SAFETY-137: the shutdown and Stop 0 W is the last write every unit hears
The 0 W of shutdown and of the Stop button now waits (bounded, 2 s) for a
write already on its way to the same unit, for every driver, GoodWe included.
Once shutdown has begun, cycle, heartbeat and safety-stop writes are dropped
right before the write is created. One shared wait (_await_inflight) serves
the 0 W and SMA-10's _release_last.

Co-Authored-By: Claude <noreply@anthropic.com>
2026-11-08 02:39:38 +01:00

1.1 KiB

SAFETY-137 - the shutdown 0 W is the last write every unit hears

SMA-10 made a hand-back release wait for a write already on its way (_release_last, Inverter.inflight). A GoodWe unit skipped that, and rig 5b saw a cycle write (-2 823 W) land after the shutdown 0 W and stay until relaunch.

Now the 0 W of shutdown and of the Stop button is a last write (_write_unit(last=True)), for every driver:

  • It first waits, at most SETTLE_BUDGET_S (2 s), for the writes already on its way to that unit (_await_inflight, shared with _release_last). A hung write is not waited out and not cancelled; the 0 W goes anyway.
  • Once shutdown has begun (stopping), every other write (cycle, heartbeat, safety stop) is dropped at the same place, right before the write is created. That is the gate that keeps the control cycle quiet; the cycle itself needs no cancelling.
  • Worst case for a GoodWe unit is 2 s + WRITE_BUDGET_S (4 s) = 6 s, the same as HAND_BACK_WORST_S; the units are handled together.

Not touched: the heartbeat's own timing, safety-stop paths, the maintenance abort (still a plain 0 W).