# SAFETY-118 - the peak forecast is read in its own unit **Status: for review.** Tests: `test_safety118.py`. `peak_forecast_entity` was read as a bare number, and anything under 50 was multiplied by 1000 ("accept kW or W"). A W sensor reading 17 to 45 W, which a real site did 430 times in one morning, was taken as 17 to 45 kW. The validator also called a kW sensor wrong, which was false for this entity. Decision: the size rule is gone. The entity is read through `pv.watts()`, the same unit table and reader as the solar entities, so W, kW, MW and the rest convert by the sensor's own `unit_of_measurement`. No unit, or a unit that is not power (kWh), means the forecast is not used, exactly as if the option were empty: the loop cap and every non-forecast peak step still apply. One WARNING per cause, and a status row and a settings note say the same. No size rule can be right in both units: 30 W and 30 kW are both ordinary. The read is still one `GET /api/states/` per cycle, as `hass.number()` made.