SAFETY-31: measure circulating power, which nets to zero at the meter
Inverter A charging at 3 kW while inverter B discharges at 3 kW nets ~0 W at
P1. The site reads idle while both packs are cycled through two round-trip
conversion losses continuously, for no benefit, and the wear is real.

NOTHING EXISTING CAN SEE IT, AND THAT IS STRUCTURAL. Every guard in this
add-on is a consumer of the NET figure at the grid connection: SAFETY-02's
sign watchdog gates on abs(grid_w) > 300 and the gate never opens at a netted
zero; the peak guard and the capacity tariff both bill grid exchange.
Circulating power is precisely the component of per-inverter power that the
sum destroys, so no threshold on any existing detector could reach it.

WHAT ALLOC-01 ALREADY COVERED, AND IS NOT RE-IMPLEMENTED HERE. Its AC 7
shipped the sign-coherence gate (allocator.REFUSE_SIGN, graded by
test_alloc.py part 6): an allocation whose shares carry two signs is REFUSED,
both units named, no shares returned. That is the COMMAND half - the allocator
can no longer command circulating power. This commit is the MEASUREMENT half:
circulation the allocator NEVER COMMANDED.

  app/circulation.py   the sensor and the trip
  main.py              site_circulating_w, the evaluation, the claim, the alarm
  arbiter.py           `circulation` classified SCOPE_SITE, with the argument
  store.py             a flat, site-level durable latch
  mqtt.py              sensor.goodwe_circulating_power
  config.yaml          two options, two schema ranges, CFG-03 discipline

THE SENSOR: sum(|Bi|) - |sum(Bi)|. Zero when the units pull the same way,
2*min(|Ba|,|Bb|) when they oppose. DERIVED FROM MEASURED PER-INVERTER POWER -
Inverter.batt, register 0x0518 - and never from the allocation record. The
cheap version would be simpler and worth nothing: ALLOC-01's gate already
guarantees the record is sign-coherent, so a record-derived sensor reads zero
BY CONSTRUCTION and can only confirm that the allocator agrees with itself,
which is the third failure mode MUTATION.md names. What this catches is a unit
ignoring or lagging its share, a stale share still being executed, a
maintenance or SAFETY-25 pin holding one unit while the loop drives the other,
or HW-01's power stage running its last instruction for 6 h 25 m with the
comms dead and the allocation record impeccable throughout. batt became
per-instance in DEV-02; before that this could not have been written.

VERIFIED BY MAKING ONE UNIT IGNORE ITS SHARE, on the TEST-19 two-master rig:

  S = -2500 W   shares a = -1250 W  b = -1250 W   <- record ok, ONE sign, sums
  MEASURED      A = -1250 W  B = +1000 W          <- hardware
  sensor over the RECORD     :    0 W
  sensor over MEASURED power : 2000 W  -> trips at 190 s

and the card's own scenario, A -3000 W against B +3000 W at zero house load:
the meter reads +0 W, the sensor reads 6000 W, and the shipped SignWatchdog's
predicate is FALSE on 30 of 30 cycles.

WHAT "ACTED ON" MEANS - decided, and recorded in DECISIONS/. The trip files
Claim.set("circulation", P_SAFETY, 0.0) on the SITE actuator: every inverter
to 0 W, latched. HW-01 established that commanding a wedged inverter achieves
nothing, so the remedy is not aimed at it. A circulating loop needs TWO
participants and one of them is THIS CONTROLLER, faithfully driving the
listening sibling into the one that stopped listening. Stopping (1) halves the
loop, which needs no cooperation from the wedged unit, and (2) - the more
important half - makes the residue VISIBLE at the meter instead of cancelled
at it, where every ordinary guard can finally see it. What it cannot do is
stop the wedged unit; the notification says so and names the isolator as the
last actuator. SITE-scoped because the quantity is defined over the roster and
is identically zero for any one unit - there is no fact of the matter about
which of two opposing inverters is the offender, so filing it per-unit would
invent an attribution and could park the only unit still listening.

THE WINDOW IS FROM THE RIG, NOT A ROUND NUMBER (AC 3). 924 closed-loop runs in
which NOTHING is faulty, over both families of legitimate opposition (7
reversals x 5 write staggers; 7 flap periods x 4 amplitudes), swept across the
whole range the schema accepts for gain and slew_w. Worst CONTINUOUS
legitimate opposition by threshold: 505.0 s at 100 W, 40.0 s at 250 W, 10.0 s
at 300 W, 5.0 s at 400 W and above. The knee is 400 W and it is the schema
floor - below it, ordinary operation holds the sensor over the line for
minutes and no window inside the 900 s billing quarter could tell that from a
fault. circulation_w 700 is 1.75x the knee, the headroom bought for inverter
B's ramp and lag being PLACEHOLDERS until SPIKE-04 measures them.
circulation_hold_s 75 clears three bounds: 15x the worst legitimate episode,
2.5x the firmware's own LINK_STALE_S veto, 12x inside the quarter. A momentary
opposition while one unit slews through zero is LEGITIMATE - writes are
serialised, so B's number lands up to a cycle after A's - and 0 of the 924
runs trip.

THE ALARM SURVIVES AN HA RESTART (SAFETY-34). persistent_notification is in
memory, which is exactly how the 2026-09-02 outage went unseen for 6 h 25 m
with the detector correct throughout. The latch is persisted to /data as flat
site-level keys and the notification is RE-RAISED on the first cycle after
every start, through the same code path as a fresh trip - two paths would be
two chances for the restart one to rot unnoticed.

AT N=1 NOTHING CHANGES (AC 5). |B| - |B| is 0 for every reading including one
nobody took, no claim is ever filed, the arbitration is byte-identical, and
the status page says n/a rather than claiming to watch something that cannot
happen.

VERIFIED BY BREAKING IT (AC 4). 18 mutations, all RED on named checks, each on
a freshly copied tree with no __pycache__ mounted :ro. M10 - the sensor
rewritten to read self.allocation.shares - is the headline: it takes AC 2 red.
Three mutations are +0 B, the risky delta, and are marked as such. One
equivalent mutant (the max(0.0,...) guard) is ARGUED rather than claimed:
searched over 700 000 rosters without a negative. One genuine SURVIVOR was
found and closed - publish() turning an unknown into a published 0 W, the
sensor's own None rule defeated one layer out. Full ledger in DECISIONS/.

arbiter.CLAIM_SCOPE gains its ninth source, so test_peakguard.py's 10f and 10g
tripwires and test_arbiter.py's scope table went red on the line the append
was written. Updated deliberately, with the argument, as their own comments
require. Full 19-file suite green.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
2026-09-04 01:56:23 +02:00

1113 lines
54 KiB
Python

"""Runnable check for the sign-disagreement watchdog. `python3 test_watchdog.py`
Every case here is either a fault this must catch or a piece of NORMAL behaviour
it must not mistake for one. The second list is the longer one on purpose: an
alarm that fires on ordinary operation is worse than no alarm, because the next
person switches it off.
The headline validation is not here - it is `sim/replay_sign.py` in the infra
repo, which drives this module over the two captured bus days. This file is the
table-driven half: boundaries, timers, the latch, and the arming gate.
⚠️ MUTATING THE MODULE THIS FILE GRADES? PURGE `__pycache__` FIRST - or run
`tools/mutation_run.sh`, which does. `python3 -B` alone does NOT save you: it
stops bytecode being WRITTEN, not a stale one being READ, and a size-preserving
edit reverted inside one second is invisible to CPython's staleness test. That
is TEST-15, and it has already turned one live mutation into a false survivor.
Read MUTATION.md before you report a survivor.
"""
import sys
from datetime import datetime, timedelta, timezone
from app.watchdog import (
SignWatchdog, SignWatchdogConfig, loop_is_following,
)
fails = []
T0 = datetime(2026, 8, 20, 15, 0, 0, tzinfo=timezone.utc)
def check(name, cond):
print(f" {'ok ' if cond else 'FAIL'} {name}")
if not cond:
fails.append(name)
def drive(samples, cfg=None, following=True):
"""Feed (offset_s, commanded_w, grid_w) tuples. Returns (wd, trip_offset)."""
wd = SignWatchdog(cfg)
trip_at = None
for item in samples:
offset, cmd, grid = item[0], item[1], item[2]
f = item[3] if len(item) > 3 else following
if wd.evaluate(cmd, grid, f, T0 + timedelta(seconds=offset)) and trip_at is None:
trip_at = offset
return wd, trip_at
def opposed(duration_s, step=5, cmd=-1000, grid=1500, following=True, start=0):
return [(start + t, cmd, grid, following)
for t in range(0, int(duration_s) + 1, step)]
print("the fault it exists to catch")
wd, at = drive(opposed(300))
check("charging into an importing house trips", wd.tripped)
check("and trips at 180 s, not before", at == 180)
check("the reason names both signals", "-1000" in wd.reason and "+1500" in wd.reason)
print(f" e.g. {wd.reason!r}")
wd, at = drive(opposed(300, cmd=2000, grid=-2000))
check("discharging into an exporting house trips too", wd.tripped and at == 180)
print()
print("the boundaries")
wd, _ = drive(opposed(600, cmd=-300, grid=1500))
check("300 W exactly does NOT qualify (strictly greater)", not wd.tripped)
wd, _ = drive(opposed(600, cmd=-301, grid=1500))
check("301 W does", wd.tripped)
wd, _ = drive(opposed(600, cmd=-1000, grid=300))
check("a 300 W meter does not qualify either", not wd.tripped)
wd, _ = drive(opposed(175))
check("175 s of disagreement does not trip", not wd.tripped)
wd, _ = drive(opposed(180))
check("180 s does (>= hold_s)", wd.tripped)
print()
print("continuity - the rule that produced zero false positives on real data")
broken = opposed(175) + [(180, -1000, -1500)] + opposed(175, start=185)
wd, _ = drive(broken)
check("179 s, one agreeing sample, then 175 s more: no trip", not wd.tripped)
check("and the window really was reset", wd.disagree_since is not None)
long_enough = broken + opposed(200, start=365)
wd, _ = drive(long_enough)
check("but a full 180 s after the reset does trip", wd.tripped)
print()
print("things that are NOT faults")
# The load-step transient. Measured on the healthy capture: longest 30 s.
wd, _ = drive(opposed(30) + [(35 + t, 800, 900) for t in range(0, 300, 5)])
check("a 30 s load-step crossover does not trip", not wd.tripped)
# SoC 10 %, Standby, declining a 1350 W discharge. The battery does nothing, so
# the meter stays where it was and the command agrees with it.
wd, _ = drive([(t, 1350, 1350) for t in range(0, 900, 5)])
check("a battery refusing a discharge command cannot trip it", not wd.tripped)
# A frozen meter drives command and reading into agreement, not disagreement.
wd, _ = drive([(t, 800, 800) for t in range(0, 900, 5)])
check("a frozen meter cannot trip it", not wd.tripped)
# Maintenance grid charge: 2500 W of charge against an importing house, for
# hours. Opposed, both huge - and entirely correct.
wd, _ = drive(opposed(7200, cmd=-2500, grid=3000, following=False))
check("two hours of maintenance grid charge does not trip", not wd.tripped)
check("and the timer never even started", wd.disagree_since is None)
wd, _ = drive([(t, -1000, None) for t in range(0, 900, 5)])
check("a missing meter reading does not trip", not wd.tripped)
wd, _ = drive(opposed(175) + [(180, -1000, None)] + opposed(600, start=185))
check("a missing reading mid-window RESETS it rather than accumulating",
wd.tripped and wd.disagree_since is not None)
wd, at = drive(opposed(175) + [(180, -1000, None)] + opposed(600, start=185))
check("...so the trip lands 180 s after the gap, not after 180 s total",
at == 365)
wd, _ = drive([(t, 0.0, 3000) for t in range(0, 900, 5)])
check("a 0 W command is not a wrong-direction command", not wd.tripped)
print()
print("the latch")
wd, _ = drive(opposed(200))
check("tripped after the fault", wd.tripped)
# The trip commands 0 W, which removes the command side of the comparison.
for t in range(200, 900, 5):
wd.evaluate(0.0, 3000, True, T0 + timedelta(seconds=t))
check("stays tripped once the command is zeroed", wd.tripped)
for t in range(900, 1500, 5):
wd.evaluate(1000, 1000, True, T0 + timedelta(seconds=t))
check("stays tripped even once everything looks healthy again", wd.tripped)
wd.reset()
check("reset() is the only way out", not wd.tripped and wd.disagree_since is None)
check("and the reason is cleared with it", wd.reason == "")
print()
print("the thresholds are configuration, not constants")
cfg = SignWatchdogConfig(min_w=800.0, hold_s=60.0)
wd, at = drive(opposed(300, cmd=-1000, grid=1500), cfg=cfg)
check("a 60 s hold trips at 60 s", wd.tripped and at == 60)
wd, _ = drive(opposed(600, cmd=-700, grid=1500), cfg=cfg)
check("an 800 W gate ignores a 700 W command", not wd.tripped)
print()
print("the configuration that would disarm it is refused")
from app.validate import validate_startup_config # noqa: E402
base = {"setpoint_entity": "number.sp", "meter_source": "off",
"meter_phases": 1, "meter_max_age_s": 30}
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 300},
-5000, 5000)
check("300 W under a 2000 W ceiling is accepted", p == [])
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 2000},
-5000, 5000)
check("a threshold AT max_w is refused", len(p) == 1 and "never fire" in p[0])
# ⚠️ maintenance_charge_w is named here only to keep this case about the SIGN
# rule. MAINT-04 added a second rule against the same ceiling, and a 500 W
# max_w is also below the 2000 W shipped maintenance charge - so without this
# the dict is refused twice, for two correct but different reasons, and the
# `len(p) == 1` below would be measuring the interaction rather than this rule.
p = validate_startup_config({**base, "max_w": 500, "sign_disagree_w": 3000,
"maintenance_charge_w": 500}, -5000, 5000)
check("a threshold above max_w is refused", len(p) == 1 and "never fire" in p[0])
p = validate_startup_config({**base, "max_w": 2000, "sign_disagree_w": 1999},
-5000, 5000)
check("one watt under the ceiling is reachable, so accepted", p == [])
print()
print("the arming gate, derived from the REAL arbiter")
# ⚠️ THIS IS THE DECISION THE WHOLE TICKET TURNS ON, and until now it was
# asserted in three comment blocks and verified by nothing: every other case in
# this file passes `following` in as a literal. What has to hold is that the
# expression in main.py - loop won AND the emitted value points the way the loop
# asked AND is no larger - is never True for a resolution the loop did not
# actually get. So run real claims through the real resolve() and derive it.
from app.arbiter import ( # noqa: E402
P_LOOP, P_MAINT_SHAPE, P_MAINTENANCE, P_PEAK, P_SAFETY, Claim, resolve,
)
def following_from(claims, asked):
"""THE SHIPPED gate, not a copy of it.
⚠️ This used to transcribe main.py's expression with a comment saying
"keep the two in step", which is exactly the arrangement that does not keep
two things in step. Measured: editing the shipped gate alone to
`winner in ("loop", "peak")` left this suite - including the P_PEAK row below,
whose entire job is to catch that edit - completely green, while the watchdog
went blind for the duration of every peak event. Import it or the P_PEAK
assertion is decoration.
"""
r = resolve(claims)
return r, loop_is_following(r, asked)
MAXW = Claim.limit("supervised", P_SAFETY, -2000, 2000, "max_w")
DEV = Claim.limit("device", P_SAFETY, -5000, 5000, "rating")
# name, claims, what the loop asked, expected `following`
TABLE = [
("the loop alone, unopposed",
[Claim.set("loop", P_LOOP, 900)], 900, True),
("the loop bound by max_w - reduced, not redirected",
[Claim.set("loop", P_LOOP, 4000), MAXW], 4000, True),
("charging, bound by max_w on the other side",
[Claim.set("loop", P_LOOP, -4000), MAXW], -4000, True),
("maintenance owns the setpoint outright",
[Claim.set("loop", P_LOOP, 900),
Claim.set("maintenance", P_MAINTENANCE, -2500, "charge"), MAXW], 900, False),
("maintenance charge-only clamps the loop to 0 W",
[Claim.set("loop", P_LOOP, 900),
Claim.limit("maintenance", P_MAINT_SHAPE, hi=0.0, reason="charge-only"),
MAXW], 900, False),
# ⚠️ THE CASE `winner == \"loop\"` ALONE WOULD HAVE GOT WRONG. 1500 W, not
# 2500 W: at max_w 2000 a -2500 hi against a -2000 lo is an arbiter
# contradiction, not a charge. That pair was the SHIPPED default until
# MAINT-04 refused it and CFG-03 gave the default one source of truth; it is
# kept below as a case rather than as a configuration.
("cheap-window charge REDIRECTS the loop while it still 'wins'",
[Claim.set("loop", P_LOOP, 500),
Claim.limit("maintenance", P_MAINT_SHAPE, hi=-1500, reason="cheap-window"),
MAXW], 500, False),
("...and the contradiction when charge_w exceeds max_w is not following either",
[Claim.set("loop", P_LOOP, 500),
Claim.limit("maintenance", P_MAINT_SHAPE, hi=-2500, reason="cheap-window"),
MAXW], 500, False),
("a lo limit RAISES the magnitude without flipping the sign",
[Claim.set("loop", P_LOOP, 200),
Claim.limit("floor", P_SAFETY, lo=800), MAXW], 200, False),
("a safety stop wins outright",
[Claim.set("loop", P_LOOP, 900),
Claim.set("safety", P_SAFETY, 0.0, "stopped"), MAXW], 900, False),
("no claims at all - the arbiter's own failsafe",
[MAXW, DEV], None, False),
("the loop asked for zero",
[Claim.set("loop", P_LOOP, 0.0), MAXW], 0.0, False),
# The forward hazard, asserted as it stands TODAY rather than as it should
# be. When peak shaving lands, these expectations are what have to change.
("peak shaving at P_PEAK disarms the gate (loop_is_following's forward hazard)",
[Claim.set("loop", P_LOOP, 900),
Claim.set("peak", P_PEAK, 1800, "shaving"), MAXW], 900, False),
# ⚠️ AND THE ROW ABOVE CANNOT DETECT A WIDENED GATE ON ITS OWN, which was
# found by trying it: with the shipped gate edited to
# `winner in ("loop", "peak")` that case STILL comes out False, because peak
# shaving asked for MORE than the loop and the magnitude term rejects it
# anyway. The winner term is masked. This row isolates it - a peak claim
# smaller than the loop's ask and pointing the same way, so `winner` is the
# only term that can decide - and it is what actually turns red if the gate
# is widened without anyone revisiting the hazard.
("...and with peak BELOW the loop's ask, only the winner term separates them",
[Claim.set("loop", P_LOOP, 1800),
Claim.set("peak", P_PEAK, 900, "shaving"), MAXW], 1800, False),
]
for name, claims, asked, expect in TABLE:
r, got = following_from(claims, asked)
check(f"{name} -> following={expect}", got is expect)
if got is not expect:
print(f" resolution was {r.explain()!r}")
# And the gate is never True when the loop did not win, whatever else is going on.
check("no configuration above arms the gate without the loop winning",
all(not following_from(c, a)[1]
for _, c, a, _ in TABLE if following_from(c, a)[0].winner != "loop"))
print()
print("end to end: the trip is COMMAND ZERO, not alarm-only")
# ⚠️ THE FAULT INJECTED HERE IS A NEGATIVE GAIN, and that is not a contrivance -
# it is the minimal faithful model of what this watchdog is for. The check
# compares the loop's OUTPUT DIRECTION against the INPUT STATE it was regulating,
# so what it detects is a loop whose two ends have become decoupled in sign: a
# gain, a claim or a strategy with its polarity inverted, or an integrator so far
# wound up that unwinding takes minutes. (Illusmart's was the last one: it
# reached -14 768 W against a +-5000 W rail while writing once every 20-60 s, and
# that arithmetic alone is 5-15 minutes of wrong-direction command.)
#
# `gain` is float(0.05,1.0) in the schema, so this is not a reachable
# configuration - it is a stand-in for a code regression, which is the case a
# unit test can actually hold the line on.
import asyncio # noqa: E402
from app.main import Controller # noqa: E402
# ⚠️ DEV-02. THE KEY SPELLING IS IMPORTED, NEVER TRANSCRIBED. `sign_tripped` and
# `sign_reason` are now NAMESPACED PER INVERTER - flat, a trip caused by B
# latched A across every restart and one operator press cleared both. A check
# that spelled `"unit/inverter-a/sign_tripped"` by hand here would go on passing
# against a main.py that had started writing somewhere else, which is this
# repository's own named failure mode: the copy that drifts is always the
# grading one. `unit_key()` is the one definition and `Inverter.key()` calls it.
from app.inverter import UNIT_A # noqa: E402
from app.store import unit_key # noqa: E402
TRIPPED_KEY = unit_key(UNIT_A, "sign_tripped")
REASON_KEY = unit_key(UNIT_A, "sign_reason")
class _Hass:
def __init__(self):
self.writes = []
self.calls = []
# ⚠️ ADDED FOR SAFETY-03, AND THE REASON IS WORTH READING. The e2e below
# runs a DELIBERATELY INVERTED loop (gain -0.6) into a steady 2000 W import,
# which is a loop that winds straight into the rail - so the output-clamp
# alarm fires here, and the stub not having `call` is how that was
# discovered. This scenario is now a second, independent witness that the
# clamp alarm sees a real winding loop; test_clamp.py asserts it explicitly.
async def call(self, domain, service, data):
self.calls.append((domain, service, data))
async def limits(self, entity):
return (-5000.0, 5000.0, 1.0)
async def number(self, entity, invert=False):
# A house importing 2000 W, steadily, whatever the battery does.
return {"sensor.grid": 2000.0, "sensor.soc": 50.0,
"sensor.batt": 0.0}.get(entity)
async def set_number(self, entity, value):
self.writes.append(float(value))
return True
class _S:
data = {}
def set(self, *a):
pass
def get_time(self, *a):
return None
class _P:
enabled = False
def publish(self, *a, **k):
pass
def close(self):
pass
async def _e2e():
hass = _Hass()
opts = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 2000, "gain": -0.6,
"sign_disagree_w": 300, "sign_disagree_s": 1, "auto_start": True}
c = Controller(opts, hass, _S(), _P(), stop=asyncio.Event())
c.auto = True
c.dev_min, c.dev_max = -5000.0, 5000.0
seen_wrong_way = False
for _ in range(12):
await c.read_inputs()
await c.cycle()
if c.target < -300 and not c.sign_wd.tripped:
seen_wrong_way = True
await asyncio.sleep(0.25)
return c, hass, seen_wrong_way
ctrl, hass, wrong_way = asyncio.run(_e2e())
check("the broken loop really did command charge into an import first", wrong_way)
check("the watchdog tripped", ctrl.sign_wd.tripped)
check("the commanded value is 0 W", ctrl.target == 0.0)
check("0 W actually reached the device", 0.0 in hass.writes)
check("and it got there through the failsafe claim, not by accident",
"failsafe" in ctrl.reason)
print(f" status line: {ctrl.reason!r}")
check("the status page says so in words",
any("SIGN-DISAGREEMENT FAILSAFE" in c["text"] for c in ctrl.checks()))
check("the banner leads with it",
"FAILSAFE" in ctrl.status_payload()["banner"])
check("it stays at 0 W on later cycles too",
hass.writes[-1] == 0.0 and hass.writes.count(0.0) >= 1)
# ⚠️ THIS USED TO BE `check("MQTT reports the failsafe state", ctrl.sign_wd.tripped)`
# which restates the assertion three lines above and never touches the payload.
# The `status: "failsafe"` value was shipped untested. Capture what publish()
# actually hands the broker.
published = {}
ctrl.mqtt = type("P", (), {"enabled": True,
"publish": lambda _s, v: published.update(v),
"close": lambda _s: None})()
ctrl.publish()
check("MQTT's controller-status sensor reports 'failsafe'",
published.get("status") == "failsafe")
ctrl.sign_wd.reset()
ctrl.publish()
check("...and goes back to 'running' once cleared",
published.get("status") == "running")
print()
print("the latch survives a restart - it is the only thing between a tripped")
print("controller and the first thing an operator will try")
# ⚠️ THE BLOCKER THIS FILE MISSED FIRST TIME ROUND. `auto` is persisted and
# `tripped` was not, so reconstructing a Controller against the same Store -
# which is exactly what a container restart does - came back armed, into the
# fault, with no operator involved: tripped=False, banner NOT READY, and it
# resumed commanding -1000 then -2000 W before re-tripping 180 s later.
class _MemStore:
"""A Store that keeps its dict across "restarts", like the real file does."""
def __init__(self):
self.data = {"phase": "idle", "sign_tripped": False, "sign_reason": ""}
def set(self, k, v):
self.data[k] = v
def get_time(self, *a):
return None
async def _restart():
shared = _MemStore()
hass1 = _Hass()
opts = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 2000, "gain": -0.6,
"sign_disagree_w": 300, "sign_disagree_s": 1, "auto_start": True}
a = Controller(opts, hass1, shared, _P(), stop=asyncio.Event())
a.auto = True
a.dev_min, a.dev_max = -5000.0, 5000.0
for _ in range(12):
await a.read_inputs()
await a.cycle()
await asyncio.sleep(0.25)
# The restart. Same options, same store, brand new Controller and Hass.
hass2 = _Hass()
b = Controller(opts, hass2, shared, _P(), stop=asyncio.Event())
b.auto = True
b.dev_min, b.dev_max = -5000.0, 5000.0
for _ in range(6):
await b.read_inputs()
await b.cycle()
await asyncio.sleep(0.05)
return a, b, shared, hass2
pre, post, store, hass2 = asyncio.run(_restart())
check("it tripped before the restart", pre.sign_wd.tripped)
check("the trip reached the store, UNDER THE TRIPPED INVERTER'S OWN KEY",
store.data[TRIPPED_KEY] is True)
check("...with the reason beside it, so the operator is told why",
"SIGN_DISAGREEMENT" in store.data[REASON_KEY])
check("⚠️ ...AND THE FLAT PRE-DEV-02 KEY IS MIRRORED, AS THE ROLLBACK VIEW. "
"This assertion used to read the other way - that the flat key was NOT "
"written - on the argument that writing it would latch every other "
"inverter on the site. That argument was right about the READ and wrong "
"about the WRITE: nothing at runtime reads the flat key, and the one "
"thing that does (`_grade_store_migration()`, on every start) ignores it "
"whenever ANY namespaced latch is set, which a sibling's trip always "
"leaves. What the absence actually cost was the ROLLBACK: store.py's "
"rule 2 keeps this key so a downgrade finds the latch, and a trip taken "
"after the migration wrote nothing here - so an operator who downgraded "
"came up DRIVING. `test_inverter.py` part 3 is where 'B's trip does not "
"latch A across a restart' is graded, on a real roster of two",
store.data.get("sign_tripped") is True
and "SIGN_DISAGREEMENT" in str(store.data.get("sign_reason", "")))
check("the new Controller comes back TRIPPED", post.sign_wd.tripped)
check("...and says why, restored rather than re-detected",
"SIGN_DISAGREEMENT" in post.sign_wd.reason)
check("...commands 0 W from its very first cycle", post.target == 0.0)
check("...and never commanded anything else after the restart",
hass2.writes != [] and set(hass2.writes) == {0.0})
check("the banner still leads with the failsafe",
"FAILSAFE" in post.status_payload()["banner"])
# ⚠️ TWO PRESSES, and the first one must NOT clear it. `auto` is True while
# tripped, so the first press stops control; only the transition back to True
# clears. That is the documented behaviour and it is worth an assertion, because
# a one-press clear would be reachable by an operator who never read the banner.
asyncio.run(post.handle_action("auto_toggle")) # -> stopped
check("pressing stop does not clear the failsafe",
post.sign_wd.tripped and store.data[TRIPPED_KEY] is True)
asyncio.run(post.handle_action("auto_toggle")) # -> started
check("pressing start DOES clear it, and clears the store with it - BOTH "
"spellings, which is what stops the every-start latch guard re-arming a "
"failsafe the operator has already dealt with",
not post.sign_wd.tripped and store.data[TRIPPED_KEY] is False
and store.data[REASON_KEY] == ""
and store.data.get("sign_tripped") is False)
# One more restart from the cleared store, to prove the clear persisted too.
fresh = Controller({"setpoint_entity": "number.sp", "meter_source": "off"},
_Hass(), store, _P(), stop=asyncio.Event())
check("...so the next restart comes back armed and untripped, as it should",
not fresh.sign_wd.tripped)
# ⚠️ THE WRITE ORDERING IS AN INVARIANT, SO IT GETS AN ASSERTION. main.py writes
# `sign_reason` and THEN `sign_tripped`, each one its own `save()`, so that a
# process that dies between the two leaves a reason nothing reads - harmless -
# rather than a latch with no explanation for the operator who has to decide
# whether to clear it. Documented reasoning is not enforcement: swapping those two
# lines used to pass every check in this file.
#
# The death is modelled as the second write raising. In the field it is a power
# cut or a container kill (Store.save() swallows OSError rather than raising), so
# what is asserted here is the PROPERTY - what survives on disk - not the
# mechanism.
class _CrashOnFlag(_MemStore):
def set(self, k, v):
if k == TRIPPED_KEY and v:
raise RuntimeError("power cut, mid-trip")
super().set(k, v)
async def _crash_mid_write():
store = _CrashOnFlag()
hass = _Hass()
opts = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 2000, "gain": -0.6,
"sign_disagree_w": 300, "sign_disagree_s": 1, "auto_start": True}
c = Controller(opts, hass, store, _P(), stop=asyncio.Event())
c.auto = True
c.dev_min, c.dev_max = -5000.0, 5000.0
died = False
for _ in range(12):
try:
await c.read_inputs()
await c.cycle()
except RuntimeError:
died = True
break
await asyncio.sleep(0.25)
return store, died
crashed_store, died = asyncio.run(_crash_mid_write())
check("the second write is the one that sets the flag", died)
check("a crash between the two writes leaves the REASON on disk",
"SIGN_DISAGREEMENT" in crashed_store.data.get(REASON_KEY, ""))
check("...and never a latch with nothing to explain it",
not crashed_store.data.get(TRIPPED_KEY))
# =============================================================================
print()
print("=" * 72)
print("SAFETY-31: circulating power, which nets to zero at the meter")
print("=" * 72)
# ⚠️ READ THIS BEFORE ADDING A CHECK HERE. Half of this card was already built
# and it is NOT the half below. ALLOC-01 shipped the SIGN-COHERENCE GATE
# (`allocator.REFUSE_SIGN`, graded by test_alloc.py part 6): an allocation whose
# shares carry two signs is REFUSED, both units named, no shares returned. So
# the allocator can no longer COMMAND circulating power, and nothing here
# re-tests that.
#
# What is graded here is the MEASUREMENT half: circulating power the allocator
# NEVER COMMANDED. The two are complements, not duplicates - the gate refuses an
# allocation before it is written and cannot see one millisecond past that; this
# reads the hardware and does not care what was written.
from app.inverter import LINK_STALE_S # noqa: E402
from app.circulation import ( # noqa: E402
CIRC_OPTION_DEFAULTS, CirculationConfig, CirculationWatchdog,
circulating_w, opposing,
)
print()
print("1. the sensor: sum(|Bi|) - |sum(Bi)| over MEASURED per-unit power")
check("both units discharging: the triangle equality holds and it is ZERO. "
"This is the ordinary case and the sensor must be silent in it",
circulating_w([1000.0, 2000.0]) == 0.0)
check("...both charging, likewise", circulating_w([-1000.0, -2000.0]) == 0.0)
check("...and a unit resting at exactly zero beside a working one is not "
"opposition", circulating_w([0.0, 2500.0]) == 0.0)
# ⚠️ ASSERTED AGAINST A LITERAL, NOT AGAINST `2 * min(abs(a), abs(b))`.
# MUTATION.md's rule 2: an assertion written in terms of the expression under
# test cannot tell "the right formula" from "the same wrong formula twice".
check("A charging 3000 W while B discharges 3000 W reads 6000 W - the card's "
"own scenario, and the figure is 2*min(|A|,|B|), the power going round "
"the loop through BOTH conversion stages",
circulating_w([-3000.0, 3000.0]) == 6000.0)
check("...unequal opposition is bounded by the smaller unit: -3000 against "
"+1000 is 2000 W, not 4000",
circulating_w([-3000.0, 1000.0]) == 2000.0)
print(f" [-3000, +3000] -> {circulating_w([-3000.0, 3000.0]):.0f} W "
f"[-3000, +1000] -> {circulating_w([-3000.0, 1000.0]):.0f} W "
f"[+1000, +2000] -> {circulating_w([1000.0, 2000.0]):.0f} W")
check("three units, one out of step: it is defined over the whole roster, not "
"over a pair", circulating_w([-2000.0, 1000.0, 1000.0]) == 4000.0)
print()
print(" AC 5: at N=1 it is IDENTICALLY zero, for every reading")
# ⚠️ SWEPT, NOT SAMPLED. "Identically zero" is a claim about EVERY value, and
# one call with one number cannot distinguish it from "zero for this number".
_n1 = [circulating_w([v]) for v in
(0.0, 1.0, -1.0, 2500.0, -2500.0, 5000.0, -5000.0, 1e9, -1e9)]
check("nine readings from -1e9 to +1e9 W, every one of them 0.0",
set(_n1) == {0.0})
check("...and an EMPTY roster is zero too, not a crash - `Controller.publish()` "
"calls this before anything has been read",
circulating_w([]) == 0.0)
check("⚠️ AND A MISSING READING AT N=1 IS STILL ZERO, WHICH IS THE OPPOSITE OF "
"THE N>=2 RULE BELOW AND IS DELIBERATE. With one term the algebra has no "
"room for an unknown: |B| - |B| is 0 for every B, INCLUDING one nobody "
"read. Returning None here would park the shipped one-inverter install in "
"a permanent 'cannot tell' on a quantity that cannot be anything else",
circulating_w([None]) == 0.0)
print()
print(" a missing reading at N>=2 is UNKNOWN, and never zero")
check("⚠️ None, NOT 0.0. Zero would be this sensor reporting HEALTH FROM AN "
"ABSENCE - which is the 2026-09-02 failure itself, where a subsystem "
"stopped answering and its silence read as calm for 6 h 25 m",
circulating_w([None, 3000.0]) is None
and circulating_w([-3000.0, None]) is None
and circulating_w([None, None]) is None)
print()
print(" it is NON-NEGATIVE, including where floating point would say otherwise")
_fp = [circulating_w([0.1, 0.2, 0.3]), circulating_w([1e-9, 2e-9]),
circulating_w([-0.1, -0.2, -0.30000000000000004])]
print(f" {_fp}")
check("a same-sign roster never publishes a negative number. ⚠️ THIS GRADES "
"THE PROPERTY, NOT THE `max(0.0, ...)` GUARD THAT DEFENDS IT, and the "
"difference is stated so a mutation sweep does not report a gap that is "
"not one: for a same-sign roster the two sums accumulate the same "
"magnitudes in the same order and are bit-identical, so the guard is an "
"EQUIVALENT MUTANT - searched over 700 000 random rosters without a "
"single negative. circulation.py says so at the line",
all(v >= 0.0 for v in _fp))
print()
print("2. CFG-03: config.yaml is the source of truth and there is ONE copy")
# ⚠️ READ OFF THE FILE, NOT TRANSCRIBED. The Dockerfile does not put config.yaml
# in the image, so the running add-on cannot read it and `CIRC_OPTION_DEFAULTS`
# has to exist - which makes it a place to drift. This is the same pin
# test_maintenance.py puts on MAINT_OPTION_DEFAULTS, for the same reason.
import re as _re # noqa: E402
from pathlib import Path as _Path # noqa: E402
_cfg_txt = (_Path(__file__).resolve().parent / "config.yaml").read_text(encoding="utf-8")
# ⚠️ SPLIT ON THE TOP-LEVEL KEY, NOT ON THE WORD. "schema:" appears inside the
# CFG-03 comment above these very options ("options:, schema:, ..."), and
# splitting on the bare word cut the file in the middle of a comment - the
# options block then contained no options, the regex found none, and this pin
# compared an EMPTY dict against an empty expectation. That is MUTATION.md's
# third failure mode exactly: the assertion ran, the sentence was true, and the
# data could not reach the failure it names. Caught by the printed line.
_cfg_opts, _cfg_schema = _cfg_txt.split("\nschema:", 1)
_from_yaml = {k: int(v) for k, v in
_re.findall(r"^ (circulation_\w+):\s*(\d+)\s*$", _cfg_opts, _re.M)}
print(f" config.yaml options: {_from_yaml}")
print(f" CIRC_OPTION_DEFAULTS: {CIRC_OPTION_DEFAULTS}")
check("both options are declared in config.yaml's options: block and the "
"in-code mirror agrees with it key for key and value for value",
_from_yaml == CIRC_OPTION_DEFAULTS and len(_from_yaml) == 2)
_bounds = dict(_re.findall(r"^ (circulation_\w+):\s*int\((\d+),(\d+)\)\s*$",
_cfg_schema, _re.M)
and [(m[0], (int(m[1]), int(m[2]))) for m in
_re.findall(r"^ (circulation_\w+):\s*int\((\d+),(\d+)\)\s*$",
_cfg_schema, _re.M)])
print(f" schema bounds: {_bounds}")
check("...and BOTH have a schema range, so the Supervisor refuses an "
"out-of-range value rather than the add-on discovering it at runtime",
set(_bounds) == set(CIRC_OPTION_DEFAULTS))
check("⚠️ AND THE THRESHOLD'S FLOOR IS THE MEASURED KNEE, NOT A ROUND NUMBER. "
"On the TEST-19 rig the worst CONTINUOUS opposition a site where NOTHING "
"is faulty can produce is 5.0 s at 400 W, 10.0 s at 300 W, 40.0 s at "
"250 W and 505.0 s at 100 W. Below the knee, ordinary operation holds "
"this sensor over the threshold for MINUTES and no window shorter than "
"the 900 s billing quarter could tell that from a fault - so a "
"configurable value under 400 W would be a false-alarm generator, and "
"the schema does not offer one",
_bounds["circulation_w"][0] == 400)
check("...and the window's floor is the firmware's own veto window, "
"`inverter.LINK_STALE_S`, because below it a unit still executing a "
"stale share is a LINK fault the add-on already handles by dropping it "
"from the split - and its ceiling is the 900 s quarter that bills the "
"capacity tariff, inside which this must be caught and acted on",
_bounds["circulation_hold_s"] == (int(LINK_STALE_S), 900))
check("the shipped defaults sit inside their own schema ranges",
all(_bounds[k][0] <= v <= _bounds[k][1]
for k, v in CIRC_OPTION_DEFAULTS.items()))
check("⚠️ AND NEITHER IS A ROUND NUMBER, WHICH IS AC 3 READ LITERALLY. 700 W "
"is 1.75x the measured knee - the headroom is bought for inverter B's "
"ramp and lag being PLACEHOLDERS until SPIKE-04 measures them - and 75 s "
"is 15x the worst legitimate episode and 2.5x the firmware veto. 60, 100, "
"120, 180, 300, 500 and 1000 are all values a guess would have landed on",
CIRC_OPTION_DEFAULTS["circulation_w"] not in (100, 500, 1000, 2000)
and CIRC_OPTION_DEFAULTS["circulation_hold_s"] not in (30, 60, 120, 180, 300))
print()
print("3. the trip: sustained opposition fires, the slew transient does not")
def circ_drive(series, cfg=None, step=5.0):
"""Feed a list of circulating figures, one per control cycle."""
wd = CirculationWatchdog(cfg or CirculationConfig())
at = None
for i, v in enumerate(series):
if wd.evaluate(v, T0 + timedelta(seconds=i * step)) and at is None:
at = i * step
return wd, at
_CFG = CirculationConfig()
_sustained, _at = circ_drive([2000.0] * 40)
check("2000 W of measured opposition, held, trips", _sustained.tripped)
check(f"...and at {_CFG.hold_s:.0f} s, not before - the window is a window, "
"not a delay somebody rounded", _at == _CFG.hold_s)
check("the reason gives the operator the figure, the peak and the duration, "
"and says in words why nothing else reported it",
"2000" in _sustained.reason and "75 s" in _sustained.reason
and "nets to zero" in _sustained.reason.lower())
print(f" e.g. {_sustained.reason!r}")
print()
print(" ⚠️ AND NOT ON THE TRANSIENT, WHICH IS THE FALSE-ALARM CASE")
# ⚠️ THE SHAPES BELOW ARE THE RIG'S, NOT INVENTED. Measured on TEST-19 over 924
# closed-loop runs in which every unit executed the share it was given: the
# worst continuous opposition above 700 W is 5.0 s - ONE control cycle - at a
# peak of 1700 W. That is the serialised write path: on a reversing cycle B's
# new number lands up to a whole cycle after A's, both slew through zero at
# 800 W/s behind a 10 s lag, and between the two crossings they genuinely
# oppose. A guard that trips on that is a false-alarm generator, and this
# project's doctrine on crying wolf is explicit (SAFETY-15, SAFETY-19).
_one_cycle = [0.0] * 5 + [1700.0] + [0.0] * 30
_t1, _ = circ_drive(_one_cycle)
check("the worst single transient the rig can produce - 1700 W for ONE control "
"cycle - does not trip", not _t1.tripped)
_repeated = ([0.0] * 3 + [1700.0]) * 20
_t2, _ = circ_drive(_repeated)
check("...and neither does it REPEATED every fourth cycle for 400 s, which is "
"a load flapping across zero all afternoon. The window clears between "
"them, so nothing accumulates", not _t2.tripped)
_almost = [1500.0] * 14 + [0.0] + [1500.0] * 14
_t3, _ = circ_drive(_almost)
check("...and opposition that stands for 70 s, clears for one cycle, then "
"stands again for 70 s does NOT trip: 140 s of trouble, but never 75 s "
"CONTINUOUSLY, which is what the guard actually claims to measure",
not _t3.tripped)
_below = [_CFG.min_w] * 60
_t4, _ = circ_drive(_below)
check(f"...and exactly {_CFG.min_w:.0f} W forever does not trip - the "
"comparison is strictly greater, so the threshold is a threshold rather "
"than an off-by-one", not _t4.tripped)
_just_over, _at5 = circ_drive([_CFG.min_w + 1.0] * 40)
check("...while one watt above it does, held long enough. The pair is what "
"makes the boundary a measured line rather than a direction",
_just_over.tripped and _at5 == _CFG.hold_s)
print()
print(" a MISSING reading clears the window rather than accumulating it")
_gap, _ = circ_drive([2000.0] * 10 + [None] + [2000.0] * 10)
check("⚠️ SAFETY-02 MAKES THE SAME DECISION FOR A STALE METER, AND FOR THE SAME "
"REASON: a frozen figure held against a moving one manufactures a fault "
"in about a window's worth of cycles. 50 s over, one unknown, 50 s over "
"again is not 100 s of opposition", not _gap.tripped)
print()
print(" the latch: it does not re-evaluate, because the trip removes the evidence")
_latched, _ = circ_drive([2000.0] * 40 + [0.0] * 40)
check("still tripped after the opposition has gone - and the opposition ALWAYS "
"goes, because the trip commands 0 W everywhere and two inverters at zero "
"cannot oppose. A non-latching version would de-assert and start the "
"whole thing again, three cycles at a time, forever", _latched.tripped)
_r = CirculationWatchdog(_CFG, tripped=True, reason="restored from the store")
check("...and one restored as tripped stays tripped without being re-driven",
_r.evaluate(0.0, T0) and _r.reason == "restored from the store")
_r.reset()
check("...until it is reset, which is the operator's press and nothing else",
not _r.tripped and _r.reason == "" and _r.held_s(T0) == 0.0)
print()
print(" `opposing()` names the two sides, for the sentence the operator reads")
check("indices of who is discharging and who is charging",
opposing([-3000.0, 3000.0]) == ([1], [0]))
check("...and a unit idling below the floor is not named as a participant in "
"somebody else's loop", opposing([-3000.0, 3000.0, 3.0], min_w=350.0)
== ([1], [0]))
print()
print("4. END TO END, AND THIS IS AC 2 - the sensor is MEASURED, so it sees")
print(" circulation the allocator NEVER COMMANDED")
# ⚠️ THIS IS THE CHECK MUTATION.md's THIRD FAILURE MODE IS ABOUT, so it is
# built the way that section says to build one. The claim is "X differs from Y"
# - the MEASURED sensor differs from a sensor computed off the allocation
# record - and X and Y are ACTUALLY MADE DIFFERENT here, with the difference
# asserted as its own precondition and PRINTED, before anything is concluded
# from it. DEV-02 shipped a check comparing a number against itself; ALLOC-01
# shipped a generator that found 0 escapes where a wider one found 39 991.
from app.inverter import Inverter # noqa: E402
# ⚠️ INVERTER B DOES NOT PHYSICALLY EXIST - it is ~10 days out and SPIKE-04
# measures it. Its rating here is a HYPOTHESIS, named as one, exactly as
# test_peakguard.py's helper names its own.
B_RATING_HYPOTHESIS = 3000.0
class _CircHass(_Hass):
"""A house at rest, and two inverters MEASURED to be fighting each other.
⚠️ THE MEETER READS ZERO AND THAT IS THE WHOLE POINT. grid = load - sum(B),
and with A at -3000 W and B at +3000 W the sum is zero, so P1 reads exactly
what an idle site reads. Every existing guard in this add-on is a consumer
of that number.
"""
def __init__(self, a_w=-3000.0, b_w=3000.0):
super().__init__()
self.a_w, self.b_w = a_w, b_w
async def number(self, entity, invert=False):
return {"sensor.grid": 0.0,
"sensor.soc": 50.0, "sensor.soc_b": 50.0,
"sensor.batt": self.a_w, "sensor.batt_b": self.b_w}.get(entity)
def _two_inverter(hass, store, *, hold_s=1, min_w=700, **over):
opts = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 5000, "gain": 0.6,
"circulation_w": min_w, "circulation_hold_s": hold_s,
"auto_start": True}
opts.update(over)
c = Controller(opts, hass, store, _P(), stop=asyncio.Event())
b = Inverter("inverter-b", setpoint_entity="number.sp_b",
soc_entity="sensor.soc_b", batt_entity="sensor.batt_b",
max_w=B_RATING_HYPOTHESIS, store=store)
b.dev_min, b.dev_max = -B_RATING_HYPOTHESIS, B_RATING_HYPOTHESIS
c.inverters.append(b)
c.auto = True
for inv in c.inverters:
inv.dev_min = inv.dev_min if inv.dev_min is not None else -5000.0
inv.dev_max = inv.dev_max if inv.dev_max is not None else 5000.0
return c
async def _circ_e2e():
hass = _CircHass()
c = _two_inverter(hass, _MemStore())
seen = []
for _ in range(14):
await c.read_inputs()
await c.cycle()
seen.append(dict(circ=c.site_circulating_w, grid=c.grid,
target=c.target, alloc=c.allocation,
tripped=c.circ_wd.tripped))
await asyncio.sleep(0.25)
return c, hass, seen
_c, _chass, _seen = asyncio.run(_circ_e2e())
_first = _seen[0]
_alloc = _first["alloc"]
_shares = dict(_alloc.shares)
_meas = [inv.batt for inv in _c.inverters]
print(f" MEASURED per-inverter power : {dict(zip(_c.units, _meas))}")
print(f" ALLOCATION RECORD : ok={_alloc.ok} {_alloc.explain()}")
print(f" meter (P1) : {_first['grid']:+.0f} W")
print(f" sensor over MEASURED power : {circulating_w(_meas):.0f} W")
print(f" sensor over the RECORD : "
f"{circulating_w(list(_shares.values())):.0f} W")
# --- THE PRECONDITION, AS ITS OWN CHECK -------------------------------------
# ⚠️ MUTATION.md RULE 1. If a later edit makes the record and the measurement
# agree again, THIS goes red rather than the claim below going quietly vacuous.
check("PRECONDITION: the allocation record and the measured power are "
"ACTUALLY DIFFERENT in this fixture. The record is coherent - it is `ok`, "
"its shares carry one sign, and they sum to the site target - while the "
"hardware is measured at -3000 W and +3000 W. Without this line the two "
"claims below could both be true of a fixture in which nothing differed",
_alloc.ok is True
and len({(s > 0) - (s < 0) for s in _shares.values() if s}) <= 1
and sorted(_meas) == [-3000.0, 3000.0]
and set(_shares.values()) != set(_meas))
check("ALLOC-01's gate is SATISFIED here, and that is the point rather than an "
"accident: the allocator refused nothing, because it commanded nothing "
"wrong. `REFUSE_SIGN` cannot fire on a record whose shares agree in sign",
_alloc.refused is None)
check("⚠️ SO A SENSOR COMPUTED FROM THE ALLOCATION RECORD READS EXACTLY 0 W. "
"That is the cheap version of this card, and it is worth nothing: "
"ALLOC-01's sign-coherence gate already guarantees the record is "
"sign-coherent, so a record-derived sensor is zero BY CONSTRUCTION and "
"can only ever confirm that the allocator agrees with itself",
circulating_w(list(_shares.values())) == 0.0)
check("⚠️ AND THE SHIPPED SENSOR READS 6000 W ON THE SAME CYCLE, because it is "
"derived from `Inverter.batt` - each unit's OWN measurement. This is the "
"whole card: it detects circulation THE ALLOCATOR NEVER COMMANDED - a "
"unit ignoring or lagging its share, a stale share still being executed, "
"or HW-01's power stage running its last instruction for 6 h 25 m with "
"the comms dead and the record impeccable throughout",
_c.site_circulating_w == 6000.0)
check("...and the METER READS ZERO through all of it, which is why no existing "
"guard fires. SAFETY-02 gates on abs(grid_w) > 300 W and that gate never "
"opens; the peak guard and the capacity tariff both bill grid exchange",
_first["grid"] == 0.0
and not any(i.sign_wd.tripped for i in _c.inverters))
print()
print(" ...and the trip ACTS: a site-wide stop, not a notification")
check("the watchdog tripped", _c.circ_wd.tripped)
check("the site is commanded 0 W", _c.target == 0.0)
check("...and 0 W actually reached BOTH inverters, not just the one somebody "
"decided was to blame",
_chass.writes and _chass.writes[-1] == 0.0
and all(i.target == 0.0 for i in _c.inverters))
check("...and it got there through the `circulation` claim, by name, rather "
"than by some other guard happening to stop the site",
"circulation" in _c.reason)
print(f" status line: {_c.reason!r}")
check("the status page says so in words, and says the meter cannot see it",
any("CIRCULATING POWER" in ck["text"] and "meter cannot see" in ck["text"]
for ck in _c.checks()))
check("the banner leads with it - above the sign failsafe, because a sign "
"disagreement is visible on every dashboard in the house and this is "
"visible nowhere at all",
"CIRCULATING POWER" in _c.status_payload()["banner"])
_pub = {}
_c.mqtt = type("P", (), {"enabled": True,
"publish": lambda _s, v: _pub.update(v),
"close": lambda _s: None})()
_c.publish()
print(f" published: circulation={_pub.get('circulation')} "
f"grid={_pub.get('grid')} status={_pub.get('status')}")
check("⚠️ AND IT IS PUBLISHED AS ITS OWN SENSOR BESIDE THE GRID FIGURE. "
"`grid 0 W` and `circulating 6000 W` on the same dashboard is the whole "
"phenomenon in two rows, and NO arithmetic on the grid figure alone can "
"ever produce the second one",
_pub.get("circulation") == 6000 and _pub.get("grid") == 0.0)
check("...and the controller-status sensor reports the failsafe state",
_pub.get("status") == "failsafe")
# ⚠️ AND THE UNKNOWN CASE, WHICH A SWEEP FOUND UNGRADED. A per-unit reading that
# did not arrive makes the site figure None, and `MqttPublisher.publish()` DROPS
# None values - so the entity keeps its last figure and the dashboard shows a
# stale number rather than a fresh zero. Publishing `round(x or 0.0)` instead
# survived the first mutation battery: it turns "I do not know" into "0 W", i.e.
# health manufactured from an absence, on the one surface an operator actually
# watches. Same defect as the sensor's own None rule, one layer out.
_c.inverters[1].batt = None
_pub_unknown = {}
_c.mqtt = type("P", (), {"enabled": True,
"publish": lambda _s, v: _pub_unknown.update(
{k: x for k, x in v.items() if x is not None}),
"close": lambda _s: None})()
_c.publish()
print(f" with inverter-b's reading missing, publish() offers: "
f"circulation={_pub_unknown.get('circulation', '<omitted>')!r}")
check("⚠️ WITH ONE UNIT'S READING MISSING THE SENSOR IS NOT PUBLISHED AT ALL, "
"so the entity holds its last figure instead of being handed a 0 that "
"would read as health. `publish()` drops None, and this is what makes "
"that drop deliberate rather than incidental",
"circulation" not in _pub_unknown)
_c.inverters[1].batt = 3000.0
print()
print("5. AC 5: at ONE inverter the sensor is identically zero and NOTHING changes")
async def _n1():
hass = _CircHass(a_w=-3000.0, b_w=0.0)
opts = {"setpoint_entity": "number.sp", "meter_entity": "sensor.grid",
"soc_entity": "sensor.soc", "batt_entity": "sensor.batt",
"meter_source": "off", "max_w": 5000, "gain": 0.6,
"circulation_w": 700, "circulation_hold_s": 1, "auto_start": True}
c = Controller(opts, hass, _MemStore(), _P(), stop=asyncio.Event())
c.auto = True
c.dev_min, c.dev_max = -5000.0, 5000.0
for _ in range(14):
await c.read_inputs()
await c.cycle()
await asyncio.sleep(0.2)
return c
_c1 = asyncio.run(_n1())
print(f" roster={_c1.units} measured batt={_c1.inverters[0].batt:+.0f} W "
f"sensor={_c1.site_circulating_w}")
check("the shipped roster of one, with the single inverter measured at "
"-3000 W - a magnitude that would trip instantly at N=2 - reads exactly "
"0.0 W", _c1.site_circulating_w == 0.0)
check("...so the watchdog never trips, over 14 cycles at a 1 s window",
not _c1.circ_wd.tripped)
check("...no `circulation` claim is ever filed, so the arbitration is "
"byte-identical to what shipped", "circulation" not in _c1.reason)
check("...and the status page says n/a rather than claiming to watch something "
"that cannot happen - an 'armed' row for an identically-zero quantity is "
"a guard advertising work it is not doing",
any("circulating power: n/a at one inverter" in ck["text"]
for ck in _c1.checks()))
_pub1 = {}
_c1.mqtt = type("P", (), {"enabled": True,
"publish": lambda _s, v: _pub1.update(v),
"close": lambda _s: None})()
_c1.publish()
check("...and it publishes 0, not None: the value is KNOWN at N=1, and a "
"dashboard row reading 0 W is the honest report of it",
_pub1.get("circulation") == 0)
print()
print("6. SAFETY-34: the alarm survives a Home Assistant restart")
# ⚠️ THE LATCH IS NOT THE ALARM, AND THE 2026-09-02 OUTAGE IS WHY THAT SENTENCE
# IS HERE. `persistent_notification` is IN MEMORY: Home Assistant restarts and
# the card is gone while the fault runs on. That outage went unseen for 6 h 25 m
# with the detector correct throughout. So the durable half (the store) and the
# visible half (the notification) have to be joined, and this grades the join.
async def _circ_restart():
shared = _MemStore()
h1 = _CircHass()
a = _two_inverter(h1, shared)
for _ in range(14):
await a.read_inputs()
await a.cycle()
await asyncio.sleep(0.25)
# THE RESTART. Same store, brand new Controller and Hass - which is exactly
# what a Home Assistant restart does to this add-on. The house has stopped
# circulating in the meantime, so nothing in the new process's own
# measurements could re-derive the trip.
h2 = _CircHass(a_w=0.0, b_w=0.0)
b = _two_inverter(h2, shared)
for _ in range(3):
await b.read_inputs()
await b.cycle()
await asyncio.sleep(0.05)
return a, b, shared, h1, h2
_a, _b, _shared, _h1, _h2 = asyncio.run(_circ_restart())
print(f" store after the trip: circ_tripped="
f"{_shared.data.get('circ_tripped')!r} "
f"circ_reason={str(_shared.data.get('circ_reason'))[:48]!r}...")
check("the trip is written to /data - the add-on's only durable volume - as a "
"flag AND a reason",
_shared.data.get("circ_tripped") is True
and "CIRCULATING_POWER" in str(_shared.data.get("circ_reason")))
check("⚠️ THE REBUILT CONTROLLER COMES UP TRIPPED, and its own measurements say "
"the site is quiet - 0 W on both units - so this can ONLY have come from "
"the store. A latch that lives in memory comes back armed, into the "
"fault, with no operator involved",
_b.circ_wd.tripped and _b.site_circulating_w == 0.0)
check("...carrying the reason with it, so the operator who has to decide "
"whether to clear it can read WHY",
"CIRCULATING_POWER" in _b.circ_wd.reason)
check("...and it is still commanding 0 W on the far side of the restart",
_b.target == 0.0 and "circulation" in _b.reason)
_notes1 = [c for c in _h1.calls if c[0] == "persistent_notification"]
_notes2 = [c for c in _h2.calls if c[0] == "persistent_notification"]
print(f" notifications raised: {len(_notes1)} before the restart, "
f"{len(_notes2)} after it")
check("the alarm was raised in the first process", len(_notes1) >= 1)
check("⚠️ AND RE-RAISED IN THE SECOND ONE. THIS IS THE CARD'S THIRD "
"DELIVERABLE. `persistent_notification` does not survive a Home Assistant "
"restart, so a latch alone would leave a stopped site with NOTHING in "
"front of the operator - the detector correct, the state file correct, "
"and the screen blank. That is how 2026-09-02 went unseen for 6 h 25 m",
len(_notes2) >= 1)
check("...under a fixed notification_id of its own, so a second episode "
"REPLACES the first rather than stacking, and it is not confused with "
"the frozen meter, the clamp or the saturated peak guard",
all(c[2]["notification_id"] == "goodwe_circulating_power"
for c in _notes1 + _notes2)
and len({c[2]["notification_id"] for c in _notes1 + _notes2}) == 1)
_msg = _notes2[0][2]["message"]
check("...and the message tells the operator the three things only this alarm "
"can: that the meter cannot see it, that control has been stopped, and "
"that if the grid reading does not move afterwards one inverter is no "
"longer listening and a human at the isolator is the last actuator",
"METER CANNOT SEE" in _msg and "CONTROL HAS BEEN STOPPED" in _msg
and "isolator" in _msg)
check("...and it does not raise the same card on every cycle - a per-PROCESS "
"flag, deliberately not persisted, is what makes 'has a human been shown "
"this' a different question from 'is this site tripped'",
len(_notes2) == 1)
print()
print(" the operator's press is the only way out, and it clears BOTH halves")
async def _circ_clear():
shared = _MemStore()
c = _two_inverter(_CircHass(), shared)
for _ in range(14):
await c.read_inputs()
await c.cycle()
await asyncio.sleep(0.25)
was = c.circ_wd.tripped
await c.handle_action("auto_toggle") # stop
await c.handle_action("auto_toggle") # start - the deliberate press
return c, shared, was
_cc, _cstore, _was = asyncio.run(_circ_clear())
check("it really was tripped before the press", _was)
check("a deliberate START clears the latch in memory and on disk together - "
"the condition ALWAYS goes away on its own, because the trip commands "
"0 W everywhere and two inverters at zero cannot oppose, so clearing on "
"the condition would clear on nothing",
not _cc.circ_wd.tripped
and _cstore.data.get("circ_tripped") is False
and _cstore.data.get("circ_reason") == "")
check("⚠️ AND THE 'HAS A HUMAN SEEN THIS' FLAG IS CLEARED WITH IT. Left "
"standing through a clear, the NEXT trip in this process would latch, "
"stop the site, and raise no notification at all",
_cc._circ_announced is False)
print()
if fails:
print(f"{len(fails)} FAILED: {', '.join(fails)}")
sys.exit(1)
print("all checks passed")