SAFETY-57: the stale-reading verdict gets an exit, because its own consequence is what stopped it being tested
SAFETY-37's freshness gate reports a battery-power register as MISSING when it
stops following its own command, and a missing input is "command 0 W and keep
commanding" (§11.1 rule 1). The gate's only exit was "an arrival carrying a
DIFFERENT number" - and at 0 W nothing is asking the register to be anywhere.
The state had no exit reachable from inside it, and the log line promised the
opposite in the same sentence that announced the 0 W.

REPRODUCED FROM THE WIRE, NOT MODELLED. scenarios/safety57-2026-09-21/ is 3840
verbatim frames off the RS-485 pair, read from the passive sniffer, decoded by
tools/decode_bus_capture.py (0 unparsed, 0 bad CRC, 0 unknown shapes; the
mode->sign convention is graded off the capture, not trusted). The box was
running 0.10.0, so the 0 W in the trace IS the add-on's own claim:

  10:51:24.7  0x0518 reaches -3 W. Pack at 11 %, the BMS refuses the discharge,
              the inverter idles. THE REGISTER IS HEALTHY AND TRUTHFUL.
  10:51:29.7  the command reaches +1060 W - 800 W of travel
  10:52:00    the conjunction arms. Inverter.batt becomes None
  10:52:21.7  the site commands 0 W, on the wire
  ...         0x0518 does not change value for 850.0 s. The setpoint does not
              change value for 790.0 s. The house exports 2.4 kW throughout
  ~11:04      a human restarts the add-on. That is what ends it

AND IT HAD BEEN ESCAPING BY LUCK. Replaying the committed 16-day loop capture
through the shipped conjunction finds 93 trips whose wait for the BMS
keep-alive pulse that cleared them has a median of 143.4 s, a worst case of
21440.1 s, and 17 of 93 at or beyond this episode's 710 s. That distribution
belongs to the battery's firmware, not to this code.

THE CARD'S OPTION 2 ALREADY HELD AND IS NOT THE BUG. _grade() has required
|standing| >= MOVE_W since SAFETY-37. The trip was at +1060 W and the stuck
state is at 0 W; they are different moments, and an entry-side rule cannot
reach a state entered legitimately and then persisted. Nothing in the
conjunction is weakened here.

THE RULE, SAFETY-13's SHAPE ONE MODULE OVER - which latches get an exit, not
how long the block lasts:

  the verdict is withdrawn when the obligation that produced it has been gone
  for RELEASE_S, and the register is then re-graded from scratch.

RELEASE_S is BATT_OBLIGED_S, 17.0 s - the obligation window already derived in
the file (6.0 plant + 10.0 publish + 1.0 read), taken at the FLOOR of its band
for the mirror of MOVE_W's reason. Which half is safe is the opposite of
SAFETY-13's: being wrong long is the failure being fixed, being wrong short
costs one bounded re-grading window. Below 17 s the release pre-empts the
cheaper exit - the register answering by itself - and that is graded
behaviourally, not asserted.

The whole parked interval is now stale_input_s + RELEASE_S = 32 s. On the live
episode: telemetry back at 10:52:39 instead of 11:05:35, with 0x0518 still
answering the same -3 W. RED BEFORE (release_s=inf, a graded counterfactual and
not a second implementation), GREEN AFTER.

WHAT IT COSTS, AND IT IS NOT SMALL. A register dead for good is re-graded for
ever: over 1201 reads the held number reaches a consumer on 630 (52.5 %)
against 35 (2.9 %) before. Payable only because one window is at most 35 s and
the two consumers hold for 75 s and 85 s, so neither can reach a verdict inside
one and the re-trip clears both windows. No detection SAFETY-37 had is given
back - a permanent None clears the same windows for ever too - and the command
is derived from the P1 meter, never from batt.

Two clocks, deliberately: changed_mono/unchanged_s() stay facts about the
REGISTER, graded_from/graded_s() are the VERDICT's window. Collapsing them
either lies to the operator or defeats the re-grading.

main.py's stale line had its ESCAPE CLAUSE corrected - it promised a clearance
the state could not produce - and gained a STALE WITHDRAWN edge that says in
its own words that nothing has been learned about the register. The DIAGNOSIS
half is SAFETY-56's and is deliberately untouched, with a named check asserting
it is still there so that rewrite has to be deliberate.

Battery: 22 mutations, 21 red, 1 argued equivalent, 0 unexplained survivors.
Two findings kept in DECISIONS: _release()'s move_w test swapped for
unchanged_s SURVIVED at +5 B because every fixture rested at exactly 0 W (habit
11, closed by a 0/100/300 W fixture); and the code shipped a habit-22 comment
claiming the _release/_grade order was load-bearing, which the battery
falsified - the two act on mutually exclusive predicates, so the order is not
observable. MUTATION.md gains habit 23 for a mutation that ran, fingerprinted
clean, and was a no-op on the fixture because `0.0 or x` is x.

Suite: 30/30 in the CI image, checks.yml's exact command, purged tree, :ro, one
file at a time.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-21 12:33:56 +02:00

221 lines
9.3 KiB
Python

#!/usr/bin/env python3
"""SAFETY-57 - turn a passive RS-485 capture into the three series the loop sees.
`python3 tools/decode_bus_capture.py scenarios/safety57-2026-09-21/bus-a-*.log.gz`
WHY THE RAW CAPTURE IS WHAT IS COMMITTED, AND NOT A DECODED TABLE. The other
scenario directories in this repository hold Home Assistant recorder exports -
a number per row, already interpreted. This one holds MODBUS FRAMES off the
wire, because the episode it records is one in which the add-on's own view and
the wire's disagree, and a decoded table would be this decoder's opinion with
the evidence thrown away. MUTATION.md habit 8: a committed transcript is a
check, and a check has to be re-derivable from something.
WHAT THE CAPTURE IS. `sniffer@192.168.2.167` is a passive listener on the
RS-485 pair between the ESP32 master and the GW5000S-BP. It writes nothing; it
has no address on the bus. Every line is one frame it heard:
a|10:51:29.695 ok F7 10 05 6E 00 02 04 00 03 04 24 ...
^ ^ ^ ^
| | | the frame, hex
| | CRC verdict as the capture tool computed it
| local wall clock, Europe/Brussels, no date - see `decode()`
bus label
THE FOUR FRAME SHAPES THIS FILE UNDERSTANDS, and it deliberately understands no
others - an unrecognised frame is COUNTED and dropped, never guessed at:
F7 03 <addr:2> <count:2> <crc:2> a read REQUEST
F7 03 <2*count> <data...> <crc:2> its response, matched to the request
immediately preceding it
F7 10 05 6E 00 02 04 <data:4> <crc:2> a write of the two EMS registers
F7 10 05 6E 00 02 <crc:2> the inverter's echo of that write
⚠️ THE SETPOINT IS A MODE AND A MAGNITUDE, NOT A SIGNED NUMBER, and getting
that backwards is the one way this decoder could quietly invert the whole
episode. `0x056E` is the EMS mode and `0x056F` the magnitude in watts,
unsigned. Mode 2 is charge and mode 3 is discharge, and that is READ OFF THIS
CAPTURE rather than off a datasheet: in the committed window, every
`mode 2, 2170 W` write is followed within one 10 s publish by an 0x0518
reading near **-2287 W**, and `mode 3, 1060 W` by a POSITIVE-side idle. The
add-on's own sign convention (`Inverter.standing_w()`, + = discharge) is
therefore `+magnitude` for mode 3 and `-magnitude` for mode 2, and
`test_freshness.py` part 10a grades that correspondence on the capture itself
rather than trusting this paragraph.
WHAT THIS DECODER CANNOT SEE, largest hole first (habit 13/16):
* **THE GRID METER.** It is not on this bus - it is a P1 telegram on a
different wire - so nothing here says what the site was importing or
exporting. The 2.4 kW export during the episode is from the operator's
Home Assistant history and is NOT re-derivable from this file.
* **WHAT THE ADD-ON BELIEVED.** The capture is the wire. It shows the
commands that arrived and the readings that were answered; it does not show
`Inverter.batt`, `inputs_ok`, or any log line. Everything about the add-on's
internal state in this episode is INFERRED by replaying the shipped modules
against these series, which is what part 10 does.
* **DATE AND YEAR.** The capture tool stamps a time of day and nothing else.
The date is supplied by the caller and is recorded in the scenario's
`manifest.json` beside the sha256 of the file it came from.
* **A FRAME THE CAPTURE TOOL SCORED BAD.** Lines whose CRC verdict is not
`ok` are counted and dropped. In the committed window there are none.
* **ANY OTHER REGISTER.** 0x0511 (a two-register read this master issues) is
recognised as a read and its values are returned untouched under its own
address; nothing here claims to know what it means.
"""
import gzip
import io
import re
import sys
# The registers this file will name. Anything else is returned by raw address.
REG_SETPOINT_MODE = 0x056E # written as a pair with 0x056F
REG_BATT_W = 0x0518 # S16, watts, + = discharge (SAFETY-37)
REG_SOC_PCT = 0x050E # U16, percent
MODE_CHARGE, MODE_DISCHARGE = 2, 3
_LINE = re.compile(r"^(\w+)\|(\d\d):(\d\d):(\d\d(?:\.\d+)?)\s+(\S+)\s+(.*)$")
def signed_setpoint_w(mode: int, magnitude: int) -> float:
"""The EMS pair as `Inverter.standing_w()` spells it: + = discharge.
⚠️ AN UNKNOWN MODE RAISES rather than defaulting. A default here would turn
a firmware that started using a third mode into a silently mis-signed
series, which is the failure this whole scenario is about one layer down.
"""
if mode == MODE_DISCHARGE:
return float(magnitude)
if mode == MODE_CHARGE:
return -float(magnitude)
raise ValueError(f"unknown EMS mode {mode} at 0x{REG_SETPOINT_MODE:04X}; "
f"this decoder knows {MODE_CHARGE} (charge) and "
f"{MODE_DISCHARGE} (discharge) only")
def _s16(v: int) -> int:
return v - 65536 if v >= 32768 else v
def decode(path):
"""Decode one capture file. Returns `(events, stats)`.
`events` is a list of `(t, kind, value)` in capture order, where `t` is
SECONDS SINCE LOCAL MIDNIGHT (the capture carries no date) and `kind` is
one of `"setpoint_w"`, `"batt_w"`, `"soc_pct"`, or `"reg_0xNNNN"`.
`stats` counts every line by what became of it, so a caller can assert that
the frames it cares about were actually present rather than that the parse
produced no error.
"""
opener = gzip.open if str(path).endswith(".gz") else io.open
events = []
stats = {"lines": 0, "unparsed": 0, "bad_crc": 0, "requests": 0,
"responses": 0, "writes": 0, "write_echoes": 0, "unknown": 0}
pending = None # the read request awaiting its response
with opener(path, "rt") as fh:
for line in fh:
line = line.strip()
if not line:
continue
stats["lines"] += 1
m = _LINE.match(line)
if not m:
stats["unparsed"] += 1
continue
_bus, hh, mm, ss, verdict, hexs = m.groups()
if verdict != "ok":
stats["bad_crc"] += 1
continue
t = int(hh) * 3600 + int(mm) * 60 + float(ss)
try:
b = [int(x, 16) for x in hexs.split()]
except ValueError:
stats["unparsed"] += 1
continue
# --- a read request: remember it so its response can be addressed
if len(b) == 8 and b[1] == 0x03:
pending = ((b[2] << 8) | b[3], (b[4] << 8) | b[5])
stats["requests"] += 1
continue
# --- a read response, addressed by the request before it
if (b[1] == 0x03 and pending is not None and len(b) >= 5
and b[2] == 2 * pending[1] and len(b) == b[2] + 5):
data = b[3:3 + b[2]]
regs = [(data[i] << 8) | data[i + 1]
for i in range(0, len(data), 2)]
addr = pending[0]
pending = None
stats["responses"] += 1
if addr == REG_BATT_W:
events.append((t, "batt_w", float(_s16(regs[0]))))
elif addr == REG_SOC_PCT:
events.append((t, "soc_pct", float(regs[0])))
else:
events.append((t, f"reg_0x{addr:04X}", tuple(regs)))
continue
# --- a write of the EMS pair
if (len(b) > 8 and b[1] == 0x10 and b[2] == 0x05 and b[3] == 0x6E
and b[6] == 4):
data = b[7:11]
mode = (data[0] << 8) | data[1]
mag = (data[2] << 8) | data[3]
events.append((t, "setpoint_w", signed_setpoint_w(mode, mag)))
stats["writes"] += 1
continue
if len(b) == 8 and b[1] == 0x10:
stats["write_echoes"] += 1
continue
stats["unknown"] += 1
return events, stats
def series(events, kind):
"""`[(t, value)]` for one kind, in capture order."""
return [(t, v) for t, k, v in events if k == kind]
def held_at(rows, t):
"""The last value at or before `t`, or None before the first row.
This is how the add-on sees an entity: Home Assistant answers with whatever
the publisher last put there, and a value that has not been re-published is
still the value. See `freshness.py` on why that is the whole problem.
"""
out = None
for ts, v in rows:
if ts > t:
break
out = v
return out
def _hms(t):
return f"{int(t // 3600):02d}:{int(t % 3600 // 60):02d}:{t % 60:06.3f}"
def main(argv):
if len(argv) != 2:
print(__doc__.splitlines()[2].strip())
return 2
events, stats = decode(argv[1])
print(f"== {argv[1]}")
for k, v in stats.items():
print(f" {k:14} {v}")
for kind in ("setpoint_w", "batt_w", "soc_pct"):
rows = series(events, kind)
if not rows:
continue
changes = [r for i, r in enumerate(rows)
if i == 0 or r[1] != rows[i - 1][1]]
print(f"== {kind}: {len(rows)} frames, {len(changes)} changes, "
f"{_hms(rows[0][0])} .. {_hms(rows[-1][0])}")
for t, v in changes:
print(f" {_hms(t)} {v:+10.1f}")
return 0
if __name__ == "__main__":
sys.exit(main(sys.argv))