# SAFETY-94 - a battery that lags or reverses is not frozen or refusing **Status: implemented 2026-10-03, for review.** Tests: `test_safety94.py` (rig: `tools/safety94_rig.py`). Also closes SAFETY-58. SAFETY-74 stays open. ## The defects 1. **Stale-reading gate (SAFETY-37).** Its 35 s ran from the register's last change. After a rest that clock was already past 35 s, so the first read after a new command tripped it, before the register could answer. Live 2026-10-03 (0.14.0, N=2): 17:39:16 B and 17:39:25 A (load ramp after a rest), 19:00:04 A (drain start), 21:21:22 B (drain -> charge). Each was 1 s after its command; each register answered within 11 s. This is SAFETY-58's shape. 2. **Refusal at N=1 (SAFETY-52).** `compute()` engaged after `SETTLE_CYCLES` frozen cycles if the reading was under 100 W at that moment. The frozen cycles include a reversal through the battery's lag. At a 1 s meter the 12th cycle comes as a battery reversing out of a charge passes 0 W (SAFETY-85 rig, O1: "gave -20 W for 13 cycles"). The refusal then held 0 W, the battery settled at 0 W, never gave 100 W, and waited for the 15-minute probe. N>1 already required 22 s in the band, so it was safe at a 10 s lag but not at 20 s. ## What changed - **The gate counts only time the register was asked to move** (`freshness.Freshness._oblige`). A read counts the time since the last read when, at that read, the command is 250 W or more and has moved 250 W from where it stood at the register's last change. A register change (or a SAFETY-57 release) restarts the count. A command flapping in and out of the ask still adds up (frozen register, 0/1500 W every 5 s: trip at 69 s). The conjunction, `MOVE_W` and `RELEASE_S` are unchanged. - **The bound is unchanged at 35 s and now means what its derivation says.** The floor was always "how long a healthy register takes to answer a command": 6 s plant + 10 s publish + 1 s read = 17 s. The band `[2 x 17, 0.5 x 75] = [34, 37.5]` holds. Live answers measured: 1.4, 3, 6 and 11 s after the command. - **Refusal evidence is the same at every roster size** (`main.Controller._gave_nothing`, SAFETY-73's count moved into a method). The reading must stay under 100 W, one way, while asked over 200 W, for 12 cycles spanning 22 s. At N=1 `compute()` gets this as `gave_nothing` and needs it on top of its own freeze test. `None` (compute alone) keeps the old law. - **The evidence restarts when the reading moves 50 W towards the ask** (`REFUSED_PROGRESS_W`). A refusing battery reads flat (-3/-4 W live). Live readings wander by under 25 W at rest. A first-order lag crossing the band gains 50 W in at most 0.4 tau, so it cannot fill 22 s unless tau > 54 s. This also covers B, whose reading is 100 W below its power. ## Bounds and worst-case catch | fault | before | after | budget | |---|---|---|---| | register frozen, then asked to move | 0-35 s after the ask (often 1 s) | 35 s after the ask (+1 read) | SAFETY-37: 35 s, under the 75/85 s consumer holds | | register frozen at rest reading ~0 W | stale 1 s after the ask | refused or stale, 0 W within 23-35 s | the same | | refusing battery, 1 s meter, N=1 | 11-16 s | 22-28 s | SAFETY-73's 22 s span (+ one 10 s publish) | | refusing battery, 2 s meter | 22-28 s | 22-28 s | unchanged | | refusing battery, 5 s meter | N=1 35-41 s, N=2 41-55 s | N=1 40-45 s, N=2 50-55 s | 12 cycles = 55-60 s | Rig: `test_safety94.py` part 3. A release after SAFETY-57 still exposes the held number for one 35 s window of asking, so 35 < 75 < 85 still holds. ## Before -> after - Live replay (part 1): 4 trips -> 0. - Refusing B (its -100 W idle reading): see SAFETY-97. - Rig, 10 s lag, N=1 and N=2, 1/2/5 s meters, two register shapes, 48 runs (part 2): before 27 stale trips and 1 refusal, after 0 and 0. - Reversals, lag 10 and 20 s, 1 s meter (part 2): before N=1 6 stale / 3 refused, N=2 6 / 1; after 0 / 0. - 16-day loop capture (`test_freshness.py` part 8): 93 trips -> 59. Trips answered within 20 s: 21 -> 1. Two of the removed trips were not quick: a register held 351 s under a command hovering at the 250 W travel edge (under 35 s of asking before it moved; survivor 2's shape), and a refusing battery the gate had caught only on a passing ramp (SAFETY-52's refusal covers it). ## SAFETY-58 and SAFETY-74 - **SAFETY-58 is fixed** by this change: its card asks for the clock to start with the obligation and for the bound to be re-derived. Both are done above. `test_freshness.py` survivor 5 is now graded as closed. - **SAFETY-74 is not fixed.** A battery capped at 300 W with a perfectly flat reading, 5 s meter, house stepping: 50 trips/h at N=1 and 80 at N=2 before, 37 and 60 after. With +-1 W dither: 0. A flat reading under a command that moved is exactly what the gate is for; telling "limited" from "frozen" needs a second signal (the meter, or SoC). ## Known gaps - ~~B's standby offset (-95 to -118 W at idle) puts a refusing B outside the 100 W band, so a refusing B never latched (review F1: at N=1 new, at N=2 as before).~~ **Fixed by SAFETY-97 in the same PR:** the band is centred on each unit's learned idle reading. `SAFETY-97-idle-offset.md`. - A command that asks only part of the time (a fraction d) is caught after 35 s of asking, which is 35/d s of wall time (0/1500 W every 5 s: 69 s). SAFETY-30's per-unit check restarts when its command stops opposing the held reading, which a lapsing ask normally does, so 35 < 85 holds there. SAFETY-31's circulation check (75 s) ignores the command, so its margin holds only while d >= 0.47. - A register frozen under a command that stays near the 250 W travel edge is caught late or not at all (survivor 2).