At the BMS cut-out the saturation freeze held the last request for hours (+5000 W for 11.87 h on 09-06, +1940 W for 3 h 55 m on 09-19) until the grid error changed sign. compute() now carries a refused direction: after SETTLE_CYCLES of a ~0 W reading against a larger ask it holds that direction at 0 W, probes 200 W (below the gate's 250 W) every 15 minutes, and lets go on charge, an answered probe, stop/start or another writer. A stale-reading trip on a frozen ~0 W reading seeds the same hold, which ends SAFETY-59's ~70 s cycle. One inverter only; no SoC in the loop (SAFETY-25 Option A). test_refusal.py drives the real Controller and gate; tools/replay_refusal.py replays the 16-day capture. test_clamp.py and test_delivery.py re-baselined where they asserted the old hold. DECISIONS/SAFETY-52 has the record and what SAFETY-58/59 must take into account. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
4.5 KiB
SAFETY-52 - a battery that refuses is asked for 0 W
Decided 2026-09-27 by the owner, on the phase A plan (option D3). All four questions answered yes.
The defect
At the BMS cut-out the battery gives ~0 W whatever it is asked. The saturation
freeze (control.py, frozen) then holds the request where it stood, and its
SAFETY-13 exit cannot fire, because a reading of ~0 against a large ask lies
inside the interval a limit can produce. The request stood at +5000 W for
11.87 h on 2026-09-06 and at +1940 W for 3 h 55 m on the bus on 2026-09-19. It
moved again only when the grid error changed sign. SAFETY-48's lead cap only
changes where i_w parks (one slew step ahead instead of at the rail). When
the request moved after the reading went flat, the stale-reading gate won
instead and ran SAFETY-59's ~70 s trip cycle.
What was decided
- A refused direction is held at 0 W, reason
battery refuses. It engages incompute()when the freeze has heldSETTLE_CYCLESand the reading is withinsaturation_wof 0 against an ask beyond it. The drop to 0 skips the slew limit (it only removes an ask nobody meets). The direction is carried likesat_count(refused=,Decision.refused). - A 200 W probe every 15 minutes, 34 s long (
PROBE_W,PROBE_EVERY_S,PROBE_S; twiceBATT_OBLIGED_S). An answer of at least 100 W ends the refusal. 200 W is belowfreshness.MOVE_W(250 W), so a probe cannot arm the gate. The clock is main.py'snow_mono;compute()stays clockless. - A gate trip while the loop is frozen on a ~0 W reading is a refusal for
control (
Controller._refusal_from_stale). This is what stops the ~70 s cycle. The log keeps SAFETY-56's two-explanation wording. - No SoC in the loop. SAFETY-25 Option A stands. Nothing reads SoC.
Other exits: the loop wants the other direction (charge is accepted at the floor), control stopped or started, another writer on the wire (the arbiter reseed). A gap in the readings keeps the refusal, because the gate's own stop is what seeds it.
One inverter only. At N>1, OPT-09's pack limit already closes an empty
battery's discharge end and moves its share. There, a one-unit gate trip must
not refuse the site. compute() is passed refused=None there, and that path
is release/1.0's law unchanged (the i_w=None equivalence sweep in
test_control.py still holds).
Evidence
test_refusal.py drives the real Controller and gate (the 09-06 and 09-19
shapes, recovery with no sign change, the probe cadence, every exit).
tools/replay_refusal.py replays the 16-day capture, same model as
replay_recorded_loop.py, and should be read for deltas:
| plant | law | gate trips | request >1 kW above delivery | longest held | import / export kWh | worst 15-min |
|---|---|---|---|---|---|---|
| fitted | old | 85 | 113.3 h | 16.57 h | 112.0 / 35.2 | 3434 W |
| fitted | new | 130 | 11.4 h | 0.21 h | 112.3 / 35.4 | 3456 W |
| offset 0 W | old | 1010 | 102.2 h | 16.58 h | 112.0 / 35.2 | 3434 W |
| offset 0 W | new | 85 | 6.1 h | 0.33 h | 111.9 / 35.1 | 3434 W |
The +22 W worst quarter and the +45 trips on the fitted plant follow the fit's -22 W offset, which slowly charges the modelled pack above its floor while the hold stands. With the offset at 0 both vanish. That is inferred from these two rows and was not traced further. Rejected alternatives and their figures are in the phase A plan: bounding the integrator by demand made the worst quarter +541 W worse or cycled the gate 3368 times, and an SoC envelope needs the configured floor to be right and needs SoC.
Not covered
A battery that gives a steady part of the ask (e.g. a 500 W keep-alive) is a genuine limit (SAFETY-13 case a) and still holds its request.
What SAFETY-58 and SAFETY-59 must take into account
- SAFETY-58 (the first read after a rest trips at once): a probe never arms
the gate (200 < 250 W), but the refusal seeding reads the trip. If 58 delays
the first verdict, the seed arrives later. The 09-19 shape then needs the
compute-side engagement (12 cycles) to win, which it does only while the
request stands still. Keep
test_refusal.pypart 4 green. - SAFETY-59 (DOCS says a ~70 s pattern proves a failed register): with this
change a refusing battery no longer produces the pattern at one inverter. The
DOCS text should say so, and that the
battery refusesreason is the discriminator the add-on now has. At N>1 the old pattern can still occur. - If either changes
MOVE_W,PROBE_Wmust stay below it.test_refusal.pypart 2 checks the inequality.