glenn schrooyenandClaude Opus 5 1b343da8e3 DOCS: say plainly that ha_dsmr and mqtt_p1 have never seen real hardware
No meter in this installation uses either transport. Both were written to
specs.md 5.2's assumption that a Belgian P1 exposes two unsigned registers,
which the meter actually fitted here does not - it is the HomeWizard P1 that
ha_signed reads. Their only coverage is test_p1.py and an end-to-end test
against a fake Home Assistant.

Deliberately not called "experimental". That word says the design is
unfinished, which is not the defect and is vaguer than the truth; these are
complete and reviewed, they have simply never had a real telegram through
them. The failure this note is guarding against is a future session debugging
a meter problem, treating those two paths as proven, and looking elsewhere.

Placed where the mode is chosen rather than in a footnote, because the choice
is the decision it should inform.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa
2026-08-25 17:35:11 +02:00

16 KiB
Raw Permalink Blame History

GoodWe RS485 Controller

Drives a GoodWe ES/BP battery inverter over its RS485 meter bus: holds net grid exchange at zero, and runs a monthly battery maintenance cycle so the BMS can balance cells and recalibrate its coulomb counter.

Installers: read FIELD-GUIDE.md in the repository. It is not optional reading — it contains the commissioning gates and the failure modes.

Before you start

You need:

  • A GoodWe ES / BP family inverter (AA55 / RS485 meter-bus generation)
  • The vendor's meter-emulating controller disconnected from the bus
  • A T-CAN485 (ESP32) flashed with firmware/goodwe-master.yaml
  • A grid-power sensor already working in Home Assistant, updating every ~510 s

The safety model, in short

The inverter holds its last command forever — it has no meter-timeout. So:

  • The ESP32 commands 0 W if this add-on stops refreshing for ~30 s, and keeps commanding it.
  • This add-on commands 0 W when its inputs go missing, when you stop control, and when it shuts down.
  • The optional RS485 e-stop is the only thing that covers this machine dying. Without it, a failed host leaves the battery latched at its last command until someone intervenes.

If anything looks wrong: stop the add-on. That commands 0 W and the hardware holds it there.

Configuration

Sources

option required meaning
meter_entity yes Net grid power. Positive must mean importing
meter_invert Flip the sign if the meter reports the other way
soc_entity yes Battery state of charge — use the ESP32's own read
batt_entity yes Battery power — again the ESP32's read, + = discharging
batt_invert Flip if needed
setpoint_entity yes The ESPHome number.*_goodwe_setpoint_w

Use the ESP32's readings rather than the inverter's cloud or dongle sensors: those serve cached values, and a stale reading here ends the maintenance charge phase having charged nothing.

P1 meter ingestion

meter_entity above expects one signed sensor, which usually means a template someone wrote by hand. Setting meter_source moves the whole derivation into the add-on, where it is done once and tested, and replaces meter_entity entirely.

Which mode you want depends on what your P1 reader publishes, and there are two shapes in the wild:

  • Two unsigned registers, consumption and injection, which is what a Belgian P1 read over DSMR gives you → ha_dsmr, or mqtt_p1 for a bridge. The add-on subtracts them.
  • One signed figure, positive = import and negative = export, which is what a HomeWizard P1 gives you (sensor.p1_meter_active_power) → ha_signed. The add-on splits it. ha_dsmr cannot read this: it wants two registers and rejects a negative one outright, which is every exporting telegram.

Either way, do not build the missing shape out of template sensors. The point of meter_source is that the sign convention is derived in one tested place rather than in YAML nobody reviews underneath a safety input.

⚠️ ha_dsmr and mqtt_p1 have never processed a telegram from real hardware. No meter in this installation uses either one. Both were written to the assumption in specs.md §5.2 that a Belgian P1 exposes two unsigned registers, and the meter actually fitted here does not — it is the HomeWizard P1 that ha_signed reads. They are covered by the unit checks in test_p1.py and by an end-to-end test against a fake Home Assistant, and nothing more.

This is recorded because the realistic way it bites is someone debugging a meter problem months from now treating those two paths as proven and looking for the fault elsewhere. If you are the first person to point one at a real meter, expect to find something, and please update this note when you do.

option default meaning
meter_source off off keeps meter_entity. ha_dsmr subscribes to the DSMR integration over the HA WebSocket; mqtt_p1 reads a topic; ha_signed subscribes to one signed entity over the HA WebSocket
meter_phases 1 1 or 3. Must match the telegram, or every telegram is rejected and logged
meter_max_age_s 30 Beyond this the reading is stale and grid power reads as missing. On its own it does not command 0 W — see the timing note below. It is also the longest a reading is held forward into the 15-minute average
meter_mqtt_topic mqtt_p1 only
p1_import_entity The unsigned consumption sensor. Do not point this at a signed template
p1_export_entity The unsigned injection sensor
p1_phase_import_entities [] L1..L3, in order. Needed for the capacity-tariff peak on a three-phase connection
p1_phase_export_entities [] L1..L3, in order
p1_net_entity ha_signed only. The signed net-power sensor: + import, - export
p1_phase_net_entities [] ha_signed only. L1..L3, in order, each signed the same way. Needed for the capacity-tariff peak on a three-phase connection. The list length must equal meter_phases

Both per-phase lists are checked against meter_phases once at startup: a list of the wrong length disables P1 ingestion with an error in the log, rather than letting every telegram fail its phase-count check one at a time. Leaving the list empty is fine and is not an error — you simply get no per-phase figures, and therefore no capacity-tariff peak. On a three-phase connection that is a much bigger omission than it looks: on a surveyed reading here the phases carried 2769 W of import while the connection netted 187 W, so the billed quantity is understated roughly fifteenfold if the phases are missing.

How long a dead meter takes to reach 0 W

meter_max_age_s and stale_input_s stack. They are two different clocks and neither one is the whole answer:

step option default
telegrams stop, P1 sample goes stale, grid power starts reading missing meter_max_age_s 30 s
inputs have been missing long enough for the loop to command 0 W stale_input_s 15 s
total, meter death → 0 W commanded by this add-on 45 s

So in P1 mode stale_input_s is not "how long inputs may be missing before commanding 0 W" measured from the meter dying — it is measured from the moment the P1 sample already went stale. Size the pair together: the ESP32's own watchdog commands 0 W after ~30 s of silence from this add-on regardless, and that layer is unaffected by either option.

There is no fallback to an inverter-side power figure, deliberately. The inverter's own AC power tracks its battery almost perfectly and the real meter hardly at all, so a controller that failed over to it would be regulating against its own output while looking healthy.

The mqtt_p1 payload is one JSON object per telegram, and the schema is strict — a key it does not recognise is a telegram from something other than what was tested, and guessing a key here means guessing a kilowatt:

{"import_w": 1234.0,
 "export_w": 0.0,
 "phases": [{"import_w": 500, "export_w": 0},
            {"import_w": 400, "export_w": 0},
            {"import_w": 334, "export_w": 0}],
 "timestamp": "2026-08-24T18:00:05+02:00"}

phases and timestamp are optional; timestamp must carry a UTC offset. Where it is present it is used for the age, which is what stops a retained message replayed on reconnect from presenting a ten-minute-old reading as current.

sensor.p1_sample_age_s

Published over MQTT discovery whenever a broker is available: seconds since the newest accepted telegram, refreshed every second rather than only when a telegram lands. The ESP32's stale-input watchdog subscribes to this exact entity id, so do not rename it.

The reason it is recomputed against the clock is that Home Assistant only pushes a state when the state changes. A meter sitting at a genuinely constant reading emits nothing, which is indistinguishable — to anything watching the value — from a meter that has died. Watching the age instead separates the two: it climbs when telegrams stop and resets when they arrive, whatever the reading says.

The entity is only created when meter_source is not off. With P1 ingestion disabled there is nothing feeding it, and an age sensor climbing with no ingester behind it would trip the firmware watchdog on a system that is working fine.

Known limit, mqtt_p1. The age measures arrival. On the MQTT path a bridge that is stuck republishing its last telegram keeps arriving, so the age stays near zero and a frozen meter still looks fresh. Detecting that needs a change-detector rather than an arrival-detector, and it is not in this version.

⚠️ Known limit, ha_signed — do not drive a watchdog off this age yet. On the HA WebSocket paths the age is stamped when a state_changed arrives, which means it measures time since the value last changed, not time since the meter last reported. Home Assistant offers nothing better: a repeated reading produces no state_changed, does not advance last_reported on either the REST or the WebSocket serialiser, and state_reported cannot be subscribed to over the WebSocket at all (Event filter is required for event state_reported). All three measured on the ENV-01 rig against the real HomeWizard integration with the meter frozen: 0 state_changed in 70 s and no timestamp movement anywhere.

ha_dsmr mostly escapes this because a DSMR telegram updates several entities and something in the set almost always moves. ha_signed has exactly one entity, so a healthy meter under a flat load is indistinguishable from a dead one. This is not hypothetical: in our own captures (sim/scenarios/ha-p1_meter_active_power-2026-08-20.json) the real house meter went 42.2 s and 97.0 s between changes, and 23 Aug peaks at 29.1 s — all past the default meter_max_age_s of 30.

So sensor.p1_sample_age_s on ha_signed is safe to read, and it is correct whenever the value is moving, but it must not yet be thresholded by the ESP32 stale-input watchdog: a quiet house would trip the battery to 0 W. Raising meter_max_age_s is not the fix — the two conditions produce an identical signal, so a bigger number only chooses which of the two errors you get. The real fix is an arrival stamp the meter itself provides, i.e. reading the HomeWizard local API directly rather than through an HA entity.

Control

option default meaning
max_w 2000 Hard limit on what may be commanded. Start low, raise after commissioning
gain 0.6 Correction per cycle. At the limit — do not raise
slew_w 1000 Maximum change per cycle
deadband_w 15 Ignore errors smaller than this
target_grid_w -10 What the meter should rest at. Negative = a slight export
step_w 10 Quantisation
saturation_w 500 Divergence that counts as "the inverter is at a limit"
saturation_cycles 3 How many consecutive cycles before freezing. A cycle is one changed meter reading, not a fixed period - see the note below. Do not set to 1
integrator_max_w 0 Bound on the loop's accumulator, and 0 means "same as max_w". Caps how much stale error can be waiting to unwind when the sign flips. Do not raise it above max_w - the output clamp already bounds what is commanded, so the only thing extra headroom buys is more cycles of wrong-direction power after every saturation event. Lowering it below max_w is the useful direction
heartbeat_s 10 Refresh interval; must stay well under the firmware watchdog
stale_input_s 15 How long inputs may be missing before commanding 0 W. In P1 mode this clock starts only after meter_max_age_s has already expired — the two stack, see "How long a dead meter takes to reach 0 W"
auto_start false Start controlling on boot (only after commissioning)

Saturation is counted in cycles, not seconds

The specification states the saturation window as "> 10 s". This add-on counts cycles instead, and that is a deliberate, accepted deviation rather than an oversight - the acceptance criterion is not met as literally written.

A cycle here is one changed meter reading: the controller only runs the loop when the meter value differs from the previous poll. At the reference P1's ~5 s update rate the default of 3 cycles is usually around 15 s, but there is no guaranteed wall-clock window - a meter that repeats the same value stalls the counter for as long as it repeats.

Two reasons that is acceptable:

  • the control law is a pure function with no clock, which is what makes it testable without hardware, and a seconds-based window would have to live in the controller;
  • a stalled counter is a detection-latency limit and not a runaway risk. The condition that stalls it - an unchanging meter - stops the whole loop, so nothing accumulates while it is stalled.

If a guaranteed window matters on your site, raise saturation_cycles for a fast meter, and treat the figure as "N meter updates" rather than "N seconds".

Why target_grid_w is not zero

The deadband is a one-way ratchet: any resting point inside it holds until something disturbs it. Import and export are separate registers on the meter, so a rest point of +14 W is billed for every second it holds and no amount of export cancels it - 14 W all day is 0.34 kWh.

Biasing the target below zero moves that residue into the export register, which is not billed. The resting band becomes target ± deadband, so:

target_grid_w resting band worst billed leak export given away
0 -15 … +15 W ~15 W (0.35 kWh/day) none
-10 -25 … +5 W ~5 W (0.12 kWh/day) ~10 W
-15 -30 … 0 W none ~15 W (0.36 kWh/day)

Set it to -deadband_w if injection is worth nothing to you and you would rather give the energy away than buy it back. Set it to 0 if you are paid properly for export, or if you are debugging and want the loop centred.

⚠️ This is a billing knob, not a speed knob. If import is arriving in bursts rather than as a trickle, the cause is tracking lag, and this will not help - see "Why the tuning is what it is".

Maintenance

option default meaning
maintenance_enabled false Enable the monthly cycle
maintenance_interval_days 28 Minimum gap between cycles
maintenance_start_hour 10 Hour of day a due cycle begins
maintenance_discharge_w 2500 Drain rate (exports the surplus)
maintenance_charge_w 2500 Charge ceiling, capped again by peak headroom
maintenance_soc_floor 11 Drain target — stay just above the inverter's own floor
maintenance_soc_target 99 Charge target
maintenance_hold_min 120 Hold at full so the BMS can balance

Tariff (all optional)

option meaning
peak_forecast_entity Quarter-hour demand forecast, for capacity-tariff markets. Empty = no cap
peak_cap_w The site's capacity-tariff target
price_now_entity, price_avg_entity Dynamic tariff. Empty = never force a paid grid top-up

On a capacity-tariff site the maintenance charge is capped by the headroom left under peak_cap_w, and if the forecast goes over the cap the charge-only clamp is dropped so the battery can shave the peak instead. Money outranks the maintenance schedule.

Site

option meaning
estop_fitted Whether the RS485 e-stop is installed. Drives the warning banner
log_level trace/debug/info/warning/error

The Web UI

The ingress panel shows live values, why the controller is commanding what it is, and a Commissioning checklist that names any problem in words. It also carries the three buttons: start/stop control, force a maintenance cycle, and abort one.

Status entities

If an MQTT broker is available the add-on publishes setpoint, grid power, battery power, state of charge, maintenance phase and controller status by MQTT discovery. This is observability only — the controller works fine without a broker, and MQTT problems can never affect control.