The product owner answered SAFETY-25's §1 on 2026-09-02: OPTION A. The BMS cut-out is the DELIBERATE and only backstop for demand-driven discharge on the grid-following loop, and Option B - a loop-side reserve floor - is DEFERRED rather than rejected. Option A is the shipped behaviour, so this is a recording, not a change. `app/` is touched in exactly two places and both are comments that claimed the question was still open (freeze.py's finding, peakguard.py's point 2). No setpoint, no claim, no option, no default moved. The 17-suite run is green on the same numbers as before. WHY DEFERRING IS THE SAFE DIRECTION. Option B's proof - bms_soc_floor < loop_soc_floor <= peak_soc_floor, run through the real arbiter in test_peakguard.py part 10d - has an unstated premise: the reserve predicate and discharge_permitted() read the SAME state of charge. With two packs they read different numbers. The reserve binds on the emptier pack and files hi = 0; the peak guard, reading the other pack or an average, files lo = excess > 0; lo > hi is arbiter clause 3 and the answer is 0 W - the battery parked in the billed quarter, which is the failure the memo itself marks fatal. And no config validator can catch it: it is a runtime divergence between two readings, not a config ordering, so CFG-01's shape of check passes on the exact tree that parks the battery. Option A's cost is energy; Option B's cost built too early is the one quarter of the month that sets the bill. THE REVISIT TRIGGER IS ALLOC-01, recorded in §0c. Under ARCH-01's host-side allocator the two claims stop sharing a list: the loop floor becomes a per-inverter `hi` consumed as an INTERVAL at stage A, while the peak floor stays a site `lo` at stage B. Different claim lists, different stages, structurally unable to cross - a stronger argument than the ordering rule, because it makes the crossing unreachable rather than harmless. That is the shape in which Option B becomes safe to build. WHAT HAS TO BE RE-EARNED AT N=2 is stated plainly in §0d rather than left for someone to discover. SAFETY-27 now names five floors across two packs, so "the SoC" stops being a scalar the config can bound. And part 10f - the pin that made SAFETY-25 mergeable - CANNOT EXPRESS TWO PACKS: its dynamic half is a scalar 0-100 % SoC sweep against a single-series capture, and a two-pack exposure lives in the DIFFERENCE between two readings, which that sweep visits at no resolution. Its static half, the AST scan pinning the eight claim sources, still bites at N=2; the dynamic half goes silent. Merging a two-pack reserve on 10f's current green would be merging on a check that cannot see the failure. The options analysis is kept intact on purpose - §1-§7 stand exactly as written, including §5's "(recommended)" on Option B and §6's recommendation, with a new §0 saying what was decided and §6 marked as answered. A memo that recorded the verdict and deleted the reasoning is the failure this DECISIONS/ directory exists to prevent. Part 10e's check moved with the memo: it used to pin the honest "Status: OPEN" line and now pins that the memo names the option, the date and the trigger AND still carries both options and the recommendation. The tripwire itself stays - a ninth claim source in Controller.cycle() still takes 10f red on the line it is written, and "deferred" is precisely the state in which someone builds Option B by accident. Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
442 lines
24 KiB
Python
442 lines
24 KiB
Python
"""SAFETY-18 - the frozen-but-fresh meter detector.
|
|
|
|
WHAT IT CATCHES, in one sentence: a meter that keeps answering 200 OK with a
|
|
document that never changes, which every freshness mechanism in this stack reads
|
|
as perfectly healthy while the loop winds to the rail and stays there.
|
|
|
|
THE FAILURE NEEDS NO FAULT ANYWHERE ELSE. A frozen-but-talking meter is
|
|
*arriving* on every poll, so:
|
|
|
|
- `meter_max_age_s` is structurally blind. Every response resets the arrival
|
|
stamp (p1.py, `HomeWizardLocalSource`), so the age never climbs. Age catches
|
|
a meter that stops TALKING; this one stops CHANGING.
|
|
- firmware layer 1 is fed. Its watchdog keys on setpoint staleness, which the
|
|
heartbeat satisfies, and on `sensor.goodwe_p1_sample_age`, which a talking
|
|
meter satisfies.
|
|
- the arbiter contributes only the device rating and +-`max_w` - it bounds the
|
|
magnitude, which is the number this fault drives us to, not away from.
|
|
- there is no SoC guard on the grid-following loop at all. `soc_floor` belongs
|
|
to the maintenance cycle; the BMS is the sole energy backstop.
|
|
|
|
⚠️ STILL TRUE, AND NOW FILED. SAFETY-24 added `peak_soc_floor` and
|
|
OPT-04 added `arbitrage_soc_floor`, so the sentence above is no longer
|
|
"there is one SoC floor and it is maintenance's" - but neither of the new
|
|
ones binds THIS loop, and `peak_soc_floor`'s name reads as though it does.
|
|
SAFETY-25 replayed the exposure (test_peakguard.py part 10) and recorded
|
|
the options in DECISIONS/SAFETY-25-loop-soc-floor.md. DECIDED 2026-09-02,
|
|
Option A: the BMS is the sole energy backstop for demand-driven discharge
|
|
ON PURPOSE. A loop-side reserve is DEFERRED, not rejected - its revisit
|
|
trigger is ALLOC-01. So the sentence above is a recorded decision, not an
|
|
oversight and no longer an open question.
|
|
|
|
The loop reads a constant error and integrates it. Time from freeze to the rail,
|
|
replaying the real `control.compute()` at 15 s cycles:
|
|
|
|
meter frozen at to rail, max_w 2000 to rail, max_w 5000
|
|
350 W 150 s 360 s
|
|
1000 W 60 s 135 s
|
|
>= 3000 W 30 s 75 s
|
|
|
|
⚠️ THE LIVE INSTALL RUNS `max_w: 5000`, which is both the schema maximum and the
|
|
device rating, so the right-hand column is the one that describes this house.
|
|
|
|
------------------------------------------------------------------------------
|
|
THIS HAS A EURO FIGURE, AND IT IS THE REASON THE TICKET IS P1
|
|
|
|
`maintenance_charge_floor()` caps MAINTENANCE charging against `peak_cap_w`. The
|
|
grid-following loop is not capped by anything but `max_w`. A meter frozen
|
|
reading a large export drives a 5 kW unattended grid IMPORT, and >= 15 minutes
|
|
of that sets the month's billed capaciteitstarief peak: specs.md:583 records a
|
|
measured case where a single 4998 W quarter moved a monthly peak from 4832 W to
|
|
5013 W and billed the whole month at it.
|
|
|
|
⚠️ THIS CUT DOES NOT CAP THAT. It notifies. See DOCS.md, "Capacity-tariff
|
|
exposure of the grid-following loop", and SAFETY-07.
|
|
|
|
------------------------------------------------------------------------------
|
|
WHY IT IS A CONJUNCTION AND NOT AN `unchanged_s` THRESHOLD
|
|
|
|
`unchanged_s` (p1.py) already measures exactly the right thing: seconds since
|
|
the meter served a DIFFERENT measurement, fingerprinted over the power figure
|
|
and both energy registers. It is computed, it is on the status page, and TEL-05
|
|
deliberately refused to threshold it - correctly:
|
|
|
|
this controller regulates grid power toward ~0 W, and at a converged -10 W
|
|
the export register takes about six minutes to advance by its 1 Wh
|
|
resolution while the power figure legitimately repeats.
|
|
|
|
So a bare `unchanged_s > N` false-trips at the exact operating point we aim for,
|
|
and `p1.py` says as much in a note that ends "whoever wires a freeze detector
|
|
must handle the low-power case first". This is that handling, and it is not a
|
|
smaller number:
|
|
|
|
unchanged_s >= hold_s AND |commanded_w| is at the rail
|
|
|
|
The second term is what TEL-05's case cannot satisfy. At the converged point the
|
|
command is nowhere near +-`max_w`; on the 40 minutes of live converged behaviour
|
|
in `sim/scenarios/p1-age-2026-08-26.jsonl.gz` the meter never once leaves
|
|
+-500 W, so the loop never even approaches a 5000 W rail. And the reverse case -
|
|
a command genuinely pinned at the rail by a real 8 kW load - cannot satisfy the
|
|
FIRST term, because a real railed condition means kilowatts still crossing the
|
|
meter, and a kilowatt advances a 1 Wh register every 3.6 s.
|
|
|
|
The two terms fail for independent reasons. That is the whole design.
|
|
|
|
⚠️ AND THE SECOND HALF OF THAT WAS MEASURED ON THE RIG, WITH A RESULT WORTH
|
|
READING CAREFULLY. Driving the real transport against the rig's own hwsim under
|
|
+8000 W of house load - a genuinely railed command, meter perfectly healthy - the
|
|
POWER FIGURE DID NOT MOVE AT ALL: `active_power_w` sat at exactly 10130.0 W for
|
|
26 consecutive polls. What kept `unchanged_s` pinned at 0.0 s was the kWh
|
|
registers advancing, and nothing else.
|
|
|
|
So the register terms in `measurement_fingerprint()` are not belt-and-braces
|
|
here, they are the entire negative case. A freeze detector fingerprinted on the
|
|
power figure alone would have raised a false alarm on that rig run - a healthy
|
|
meter, a real load, a correctly railed command - which is the exact failure mode
|
|
that gets a safety guard switched off. Anyone tempted to simplify the fingerprint
|
|
should read that run first.
|
|
|
|
------------------------------------------------------------------------------
|
|
WHERE `hold_s` COMES FROM
|
|
|
|
Measured on `sim/scenarios/p1-age-2026-08-26.jsonl.gz` - 2399 s (40 min) of the
|
|
live house at the converged operating point, mean grid -14.2 W, 1194 polls:
|
|
|
|
polls that repeated the previous reading 735 of 1193 (61.6 %)
|
|
distinct-reading transitions 458
|
|
median gap between distinct readings 6.0 s
|
|
p95 gap 6.0 s
|
|
LARGEST `unchanged_s` any sample observes 8.0 s
|
|
longest interval serving no distinct reading 15.4 s
|
|
samples outside +-500 W 0
|
|
|
|
The default 300 s is 37x the largest `unchanged_s` this house has been recorded
|
|
producing while converged, and 19.5x the longest interval in which it served no
|
|
distinct reading at all. The two figures differ because the capture has an 11.4 s
|
|
hole in its OWN polling; the second is quoted because it is the pessimistic one.
|
|
300 s is not fitted to either margin - it is picked as "clearly past any
|
|
plausible register-tick interval, and clearly inside the 900 s quarter that bills
|
|
the capacity tariff". test_freeze.py re-measures both every run, so this
|
|
paragraph cannot quietly stop being true.
|
|
|
|
⚠️ BE PRECISE ABOUT WHAT THAT CAPTURE PROVES. It is POWER-ONLY - the shipped
|
|
fingerprint also covers both kWh registers, so a real `unchanged_s` on that data
|
|
can only be shorter, never longer, which makes it a conservative measurement of
|
|
the converged case. But it does NOT on its own refute a bare `unchanged_s`
|
|
threshold, and saying it did would be exactly the overstatement this project
|
|
keeps having to walk back: at 8 s worst, a bare 300 s threshold is silent on it
|
|
too. The case that refutes the bare threshold is the one below, which no capture
|
|
of THIS meter contains because this meter's power figure jitters.
|
|
|
|
The floor on the other side: at the rail, the smallest residual grid flow that
|
|
still ticks a 1 Wh register inside 300 s is 12 W. Any condition that genuinely
|
|
pins this loop at +-5000 W has three orders of magnitude more than that crossing
|
|
the meter.
|
|
|
|
⚠️ AND THOSE TWO NUMBERS DO NOT MERELY HAVE MARGIN - THEY CANNOT BOTH BE TRUE.
|
|
The worry the conjunction has to answer is "a HEALTHY meter whose register is
|
|
slower than `hold_s`". At 300 s that is |grid| < 12 W. The shipped `deadband_w`
|
|
is 15 W, so anywhere the register is that slow the control law is already inside
|
|
its deadband and the command is parked - the rail term is not merely unlikely to
|
|
be true there, it is 0 W. The two terms are mutually exclusive by construction
|
|
at the defaults, not just far apart, and the check re-derives that every run.
|
|
|
|
That relationship is the one to protect. `hold_s` may be lowered only while
|
|
3600/hold_s stays under `deadband_w`; at the schema floor of 60 s that is 60 W
|
|
against a 15 W deadband, and the mutual exclusion is gone. A 60 s `meter_freeze_s`
|
|
is a supported configuration that gives up this argument and keeps only the
|
|
margin - do not set one without a capture that says the margin is enough.
|
|
|
|
⚠️ WHAT `hold_s` DOES NOT BUY IS DETECTION SPEED. The alert lands at
|
|
max(hold_s, time-to-rail) after the freeze, so at the shipped default and
|
|
`max_w: 5000` that is 300-360 s. The rail is REACHED first, from 75 s. A
|
|
notification is not a brake; see the DOCS.md note.
|
|
|
|
------------------------------------------------------------------------------
|
|
THE RAIL TERM, PRECISELY
|
|
|
|
abs(commanded_w) >= RAIL_FRAC * max_w
|
|
|
|
`commanded_w` is the EMITTED setpoint - what the arbiter resolved and
|
|
`write_setpoint()` put on the wire - not the loop's raw wish, for the same
|
|
reason SAFETY-02 uses the emitted value: the wire carries the emitted number.
|
|
|
|
RAIL_FRAC is 0.95 and is a constant rather than an option. The command is
|
|
quantised to `step_w` (max 100), so at the rail the emitted value IS the ceiling
|
|
on every schema-legal combination; the 5 % is quantisation slack, not a tuning
|
|
knob. Making it configurable would offer a way to widen the one term that
|
|
carries the whole no-false-positive argument.
|
|
|
|
⚠️ SAFETY-20 - AND THE CEILING IS NOT `max_w`. THE 5 % USED TO BE DESCRIBED AS
|
|
"slack for a device rating that clips `max_w` slightly in `write_setpoint()`",
|
|
AND THAT SENTENCE WAS THE BUG. 5 % of slack does not absorb a device rating; it
|
|
inverts the guard. `write_setpoint()` clamps the emitted command to `max_w` AND
|
|
THEN to the setpoint device's own `[dev_min, dev_max]` range (clamp.py,
|
|
`clamp_to_rating()`), and the arbiter files the same range as a P_SAFETY limit
|
|
claim, so the largest magnitude that can ever stand on the wire is
|
|
|
|
min(max_w, |dev_min|, |dev_max|)
|
|
|
|
not `max_w`. Measured on the shipped predicate at `max_w: 5000` against a device
|
|
of +-4700 - the exact case the ticket is named for:
|
|
|
|
looks_frozen(unchanged_s=3600, commanded_w=4700, max_w=5000) -> False
|
|
|
|
The command is pinned at the hardware's rail, the meter has been frozen for an
|
|
hour, and term 2 is unsatisfiable BY CONSTRUCTION because 4700 < 4750. Any
|
|
device rating at or below `RAIL_FRAC * max_w` disarms the conjunction outright.
|
|
The status page then printed `armed (...command is over 4750 W)`, which is the
|
|
"disarmed guard that advertises itself as armed" failure validate.py rule 5 and
|
|
SAFETY-15/19 all exist to prevent - so `rail_ceiling_w()` below takes the device
|
|
range and the rail is measured against the smaller number.
|
|
|
|
WHY THE SMALLER OF THE TWO DEVICE BOUNDS, AND NOT A SIDE-AWARE PAIR. The rail is
|
|
a MAGNITUDE test against what clamp.py calls a magnitude clamp - it binds import
|
|
and export identically - so the ceiling here is a magnitude that is available in
|
|
BOTH directions. The alternative considered was a per-sign rail:
|
|
`min(max_w, dev_max)` for a positive command, `min(max_w, |dev_min|)` for a
|
|
negative one. That is arithmetically tighter and it is NOT wrong - on a device
|
|
range of -500..+5000 it would grade a -480 W charge command as railed, which the
|
|
symmetric ceiling reaches only by dropping the discharge rail to 475 W too. It
|
|
was rejected on cost, not on correctness: a per-sign rail is two rails, and two
|
|
rails need two coverage verdicts (`dev_min == 0` is a degenerate charge rail
|
|
whatever the discharge side can do) on a status row that carries one number and
|
|
in a predicate that takes one magnitude. That is a bigger change than this
|
|
defect earns, and the ONLY configuration that distinguishes the two - a device
|
|
range narrower than `max_w` on one side - is refused at startup by CFG-01 (see
|
|
the reachability note below). Between the two, the symmetric ceiling can only
|
|
ever LOWER the rail, which widens term 2 rather than disarming it; term 1
|
|
(`unchanged_s >= hold_s`) is the term carrying the no-false-positive argument,
|
|
and it is untouched. Whoever needs the tighter version should take both status
|
|
rows with it.
|
|
|
|
⚠️ AND WHEN THE CEILING IS ZERO THE RAIL IS NOT "LOW", IT IS GONE. A device that
|
|
accepts no command in one direction at all (`dev_max == 0`, or `dev_min == 0`)
|
|
gives a ceiling of 0 W, and `abs(commanded_w) >= 0` is TRUE FOR EVERY COMMAND
|
|
INCLUDING 0 W. Term 2 would not be disarmed there, it would be degenerately
|
|
true, and the detector would collapse into the bare `unchanged_s > N` threshold
|
|
TEL-05 refused - false-tripping at the converged operating point we aim for.
|
|
That case is reported as NOT COVERED, through the row the unsupported-transport
|
|
case already uses, and `looks_frozen()` returns False rather than firing.
|
|
|
|
⚠️ HOW REACHABLE IS ANY OF THIS - READ THIS BEFORE "SIMPLIFYING" IT AWAY.
|
|
`validate_startup_config()` rule 2 (CFG-01) already REFUSES TO START on
|
|
`max_w > dev_max` or `-max_w < dev_min`, and `run_control()` re-runs that gate
|
|
once ESPHome is up and the real rating is known. So on any install that reaches
|
|
the control loop with a rating it could read, `min(max_w, |dev_min|, |dev_max|)`
|
|
IS `max_w` and everything above is arithmetically dead. That is not an argument
|
|
against it - it is clamp.py's argument for its own second stage, word for word:
|
|
the case where this bites is the case where the startup gate did not run or no
|
|
longer holds (`hass.limits()` returns (None, None) whenever ESPHome is not up,
|
|
and the range checks are then skipped rather than guessed at, so a rating that
|
|
arrives late is never re-read), and a guard that quietly assumes the gate ran is
|
|
a guard that reports armed in exactly the state it cannot fire in. See AC 4's
|
|
decision, recorded in validate.py under WHAT IS DELIBERATELY *NOT* REFUSED.
|
|
|
|
⚠️ NOT GATED ON `following`, and that is deliberate. A maintenance charge
|
|
commands against the meter on purpose and can sit at the rail for hours - but it
|
|
does so while pushing kilowatts through the meter, so the FIRST term is what
|
|
excludes it, and it excludes it on physics rather than on bookkeeping. Gating on
|
|
`following` as well would additionally blind the detector to a maintenance phase
|
|
running against a meter that really has frozen, which is the same fault with a
|
|
worse actuator behind it.
|
|
|
|
------------------------------------------------------------------------------
|
|
NOTIFY, DO NOT TRIP
|
|
|
|
First cut is an alarm and nothing else: an HA persistent notification, an ERROR
|
|
in the log, an event on the status page, and a failed check row. It does NOT
|
|
claim the actuator, does NOT file a P_SAFETY claim and does NOT latch.
|
|
|
|
That is a deliberate ordering of costs, not timidity. A false trip here parks
|
|
the battery - on a house that is running this loop precisely to avoid buying
|
|
power at the wrong moment - and the operator's response to a parked battery is
|
|
to switch the guard off. A false notification costs one alert. The trip is a
|
|
separate decision that has to be earned with observed data from a real install,
|
|
and it needs an answer to a question this cut does not have one for: what should
|
|
the loop do instead, given that 0 W is itself a grid import of whatever the
|
|
house is drawing.
|
|
|
|
⚠️ TRANSPORT-CONDITIONAL. `unchanged_s` exists ONLY on `homewizard_local`,
|
|
because it is the only transport that sees the meter's own document. Under
|
|
`ha_dsmr`, `mqtt_p1`, `ha_signed` and `meter_source: off` this detector is
|
|
silent and the exposure above is uncovered. The caller passes None and gets
|
|
False; there is no half-measure available on those paths, and pretending
|
|
otherwise would be worse than the gap.
|
|
"""
|
|
|
|
from dataclasses import dataclass
|
|
from datetime import datetime
|
|
|
|
from .clamp import is_commandable
|
|
|
|
# See "THE RAIL TERM, PRECISELY" above. A constant, on purpose.
|
|
RAIL_FRAC = 0.95
|
|
|
|
|
|
@dataclass(frozen=True)
|
|
class FreezeWatchdogConfig:
|
|
"""Default, not a constant - config.yaml carries `meter_freeze_s`."""
|
|
|
|
hold_s: float = 300.0
|
|
|
|
|
|
def rail_ceiling_w(max_w, *, dev_min=None, dev_max=None) -> float:
|
|
"""The largest command magnitude that can actually stand on the wire.
|
|
|
|
SAFETY-20, and the whole point of the ticket: this is NOT `max_w`. The
|
|
emitted command is bounded by `max_w` AND by the setpoint device's own
|
|
`[dev_min, dev_max]` range - twice, in `clamp_to_rating()` and again as the
|
|
arbiter's `device` P_SAFETY limit claim - so the reachable ceiling is the
|
|
smallest of the three magnitudes. See "THE RAIL TERM, PRECISELY" for why it
|
|
is the smaller of the two device bounds rather than a per-sign pair, and for
|
|
why this is arithmetically dead on any install CFG-01 let start.
|
|
|
|
`dev_min` / `dev_max` are `hass.limits()`'s answer and are None whenever
|
|
ESPHome could not be reached. UNKNOWN IS NOT ZERO: a missing bound means
|
|
this add-on applies no device clamp at all on that side (clamp.py's second
|
|
stage is skipped unless BOTH are known), so an unknown bound must not lower
|
|
the ceiling. `is_commandable()` is write_setpoint()'s own predicate, reused
|
|
rather than retyped: a NaN rating must not become a 0 W ceiling.
|
|
|
|
Returns 0.0 when the device can command nothing - see rail_unreachable().
|
|
"""
|
|
ceiling = abs(float(max_w))
|
|
for bound in (dev_min, dev_max):
|
|
if is_commandable(bound):
|
|
ceiling = min(ceiling, abs(float(bound)))
|
|
return max(0.0, ceiling)
|
|
|
|
|
|
def rail_unreachable(max_w, *, dev_min=None, dev_max=None) -> str:
|
|
""""" when the rail is a real threshold, else WHY it is not. SAFETY-20 AC2.
|
|
|
|
The status page renders this as a NOT COVERED row - the same row, for the
|
|
same reason, that an unsupported transport already gets. It is a second
|
|
reason to use that surface, not a new mechanism: in both states the honest
|
|
report is "this guard is not watching", and the one thing this project has
|
|
decided repeatedly it will not ship is a page that says `armed` instead.
|
|
|
|
⚠️ THE UNREACHABLE CASE IS NOT "THE RAIL IS HIGH", IT IS "THE RAIL IS 0 W".
|
|
A ceiling of zero makes `abs(commanded_w) >= 0` true for every command
|
|
including a parked 0 W one, so term 2 is not disarmed but DEGENERATELY TRUE,
|
|
and the conjunction decays into the bare `unchanged_s > N` threshold TEL-05
|
|
refused - which false-trips at the converged operating point this controller
|
|
aims for. Silence plus a NOT COVERED row is strictly better than that.
|
|
"""
|
|
if not max_w or not is_commandable(max_w):
|
|
return (f"max_w is {max_w!r}, so there is no ceiling to measure a rail "
|
|
f"against")
|
|
if rail_ceiling_w(max_w, dev_min=dev_min, dev_max=dev_max) > 0.0:
|
|
return ""
|
|
return (f"the setpoint device reports a range of {dev_min}...{dev_max} W, "
|
|
f"which leaves no command magnitude available in both directions, "
|
|
f"so the rail term would be true of every command including 0 W")
|
|
|
|
|
|
def rail_w(max_w, *, dev_min=None, dev_max=None) -> float:
|
|
"""The magnitude at or above which a command counts as railed.
|
|
|
|
Measured against the REACHABLE ceiling, not against `max_w` - SAFETY-20.
|
|
Callers that do not know the device range pass none and get the old
|
|
behaviour, which is correct precisely when there is no device clamp to
|
|
account for.
|
|
"""
|
|
return rail_ceiling_w(max_w, dev_min=dev_min, dev_max=dev_max) * RAIL_FRAC
|
|
|
|
|
|
def looks_frozen(unchanged_s, commanded_w, max_w,
|
|
cfg: FreezeWatchdogConfig, *, dev_min=None, dev_max=None) -> bool:
|
|
"""The predicate, and the ONLY place the conjunction is written down.
|
|
|
|
Public for the same reason `watchdog.disagrees()` is: the checks that grade
|
|
it must assert on THE SHIPPED EXPRESSION. A safety predicate transcribed
|
|
into its own test is one copy plus a future disagreement about what the
|
|
check means, and the copy that drifts is always the one doing the grading.
|
|
|
|
`unchanged_s` seconds since the meter served a different measurement, or
|
|
None on a transport that cannot know (see the module note).
|
|
`commanded_w` the EMITTED setpoint standing on the wire.
|
|
`max_w` the configured output bound.
|
|
`dev_min` / the setpoint device's own reported range, or None when it
|
|
`dev_max` could not be read. SAFETY-20: the rail is measured against
|
|
`min(max_w, |dev_min|, |dev_max|)`, because that - not
|
|
`max_w` - is what the wire can carry.
|
|
|
|
⚠️ THE DEVICE BOUNDS ARE KEYWORD-ONLY AND DEFAULT TO None, WHICH IS THE
|
|
CONSERVATIVE DIRECTION AND ALSO THE HONEST ONE. A caller that does not know
|
|
the rating gets a rail measured against `max_w` - correct, because when this
|
|
add-on has no rating it applies no device clamp either (clamp.py's second
|
|
stage needs both bounds), so `max_w` really is the ceiling on that path.
|
|
"""
|
|
if unchanged_s is None or commanded_w is None or not max_w:
|
|
return False
|
|
# SAFETY-20. A ceiling of 0 W would make term 2 true of EVERY command; that
|
|
# is the degenerate case, not the armed one. Silence, and the status page
|
|
# says NOT COVERED - see rail_unreachable().
|
|
if rail_unreachable(max_w, dev_min=dev_min, dev_max=dev_max):
|
|
return False
|
|
return (float(unchanged_s) >= cfg.hold_s
|
|
and abs(float(commanded_w))
|
|
>= rail_w(max_w, dev_min=dev_min, dev_max=dev_max))
|
|
|
|
|
|
class FreezeWatchdog:
|
|
"""One instance per controller, evaluated once per control cycle.
|
|
|
|
Level-triggered state with an EDGE for the alarm: `evaluate()` returns True
|
|
on the cycle the conjunction first becomes true and False on every cycle
|
|
after, so the caller raises one notification per episode rather than one
|
|
every second. `active` is the level, for the status page.
|
|
|
|
No latch, deliberately - see "NOTIFY, DO NOT TRIP". A latch exists so a trip
|
|
cannot erase its own evidence by working; nothing here acts, so there is
|
|
nothing to erase. When the meter starts moving again the alert clears
|
|
itself, which is the honest report of the state.
|
|
"""
|
|
|
|
def __init__(self, cfg: FreezeWatchdogConfig | None = None):
|
|
self.cfg = cfg or FreezeWatchdogConfig()
|
|
self.active = False
|
|
self.since: datetime | None = None
|
|
self.reason = ""
|
|
self.episodes = 0
|
|
|
|
def evaluate(self, unchanged_s, commanded_w, max_w, now: datetime, *,
|
|
dev_min=None, dev_max=None) -> bool:
|
|
"""Advance one cycle. Returns True ONLY on the rising edge.
|
|
|
|
`now` is the caller's clock so this stays testable and replayable - the
|
|
same discipline as `SignWatchdog.evaluate()`. `dev_min`/`dev_max` are
|
|
the setpoint device's reported range; see looks_frozen().
|
|
"""
|
|
if not looks_frozen(unchanged_s, commanded_w, max_w, self.cfg,
|
|
dev_min=dev_min, dev_max=dev_max):
|
|
self.active = False
|
|
self.since = None
|
|
self.reason = ""
|
|
return False
|
|
|
|
# ⚠️ SAFETY-20. THE REASON QUOTES THE CEILING IT ACTUALLY USED, not
|
|
# `max_w`. The old line said "at the 5000 W rail (... command over
|
|
# 4750 W)" on an install whose device stopped at 4700 W, i.e. it named
|
|
# a threshold the command could not reach - the same untruth the status
|
|
# page was telling, printed into the log and the HA notification where
|
|
# it would outlive the page.
|
|
ceiling = rail_ceiling_w(max_w, dev_min=dev_min, dev_max=dev_max)
|
|
capped = ("" if ceiling >= abs(float(max_w))
|
|
else f", capped from max_w {float(max_w):.0f} W by the "
|
|
f"setpoint device's own rating")
|
|
self.reason = (
|
|
f"METER_FROZEN: the meter has answered {float(unchanged_s):.0f} s "
|
|
f"without its measurement changing while the command stands at "
|
|
f"{float(commanded_w):+.0f} W, at the {ceiling:.0f} W rail{capped} "
|
|
f"(limits: unchanged over {self.cfg.hold_s:.0f} s, command over "
|
|
f"{rail_w(max_w, dev_min=dev_min, dev_max=dev_max):.0f} W)")
|
|
if self.active:
|
|
return False
|
|
self.active = True
|
|
self.since = now
|
|
self.episodes += 1
|
|
return True
|