max((abs(r[5] + 10.0) for r in now if r[0] >= back),
default=1e9) < 250.0
and not tripped(now))
if w is None:
check("non-vacuous (stuck): without the fix the grid swings over "
"1000 W after the rejoin", max((abs(r[5] + 10.0) for r in old
if r[0] >= back), default=0.0)
>= 1000.0)
# Review: a battery that does refuse, behind a link that refuses one write
# in three, is still found out (the count is kept over a refused write).
_fl_rows, _fl = run(dur=700.0, dead=("a", 300.0),
flaky=lambda u, t: u == "a" and t >= 300.0
and int(t / 2) % 3 == 0)
_fl_at = next((r[0] for r in _fl_rows if r[2][0] == 0.0 and r[0] > 300.0),
None)
_fl_end = first((r[2] for r in _fl_rows[-1:]), "the last row")
print(f" A gives nothing from 300 s, 1 write in 3 refused: A's share is "
f"taken off at {_fl_at} s; A {_fl.inverters[0].refused}, last "
f"commands {_fl_end}")
check("⭐ a battery that refuses behind a link refusing 1 write in 3: its "
"refusal is still learned and B carries the house",
_fl.inverters[0].refused == 1 and _fl_at is not None
and _fl_at <= 400.0 and present(_fl_end)
and abs(_fl_end[1] - 2410.0) <= 20.0)
# Review: a fast battery whose board goes to 0 W 1 s after the first refused
# write reads ~0 W long before its link is stale (30 s): no refusal either.
_ref5 = []
_e5_rows, _e5 = run(reject={"a": 300.0}, back=420.0, wd=1.0, lag=1.0,
dur=700.0,
before=lambda c, t: _ref5.append(c.inverters[0].refused))
check("fast battery, board 0 W 1 s after the first refused write: no "
"refusal is learned, A is back in the split within 4 s of its link "
"returning",
not any(_ref5) and rejoined(_e5_rows) <= 424.0)
_seen = []
def blind_seen(c, t):
"""Record the last cycle: whether the loop ran, is A live, what settles."""
if t > 340.0:
_seen.append((t - 2.0, c.loop_reason, "inverter-a" in c.live_units(),
dict(c._settle)))
run(reject={"a": 300.0}, back=420.0, blind=(340.0, 470.0), dur=490.0,
before=blind_seen)
_back = first((x for x in _seen if x[1] != "not-running" and x[0] > 400),
"the restart")
print(f" B's reading missing 340-470 s, A back at 420 s: control holds from "
f"{first((x[0] for x in _seen if x[1] == 'not-running'), '?')} s, "
f"restarts at {_back[0]:.0f} s, settling then: {_back[3]}")
check("A drops, then comes back while control holds (a reading missing): no "
"rejoin at the restart, which starts from what is on the wire",
any(x[1] == "not-running" and x[2] for x in _seen) and _back[3] == {})
# ============================================================================ #
print("\n5. A's charge times out, or A is switched Off, at a 6000 W house")
def timed_out(end):
"""A's charge passes CHARGE_TIMEOUT_MIN at `end` s; A then stays free
(its cycle started today, so no restart) and B is not due."""
s = s79.store_charging(2)
s.data[unit_key("inverter-a", "phase_started")] = (
rig.BASE + timedelta(seconds=end - CHARGE_TIMEOUT_MIN * 60 - 1)
).isoformat()
s.data[unit_key("inverter-a", "last_start_attempt")] = rig.BASE.isoformat()
s.data[unit_key("inverter-b", "last_completed")] = rig.BASE.isoformat()
return s
def b_done():
s = s79.store_charging(2)
s.data[unit_key("inverter-b", "last_completed")] = rig.BASE.isoformat()
return s
def switch_off(at_t):
def before(c, t):
if t >= at_t:
c.store.data[unit_key("inverter-a", packmode.USE_KEY)] = False
return before
def high(t):
return 6000.0 if t >= 1760.0 else 1200.0
ENDS = {
"timeout": lambda: run(house=high, dur=1798.0, store=timed_out(1780.0),
opt=dict(OPT, maintenance_hold_min=600),
soc=lambda u, t: 90.0 if u == "a" else 60.0),
"Off": lambda: run(house=high, dur=1798.0, store=b_done(),
before=switch_off(1780.0),
opt=dict(OPT, maintenance_hold_min=600,
battery_modes_enabled=True),
soc=lambda u, t: 90.0 if u == "a" else 60.0),
}
for k, fn in ENDS.items():
now, old = case(f"{k} at 6000 W", fn, 1780.0, 1)
print(f" B {[r[2][1] for r in now if 1778 <= r[0] <= 1796]}, base "
f"{[r[2][1] for r in old if 1778 <= r[0] <= 1796]}")
check(f"⭐ {k}: no freeze about A while it comes out of its charge; B "
f"climbs one slew step a cycle and never charges",
phantom(now, 1, 1780) == 0 and ramp(now, 1, 1780) <= SLEW
and min(r[2][1] for r in now if r[0] >= 1780) >= 0.0)
check(f"non-vacuous ({k}): without the fix the loop freezes about A and "
f"B ends lower", phantom(old, 1, 1780) >= 3
and at(now, 1796.0, 1) > at(old, 1796.0, 1))
# ============================================================================ #
print("\n6. N=1 is untouched; the rule's parts")
def digest(rows):
return hashlib.sha256(repr(rows).encode()).hexdigest()
def wave(t):
return 2400.0 + 1500 * math.sin(t / 40)
_n1 = [lambda: run(1, reject={"a": 300.0}, back=420.0, wd=25.0),
lambda: run(1, house=high, dur=1798.0, store=timed_out(1780.0),
opt=dict(OPT, maintenance_hold_min=600)),
lambda: run(1, house=wave)]
check("⭐ N=1 (a refused link that comes back, a charge timeout, a moving "
"house): every row byte-identical with and without SAFETY-96",
[digest(f()[0]) for f in _n1] == [digest(without(f)[0]) for f in _n1])
check("N=2 healthy (a moving house, no drop): every row byte-identical with "
"and without SAFETY-96",
digest(run(house=wave)[0]) == digest(without(lambda: run(
house=wave))[0]))
if fixed is None:
print(f"\n{len(fails)} FAILED (no _held_out_w): " + ", ".join(fails))
sys.exit(1)
_c = run(dur=4.0)[1]
AB = ("inverter-a", "inverter-b")
def held(batts, targets, live=AB, rejected=(), settle=None, now=100.0,
start=None):
for inv, b, t in zip(_c.inverters, batts, targets):
inv.batt, inv.target = b, t
inv.rejected_since = rig.BASE if inv.name in rejected else None
_c._settle = dict(settle or {})
_c._loop_start = dict(start or {})
_c._now_mono = now
return _c._held_out_w(set(live))
check("a healthy pair: nothing held out, however far a reading lags",
held((-2000.0, 400.0), (0.0, 400.0)) == 0.0)
check("a dropped battery counts at its command (0 W), not its reading",
held((-2000.0, 800.0), (0.0, 800.0), live=("inverter-b",)) == 2000.0)
check("a battery whose writes are refused counts at its command",
held((900.0, 800.0), (1200.0, 800.0), rejected=("inverter-a",))
== 300.0)
check("a settling battery counts at its command until its reading is within "
"the deadband (15 W) of it, then it is the loop's again",
held((-20.0, 800.0), (0.0, 800.0), settle={"inverter-a": 95.0})
== 20.0 and "inverter-a" in _c._settle
and held((-10.0, 800.0), (0.0, 800.0), settle={"inverter-a": 95.0})
== 0.0 and "inverter-a" not in _c._settle)
check("...but not on the cycle it starts",
held((-10.0, 800.0), (0.0, 800.0), settle={"inverter-a": 100.0})
== 10.0 and "inverter-a" in _c._settle)
check("...or until PLANT_SETTLE_DOWN_S (23 s) has passed, whichever is first",
held((-2000.0, 800.0), (0.0, 800.0), settle={"inverter-a": 77.1})
== 2000.0 and held((-2000.0, 800.0), (0.0, 800.0),
settle={"inverter-a": 77.0}) == 0.0)
check("a reseeded start (SAFETY-93's charge end) is the command it counts at",
held((-2000.0, 800.0), (-2000.0, 800.0), settle={"inverter-a": 99.0},
start={"inverter-a": 0.0}) == 2000.0)
def dropped(was, live, target, shares, batts=(0.0, 0.0), start=None):
_c._live_was, _c.target, _c.i_w = (None if not was else frozenset(was),
target, 123.0)
_c._loop_start, _c._settle, _c._now_mono = dict(start or {}), {}, 50.0
for inv, b in zip(_c.inverters, batts):
inv.target, inv.batt = shares[inv.name[-1]], b
_c._reseed_drop(set(live))
return _c.target, _c.i_w
check("a drop: the dropped battery's share leaves the start point, the "
"integrator with it", dropped(AB, ("inverter-b",), 2400.0,
{"a": 1200.0, "b": 1200.0})
== (1200.0, 1200.0) and _c._live_was == frozenset({"inverter-b"}))
_c._charge_ended = frozenset({"inverter-a"})
check("...but a battery whose charge ended too is left to SAFETY-93's reseed",
dropped(AB, ("inverter-b",), -2000.0, {"a": -2000.0, "b": 0.0})
== (-2000.0, -2000.0))
_c._charge_ended = frozenset()
_free = MaintResult(IDLE, False, None, False, [])
def charge_end(rejected_s):
"""SAFETY-93's reseed for A (giving 1385 W under the loop, its charge
suspended), A's writes refused for `rejected_s` s: (target, start)."""
_c.target, _c.i_w, _c._charge_ended = 2770.0, 0.0, frozenset({AB[0]})
_c._loop_start, _c._settle = {}, {}
for inv in _c.inverters:
inv.target, inv.rejected_since = 1385.0, None
_c.inverters[0].rejected_since = datetime.now(timezone.utc) - timedelta(
seconds=rejected_s)
_c._reseed_charge_end([_free, _free])
_c.inverters[0].rejected_since = None
return _c.target, _c._loop_start[AB[0]]
check("a charge that ends as its battery drops: the battery's start is 0 W "
"(it is sent 0 W), not its last give; still live, its give stays",
charge_end(31.0) == (1385.0, 0.0) and charge_end(5.0) == (2770.0, 1385.0))
check("a rejoin: the battery enters the start point at its reading, and "
"both settle while the split is made again",
dropped(("inverter-b",), AB, 1200.0, {"a": 0.0, "b": 1200.0},
batts=(-700.0, 1200.0)) == (500.0, 500.0)
and _c._settle == {"inverter-a": 50.0, "inverter-b": 50.0})
check("no change: nothing moves (the integrator either)",
dropped(AB, AB, 1200.0, {"a": 600.0, "b": 600.0}) == (1200.0, 123.0)
and dropped((), ("inverter-b",), 1200.0, {"a": 0.0, "b": 1200.0})
== (1200.0, 123.0))
_n1c = run(1, dur=4.0)[1]
_n1c._live_was, _n1c.target, _n1c.i_w = frozenset({"inverter-a"}), 900.0, 5.0
_n1c._reseed_drop(set())
check("N=1: nothing moves and nothing is held out",
(_n1c.target, _n1c.i_w) == (900.0, 5.0)
and _n1c._held_out_w(set()) == 0.0)
print("\n case | freeze head/base | not about its own lag head/base | "
"step W head/base | grid error W head/base | circulation trip head/base")
for r in TABLE:
print(f" {r[0]} | {r[1]}/{r[2]} | {r[3]}/{r[4]} | {r[5]:.0f}/{r[6]:.0f} |"
f" {r[7]:.0f}/{r[8]:.0f} | {r[9]}/{r[10]}")
print()
if fails:
print(f"{len(fails)} FAILED: " + ", ".join(fails))
sys.exit(1)
print("all SAFETY-96 checks passed")