checks / unit (pull_request) Successful in 8m6s
TEL-11: PV production stops being invisible, and stays out of the control law
OPT-10 measured that this site's pack reaches 90 % SoC on 2 days of 16 and that
20.5 kWh of surplus left the site while the pack had room - 12.6 kWh of it with
the battery not charging at all - and could not say WHY, because PV production
is recorded NOWHERE. Three causes need three different fixes (no irradiance:
nothing to fix; a charge-power limit; the optimiser declining to charge, which
is the only software defect) and guessing between them is how an optimiser gets
tuned to solve a cloud problem. This card adds the channel. It does not do the
attribution.

AN HA ENTITY, NOT A REGISTER, AND THAT IS A PRODUCT DECISION. This add-on's
RS485 bus carries the BATTERY inverter it drives; a household's PV inverter is
normally a different box from a different vendor reporting into Home Assistant
through its own integration. `pv_entity` takes whatever `sensor.*` the site's
own PV integration provides, any brand HA can read.

POSITIVE IS PRODUCTION, AND THERE IS NO `pv_invert`. The convention is derived
rather than assumed: `meter_entity` is positive when IMPORTING and `batt_entity`
is positive when DISCHARGING (DOCS.md, Sources), both of which are "power
arriving at the house's AC bus", and production arrives there too. Those two
keys carry invert flags because they are BIPOLAR and are READ BY THE CONTROL
PATH - `inv.batt` feeds SAFETY-30's per-unit sign check and SAFETY-31's
circulating-power sensor, so a reversed sensor hands the site a plausible number
it acts on. Production is unipolar and is read by nothing: a reversed sensor
announces itself as -4 kW at noon in the very history this card creates, and a
flag would only let an installer hide it. No negative-value alarm either - a PV
inverter's own standby draw makes a small negative reading at night ordinary, so
any threshold would be a number nobody measured.

ABSENCE IS NEVER ZERO, AND "DROPPED" IS NOT ABSENT. `publish()` SKIPS a None,
which is right for `circulation` and exactly wrong here: a skipped row leaves
Home Assistant holding the last number forever and the recorder draws a FLAT
LINE through the outage, which is indistinguishable from a measurement and
manufactures the "there was no surplus" conclusion this card exists to TEST. So
the absence is published, with HA's own payload: `mqtt/const.py` declares
`PAYLOAD_NONE = "None"` and `mqtt/sensor.py` tests it BEFORE the numeric branch,
so the entity's state becomes `unknown` and the recorder stores a GAP. Read out
of home-assistant/core `dev` on 2026-09-24 and quoted at the constant.
`ABSENT_AS_UNKNOWN` is a one-key set and the suite asserts `circulation: None`
is STILL dropped.

THE UNIT IS READ OFF THE ENTITY. `mW`, `W`, `kW`, `MW`, `GW`, `TW` - HA's own
`UnitOfPower`, every factor an exact power of ten. A sensor with no unit, or a
unit outside that table, is REFUSED by name and the status page says which.
`read_inputs()`'s `abs(raw) < 50` kW-or-W guess is safe for a quarter-hour
demand forecast and is NOT safe here: 30 W of dusk is an ordinary reading and
that heuristic would publish it as 30 kW.

GENUINELY OPTIONAL, AND NOT A SECOND `price_now_entity`. validate.py does not
mention the key - it cannot conflict with anything, because nothing else reads
it. The MQTT row lives in a new `OPTIONAL_SENSORS` list whose `include` argument
DEFAULTS TO EMPTY, so every caller that has never heard of `pv_entity` -
test_mqtt.py's fixtures, tools/rehearse_roster.py, anything written next year -
announces exactly what it announced before. Unset: no state call at all, no
entity, no topic, no status row, no page row. Set and failing: a CAUTION
(`ok=False, warn=True`), never a `bad` row, so a telemetry channel can never put
a battery site into NOT READY.

IT MUST NOT BECOME A CONTROL INPUT, AND THAT IS GRADED TWICE. `test_pv.py`
part 6 drives 40 cycles of the real `cycle()` and asserts the commands are
bit-identical across unset / no reading / 0 W / 8 kW, with a COMPUTED census
(33 modules under app/) showing the material is mentioned in exactly three:
pv.py, main.py, mqtt.py. `tools/tel11_pv_trace.py` is the cross-tree half -
`safety56_behaviour_trace.py`'s pattern with a DIFFERENT control clause, because
this card's claim is that nothing differs rather than that only sentences do: it
REFUSES unless the two `app/` fingerprints differ and unless exactly one side
reacts to the option. Measured on 41 stimulus cells:

    control   release/1.0 unset  846a10a5b89e321086d535825925721e2f791012e8405948d4fd38d3f9d0be5f
    control   TEL-11      unset  846a10a5b89e321086d535825925721e2f791012e8405948d4fd38d3f9d0be5f
    control   TEL-11      set    846a10a5b89e321086d535825925721e2f791012e8405948d4fd38d3f9d0be5f
    telemetry release/1.0 unset  a443a6ceaffe072b44bcd5f2ad946c1ed6c9e01b69e278eca631f7f4d7892164
    telemetry TEL-11      unset  a443a6ceaffe072b44bcd5f2ad946c1ed6c9e01b69e278eca631f7f4d7892164
    telemetry TEL-11      set    4e6d1cb289a957223ad0205f732a6fec6110ce1f2032c98ad60694e67625274f

UNSET is byte-identical in BOTH documents, which is stronger than "the control
path is untouched": an install that does not set the option sees no change of
any kind, announcement and status rows included.

⚠️ AND THE CARD'S CENTRAL MUTATION WAS A SURVIVOR ON THE FIRST BATTERY.
`self.grid -= self.pv_w` in `read_inputs()` - +106 B, on disk, purged, genuinely
running - came back GREEN, because the fixture drove a 6 kW export over 12
cycles, which puts the loop AGAINST ITS RAIL: a command moving `slew_w` every
cycle produces the same ramp for -6000 W and for -14 000 W of apparent error.
MUTATION.md habit 23 with a saturated ACTUATOR in place of a coinciding value,
and it is in that file now as the habit's second instance. The fixture now
drives a 600 W import the loop SETTLES on, against a responsive meter, and asks
habit 23's own question as its own check: shift the METER by the same 8 kW and
confirm the commands really would have moved.

Evidence: 31/31 suites green in the CI image, checks.yml's exact command, purged
tree, `:ro`. Ten mutations, NO survivors, each on its own `cp -a` of the tree so
habit 18's revert hazard is closed by construction - table in
`DECISIONS/TEL-11-pv-production.md` §7 with byte deltas and sha256s.

⚠️ THIS IS A RUNTIME CHANGE BEHIND AN UNCHANGED VERSION, AND
`tools/predeploy_check.py` WILL REFUSE IT. `app/`, `config.yaml` and
`translations/` are all in its `RUNTIME` tuple and `config.yaml` still reads
0.10.1, so the gate reports a NO-OP deploy until a version is cut. That is PKG's
call and this card does not take it.

No CHANGELOG section: `test_version_gate.py` 11b refuses a newest `## ` heading
that is not config.yaml's `version:`, and opening one would mean taking that
same packaging decision. The operator account is in DOCS.md.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-24 15:35:07 +02:00

118 lines
6.2 KiB
Python

"""TEL-11 - the site's PV production, read from a Home Assistant entity.
WHY THIS IS AN ENTITY AND NOT A REGISTER. This add-on's RS485 bus carries the
BATTERY inverter it drives. A household's PV inverter is, on nearly every site,
a different box from a different vendor that reports into Home Assistant
through its own integration - so the only place a product can read production
for an arbitrary install is an HA entity. `pv_entity` therefore takes whatever
`sensor.*` the site's own PV integration provides.
WHY THE CHANNEL EXISTS AT ALL. OPT-10 measured that 20.5 kWh of surplus left the
site in 16 days while the pack had room, 12.6 kWh of it with the battery not
charging at all - and could not say WHY, because PV production is recorded
NOWHERE. Three causes need three different fixes (no irradiance: nothing to fix;
a charge-power limit; the optimiser declining to charge - the only software
defect), and guessing between them is how an optimiser gets tuned to solve a
cloud problem. This module is the missing measurement and NOTHING ELSE.
⚠️ NOTHING HERE MAY EVER REACH A CONTROL DECISION, AND THAT IS THE CARD'S FIRST
CONSTRAINT RATHER THAN A STYLE NOTE. The add-on regulates a real battery; adding
production as a term of the control law would be an unrequested behaviour change
AND it would destroy the measurement, because the loop would then be reacting to
the quantity being measured. `tools/tel11_pv_trace.py` is what says the path is
untouched: it grades a control document that contains none of this material on
both trees and with `pv_entity` set and unset.
⚠️ ABSENCE IS NEVER ZERO, AND THAT IS THE SECOND CONSTRAINT. Every refusal below
returns `None` with a REASON, never `0.0`. A PV channel that reported 0 W for a
dead sensor would manufacture exactly the "there was no surplus to store"
conclusion the card exists to TEST - and it would do it silently, in a week of
recorder history nobody would re-derive. `app/hass.py`'s own note on `state()`
is the same rule one layer down.
THE SIGN CONVENTION: POSITIVE IS PRODUCTION. Derived from the two conventions
this add-on already ships rather than assumed:
`meter_entity` positive = IMPORTING from the grid (DOCS.md, Sources)
`batt_entity` positive = DISCHARGING the pack (DOCS.md, Sources)
Both are "positive = power arriving at the house's AC bus", and production
arrives there too. There is deliberately NO `pv_invert` to go with
`meter_invert` and `batt_invert`: those two quantities are BIPOLAR and are READ
BY THE CONTROL PATH - a reversed `batt_entity` feeds SAFETY-30's per-unit sign
check and SAFETY-31's circulating-power sensor with a plausible number the site
then acts on - whereas production is unipolar and is read by nothing. A reversed
PV sensor announces itself as -4 kW at noon in the very history this card
creates, and flipping it here would only hide it. See
`DECISIONS/TEL-11-pv-production.md` §2.
"""
from .hass import BAD_STATES
# Home Assistant's OWN power units, each as the number of watts one of it is.
# ⚠️ READ OUT OF HA, NOT LISTED FROM MEMORY: `UnitOfPower` in
# `homeassistant/const.py` (github.com/home-assistant/core, `dev`, retrieved
# 2026-09-24) declares mW, W, kW, MW, GW, TW and BTU/h. Every factor here is an
# exact power of ten, so none of them is a number anybody chose.
#
# ⚠️ BTU/h IS IN HA's ENUM AND DELIBERATELY NOT HERE. Its factor (0.293071…)
# is a measured conversion rather than a decimal shift, no PV integration
# publishes in it, and a wrong constant in the one channel that exists to
# attribute a 20.5 kWh shortfall is worse than a refusal an operator can read.
# It lands in the "not a power unit" refusal below, BY NAME.
WATTS_PER = {
"mW": 0.001,
"W": 1.0,
"kW": 1000.0,
"MW": 1000000.0,
"GW": 1000000000.0,
"TW": 1000000000000.0,
}
# What `watts()` answers when there is nothing to report. ⚠️ THE REASON IS PART
# OF THE RETURN VALUE, not a log line: it is what the status page prints, and an
# absence whose cause is invisible sends an operator to look at the wrong box.
UNIT_KEY = "unit_of_measurement"
def watts(state: dict | None) -> tuple:
"""`(watts, why)` from a Home Assistant state object.
`watts` is `None` whenever there is no reading - and `why` then says which
of the five refusals it was, in words an operator can act on. On a good read
`why` is the unit the value was read in, because "1234 W" and "1234, unit
unknown" are different claims and the page has to be able to make the first.
⚠️ THE UNIT IS READ OFF THE ENTITY AND NOT ASSUMED, AND THERE IS NO
MAGNITUDE HEURISTIC. `read_inputs()` guesses kW-or-W for
`peak_forecast_entity` with `abs(raw) < 50`, which is safe there because
nobody's quarter-hour demand forecast is 50 W. It is NOT safe here: 30 W of
real production at dusk is an ordinary reading, and that heuristic would
publish it as 30 kW - a fabricated number, in the channel whose entire
purpose is to be believed a week later. A sensor whose unit this cannot read
is REFUSED rather than guessed at.
"""
if state is None:
# `hass.state()` answers None for a non-existent entity, a 404 and a
# transport failure alike. All three are "no reading", and HA does not
# consider a non-existent entity an error - see `hass.state()`.
return None, "no state (entity missing, or the read failed)"
raw = str(state.get("state", "")).strip()
if raw.lower() in BAD_STATES:
# ⚠️ THE SAME LIST `hass.number()` REFUSES ON, IMPORTED RATHER THAN
# RESPELLED. A second copy of it is how one path starts treating
# `unavailable` as a number the other one rejects.
return None, f"entity is {raw or 'empty'}"
try:
value = float(raw)
except ValueError:
return None, f"state {raw!r} is not numeric"
unit = str((state.get("attributes") or {}).get(UNIT_KEY) or "").strip()
if not unit:
return None, ("no unit_of_measurement on the entity - it cannot be "
"read in watts")
if unit not in WATTS_PER:
return None, (f"unit {unit!r} is not one of "
f"{', '.join(WATTS_PER)} - it cannot be read in watts")
return value * WATTS_PER[unit], unit