# GoodWe RS485 Controller Drives a GoodWe ES/BP battery inverter over its RS485 meter bus: holds net grid exchange at zero, and runs a monthly battery maintenance cycle so the BMS can balance cells and recalibrate its coulomb counter. Installers: read `FIELD-GUIDE.md` in the repository. It is not optional reading — it contains the commissioning gates and the failure modes. ## Before you start You need: - A GoodWe **ES / BP family** inverter (AA55 / RS485 meter-bus generation) - The vendor's meter-emulating controller **disconnected** from the bus - A T-CAN485 (ESP32) flashed with `firmware/goodwe-master.yaml` - A grid-power sensor already working in Home Assistant, updating every ~5–10 s ## The safety model, in short The inverter **holds its last command forever** — it has no meter-timeout. So: - The ESP32 commands 0 W if this add-on stops refreshing for ~30 s, and keeps commanding it. - This add-on commands 0 W when its inputs go missing, when you stop control, and when it shuts down. - This add-on commands 0 W **and latches there** if what it is commanding and what the meter reads point opposite ways for three minutes — see "The sign-disagreement failsafe" below. - The **optional RS485 e-stop** is the only thing that covers this machine dying. Without it, a failed host leaves the battery latched at its last command until someone intervenes. - This add-on **raises an alarm — and nothing more —** when the meter keeps answering with a reading that never changes while the command sits at the rail. See "The frozen-meter alarm" and, before you rely on it, "Capacity-tariff exposure of the grid-following loop". **If anything looks wrong: stop the add-on.** That commands 0 W and the hardware holds it there. ## Configuration ### Sources | option | required | meaning | |---|---|---| | `meter_entity` | yes | Net grid power. **Positive must mean importing** | | `meter_invert` | | Flip the sign if the meter reports the other way | | `soc_entity` | yes | Battery state of charge — use the **ESP32's own read** | | `batt_entity` | yes | Battery power — again the ESP32's read, `+` = discharging | | `batt_invert` | | Flip if needed | | `setpoint_entity` | yes | The ESPHome `number.*_goodwe_setpoint_w` | Use the ESP32's readings rather than the inverter's cloud or dongle sensors: those serve cached values, and a stale reading here ends the maintenance charge phase having charged nothing. ### More than one inverter (`inverters`) The six keys above describe **one** inverter, and if that is your site there is nothing to do here — `inverters` ships empty and empty means *"the flat keys above describe the one inverter"*. **An install that upgrades into 0.6.0 reads identically to before: same entities, same rating, same behaviour, no operator action.** To run two, declare them. Each entry names its own actuator, its own rating and its own sensors: ```yaml setpoint_entity: "" # ⚠️ must be cleared — see below inverters: - name: inverter-a setpoint_entity: number.goodwe_a_setpoint_w soc_entity: sensor.goodwe_a_soc batt_entity: sensor.goodwe_a_battery_power max_w: 5000 - name: inverter-b setpoint_entity: number.goodwe_b_setpoint_w soc_entity: sensor.goodwe_b_soc batt_entity: sensor.goodwe_b_battery_power max_w: 3000 ``` | per-entry key | required | meaning | |---|---|---| | `name` | yes | Short identifier. It namespaces this unit's SAFETY-02 latch, heartbeat and write bookkeeping in the add-on's state file, so **two units may not share one** | | `setpoint_entity` | yes | This inverter's own ESPHome `number.*_goodwe_setpoint_w` | | `max_w` | yes | The supervised cap on what may be written to **this** inverter. The site's ceiling is the **sum** | | `soc_entity` | | This pack's state of charge | | `batt_entity` | | This unit's battery power, `+` = discharging | | `batt_invert` | | Flip if needed | ⚠️ **Nothing is inherited.** An entry that leaves out `soc_entity` has **no SoC sensor** — it does *not* fall back to the flat one. That is deliberate: every per-device value became per-instance in 0.5.x precisely so that no inverter is ever graded against a sibling's numbers, and a silent fallback would rebuild that in YAML. `name`, `setpoint_entity` and `max_w` are required of every entry for the same reason: there is no rating to borrow. ⚠️ **Clear the flat `setpoint_entity` when you declare a roster,** or the add-on refuses to start and says so. It is the single-inverter form and it is not read once a roster exists, so leaving it set means one of two things: it names an entity an entry also names — two writers on one actuator, which specs §1.5 makes a non-goal and the add-on refuses outright — or it names a different one, which nothing would ever write, leaving a site running quietly smaller than its configuration reads. `soc_entity`, `batt_entity`, `batt_invert` and `max_w` cannot be blanked (the schema gives them no empty value); they are simply not read, and the add-on writes one line into its action log at every start saying so. ⚠️ **Two inverters naming the same `setpoint_entity` are refused,** whichever keys they are declared under and whatever the capitalisation. Two independent setpoints on one inverter is the arbitration problem this add-on exists not to have. ⚠️ **Update the add-on first, then add the roster.** Home Assistant validates the options you save against the schema of the version that is *installed*, so `inverters` cannot be set before 0.6.0 is installed. The order is: update, then configure. ⚠️ **Going the other way — downgrading with a roster configured — is recoverable but NOT uneventful, and the add-on will not start until you refill a field.** The *schema* side is fine: the older version's schema has no `inverters` key, so it drops the key with a warning rather than refusing the whole blob (measured — `DECISIONS/CFG-04-inverter-roster.md` §E). The *add-on* side is not. Rule 9(e) requires the flat `setpoint_entity` be **cleared** when a roster is declared, so a config that downgrades cleanly is by construction a config whose flat actuator is blank — and the older version has nothing else to write to. It stops at startup validation with a refusal naming `setpoint_entity`, which is loud and in the log rather than silent, but it is an outage until someone puts the single-inverter entity back in that field. **Before downgrading, write down the `setpoint_entity` of the unit you want to keep running.** ### P1 meter ingestion `meter_entity` above expects one signed sensor, which usually means a template someone wrote by hand. Setting `meter_source` moves the whole derivation into the add-on, where it is done once and tested, and replaces `meter_entity` entirely. Which mode you want depends on what your P1 reader publishes, and there are two shapes in the wild: - **Two unsigned registers**, consumption and injection, which is what a Belgian P1 read over DSMR gives you → `ha_dsmr`, or `mqtt_p1` for a bridge. The add-on subtracts them. - **One signed figure**, positive = import and negative = export, which is what a HomeWizard P1 gives you (`sensor.p1_meter_active_power`) → `ha_signed`. The add-on splits it. `ha_dsmr` **cannot** read this: it wants two registers and rejects a negative one outright, which is every exporting telegram. Either way, do not build the missing shape out of template sensors. The point of `meter_source` is that the sign convention is derived in one tested place rather than in YAML nobody reviews underneath a safety input. > ✅ **If your meter is a HomeWizard P1, use `homewizard_local`, not > `ha_signed`.** It reads the same meter and produces the same numbers, but it > polls the meter directly instead of watching a Home Assistant entity — and > that is the difference between an age sensor a watchdog can threshold and one > it cannot. See "`sensor.p1_sample_age_s`" below; `ha_signed` remains for > installs where the meter is only reachable through Home Assistant. > ⚠️ **`ha_dsmr` and `mqtt_p1` have never processed a telegram from real > hardware.** No meter in this installation uses either one. Both were written > to the assumption in `specs.md` §5.2 that a Belgian P1 exposes two unsigned > registers, and the meter actually fitted here does not — it is the HomeWizard > P1 that `ha_signed` reads. They are covered by the unit checks in `test_p1.py` > and by an end-to-end test against a fake Home Assistant, and nothing more. > > This is recorded because the realistic way it bites is someone debugging a > meter problem months from now treating those two paths as proven and looking > for the fault elsewhere. If you are the first person to point one at a real > meter, expect to find something, and please update this note when you do. | option | default | meaning | |---|---|---| | `meter_source` | `off` | `off` keeps `meter_entity`. `ha_dsmr` subscribes to the DSMR integration over the HA WebSocket; `mqtt_p1` reads a topic; `ha_signed` subscribes to one signed entity over the HA WebSocket; `homewizard_local` polls a HomeWizard P1's own local API, bypassing Home Assistant | | `meter_phases` | 1 | 1 or 3. Must match the telegram, or every telegram is rejected and logged | | `meter_max_age_s` | 30 | Beyond this the reading is stale and grid power reads as *missing*. On its own it does **not** command 0 W — see the timing note below. It is also the longest a reading is held forward into the 15-minute average | | `meter_poll_s` | 5 | `homewizard_local` only. Seconds between polls. **Must be well under `meter_max_age_s`** — see below | | `p1_host` | | `homewizard_local` only. The meter's own address, `host` or `host:port` (e.g. `192.168.2.250`) | | `meter_mqtt_topic` | | `mqtt_p1` only | | `p1_import_entity` | | The **unsigned** consumption sensor. Do not point this at a signed template | | `p1_export_entity` | | The **unsigned** injection sensor | | `p1_phase_import_entities` | `[]` | L1..L3, in order. Needed for the capacity-tariff peak on a three-phase connection | | `p1_phase_export_entities` | `[]` | L1..L3, in order | | `p1_net_entity` | | `ha_signed` only. The **signed** net-power sensor: `+` import, `-` export | | `p1_phase_net_entities` | `[]` | `ha_signed` only. L1..L3, in order, each signed the same way. Needed for the capacity-tariff peak on a three-phase connection. **The list length must equal `meter_phases`** | Both per-phase lists are checked against `meter_phases` **once at startup**: a list of the wrong length disables P1 ingestion with an error in the log, rather than letting every telegram fail its phase-count check one at a time. Leaving the list empty is fine and is not an error — you simply get no per-phase figures, and therefore no capacity-tariff peak. On a three-phase connection that is a much bigger omission than it looks: on a surveyed reading here the phases carried 2769 W of import while the connection netted 187 W, so the billed quantity is understated roughly fifteenfold if the phases are missing. #### How long a dead meter takes to reach 0 W `meter_max_age_s` and `stale_input_s` **stack**. They are two different clocks and neither one is the whole answer: | step | option | default | |---|---|---| | telegrams stop, P1 sample goes stale, grid power starts reading *missing* | `meter_max_age_s` | 30 s | | inputs have been missing long enough for the loop to command 0 W | `stale_input_s` | 15 s | | **total, meter death → 0 W commanded by this add-on** | | **45 s** | So in P1 mode `stale_input_s` is *not* "how long inputs may be missing before commanding 0 W" measured from the meter dying — it is measured from the moment the P1 sample already went stale. Size the pair together: the ESP32's own watchdog commands 0 W after ~30 s of silence from this add-on regardless, and that layer is unaffected by either option. There is **no fallback to an inverter-side power figure**, deliberately. The inverter's own AC power tracks its battery almost perfectly and the real meter hardly at all, so a controller that failed over to it would be regulating against its own output while looking healthy. The `mqtt_p1` payload is one JSON object per telegram, and the schema is strict — a key it does not recognise is a telegram from something other than what was tested, and guessing a key here means guessing a kilowatt: ```json {"import_w": 1234.0, "export_w": 0.0, "phases": [{"import_w": 500, "export_w": 0}, {"import_w": 400, "export_w": 0}, {"import_w": 334, "export_w": 0}], "timestamp": "2026-08-24T18:00:05+02:00"} ``` `phases` and `timestamp` are optional; `timestamp` must carry a UTC offset. Where it is present it is used for the age, which is what stops a retained message replayed on reconnect from presenting a ten-minute-old reading as current. #### `homewizard_local` — polling the meter instead of Home Assistant Set `p1_host` to the meter's address and the add-on does `GET /api/v1/data` on it every `meter_poll_s` seconds, reading `active_power_w` (signed, same convention as `ha_signed`) and the three `active_power_l{1,2,3}_w` fields. Home Assistant is not involved: no entity, no WebSocket, no integration to mis-configure. Per-phase figures are used only when the meter serves all `meter_phases` of them — a single-phase meter returns `null` for L2/L3, and the connection-level reading is still accepted on its own. **Why this mode exists:** every HTTP response is an *arrival*. The meter answered, now, with its current reading — whether or not the number moved. That is the signal `sensor.p1_sample_age_s` needs and the one Home Assistant cannot give it at all (see the note below). It is also simply fewer moving parts: the five-second cadence is the meter's own, rather than an integration's polling of it re-published as a state change. **Cadence.** The age is never fresher than the poll interval, so: | | | |---|---| | meter's own update rate | ~5.0 s (measured 4.97 s) | | `meter_poll_s` default | 5 s — nothing to gain below the meter's own rate | | `meter_max_age_s` default | 30 s, i.e. six polls of headroom | | `meter_poll_s >= meter_max_age_s` | **refused at startup** — every reading would be stale before its successor arrived | | `meter_poll_s > meter_max_age_s / 2` | warned — one missed poll makes the reading stale | A failed poll — timeout, connection refused, non-200, unparseable body — is a **missing** reading. It submits nothing, so the reading does not become 0 W, the last good value and its timestamp are left alone, and the age goes on climbing. That is exactly what a dead meter should look like. **What it still cannot see: a frozen meter.** A meter that answers `200 OK` forever with a stale number is arriving, so no arrival detector — this one included — can tell it from a healthy one. The local API does expose the raw material the HA path never had (the `total_power_*_kwh` registers stop advancing), and the transport tracks it as `unchanged_s`, but it is deliberately *not* folded into the age and *not* thresholded: this controller regulates grid power toward ~0 W, and at a converged −10 W the export register needs six minutes to move by its 1 Wh resolution while the power figure legitimately repeats. Thresholding that at 30 s would rebuild the false-trip limit cycle at the exact operating point the controller aims for. Freeze detection is a separate problem and needs the low-power case solved first. You read it yourself instead: the add-on's status page shows it on the P1 line, as `… 4 rejected, measurement unchanged for 312 s`. On a house drawing real power that figure stays in the seconds; minutes of it while the load is clearly not near zero is the meter to go and look at. #### `sensor.p1_sample_age_s` Published over MQTT discovery whenever a broker is available: **seconds since the newest accepted telegram**, refreshed every second rather than only when a telegram lands. The ESP32's stale-input watchdog subscribes to this exact entity id, so do not rename it. The reason it is recomputed against the clock is that Home Assistant only pushes a state when the state *changes*. A meter sitting at a genuinely constant reading emits nothing, which is indistinguishable — to anything watching the value — from a meter that has died. Watching the age instead separates the two: it climbs when telegrams stop and resets when they arrive, whatever the reading says. The entity is only created when `meter_source` is not `off`. With P1 ingestion disabled there is nothing feeding it, and an age sensor climbing with no ingester behind it would trip the firmware watchdog on a system that is working fine. > **Known limit, `mqtt_p1`.** The age measures *arrival*. On the MQTT path a > bridge that is stuck republishing its last telegram keeps arriving, so the age > stays near zero and a frozen meter still looks fresh. Detecting *that* needs a > change-detector rather than an arrival-detector, and it is not in this version. > ⚠️ **Known limit, `ha_signed` — do not drive a watchdog off this age yet.** > On the HA WebSocket paths the age is stamped when a `state_changed` arrives, > which means it measures *time since the value last changed*, not time since > the meter last reported. Home Assistant offers nothing better: a repeated > reading produces no `state_changed`, does **not** advance `last_reported` on > either the REST or the WebSocket serialiser, and `state_reported` cannot be > subscribed to over the WebSocket at all (`Event filter is required for event > state_reported`). All three measured on the ENV-01 rig against the real > HomeWizard integration with the meter frozen: 0 `state_changed` in 70 s and no > timestamp movement anywhere. > > `ha_dsmr` mostly escapes this because a DSMR telegram updates several entities > and something in the set almost always moves. **`ha_signed` has exactly one > entity, so a healthy meter under a flat load is indistinguishable from a dead > one.** This is not hypothetical: in our own captures > (`sim/scenarios/ha-p1_meter_active_power-2026-08-20.json`) the real house meter > went **42.2 s and 97.0 s** between changes, and 23 Aug peaks at 29.1 s — all > past the default `meter_max_age_s` of 30. > > So `sensor.p1_sample_age_s` on `ha_signed` is safe to *read*, and it is > correct whenever the value is moving, but it must not yet be thresholded by > the ESP32 stale-input watchdog: a quiet house would trip the battery to 0 W. > Raising `meter_max_age_s` is **not** the fix — the two conditions produce an > identical signal, so a bigger number only chooses which of the two errors you > get. The real fix is an arrival stamp the meter itself provides — and that now > exists: **`meter_source: homewizard_local`**. If you have a HomeWizard P1, > switch to it. If your meter is only reachable through Home Assistant, this > limit still applies to you and the watchdog threshold still must not be armed. **Where the age is trustworthy:** | mode | the age measures | safe to threshold from firmware | |---|---|---| | `homewizard_local` | time since the meter **answered** | **yes** — every HTTP response is an arrival | | `ha_dsmr` | time since one of several entities changed | no — statistically usually fine, which is a masked bug, not an absent one | | `ha_signed` | time since the one entity changed | **no** — see above | | `mqtt_p1` | time since a message arrived | arrivals yes, but a stuck bridge republishing keeps arriving | ### Control | option | default | meaning | |---|---|---| | `max_w` | 2000 | Hard limit on what may be commanded. Start low, raise after commissioning. **Not read when `inverters` is declared** — each entry carries its own, and the site ceiling is their sum | | `gain` | 0.6 | Correction per cycle. **At the limit — do not raise** | | `slew_w` | 1000 | Maximum change per cycle | | `deadband_w` | 15 | Ignore errors smaller than this | | `target_grid_w` | -10 | What the meter should rest at. Negative = a slight export | | `step_w` | 10 | Quantisation | | `saturation_w` | 500 | Divergence that counts as "the inverter is at a limit" | | `saturation_cycles` | 3 | How many consecutive cycles before freezing. A cycle is one meter update or `cycle_floor_s`, whichever comes first - see the note below. **Do not set to 1** | | `integrator_max_w` | 0 | Bound on the loop's accumulator, and 0 means "same as `max_w`". Caps how much stale error can be waiting to unwind when the sign flips. **Do not raise it above `max_w`** - the output clamp already bounds what is commanded, so the only thing extra headroom buys is more cycles of wrong-direction power after every saturation event. Lowering it below `max_w` is the useful direction | | `heartbeat_s` | 10 | Refresh interval; must stay well under the firmware watchdog | | `cycle_floor_s` | 15 | The longest the loop may go without evaluating. A deadline on the gap between cycles, reset by every cycle — on a healthy meter it never elapses and changes nothing. Raise it only if your meter is slower than ~10 s; it must stay under `meter_max_age_s`, past which there is no reading to evaluate anyway | | `stale_input_s` | 15 | How long inputs may be missing before commanding 0 W. In P1 mode this clock starts only *after* `meter_max_age_s` has already expired — the two stack, see "How long a dead meter takes to reach 0 W" | | `auto_start` | false | Start controlling on boot (only after commissioning) | | `sign_disagree_w` | 300 | Both the command and the meter must exceed this before a sign difference counts. Must stay **below `max_w`** or the watchdog can never fire, and the add-on refuses to start | | `sign_disagree_s` | 180 | How long they must stay opposed, continuously, before the failsafe trips | | `unit_sign_disagree_w` | 250 | **Two or more inverters only.** Both a unit's own share and its own measured power must exceed this before their sign difference counts. It is `saturation_w / 2`, so the smallest divergence it can see is exactly the gap at which the loop already calls the inverter "not following". Must stay **below `max_w`** or it can never fire, and the add-on refuses to start | | `unit_sign_disagree_s` | 85 | **Two or more inverters only.** How long one unit's command and its own power must stay opposed before that unit is parked | | `site_sign_disagree_w` | 300 | **Two or more inverters only.** Threshold for the site-wide check - the sum of the commands against the meter. The same 300 W as `sign_disagree_w`, for the same reason: near zero the sign is noise | | `site_sign_disagree_s` | 325 | **Two or more inverters only.** How long the site's total command and the meter must stay opposed before every inverter is parked. Longer than `sign_disagree_s` because the command has to cross zero over a rail that is the sum of the roster, at a `slew_w` that is not - measured at 110 s with one inverter and 215 s with two | #### The sign-disagreement failsafe If the setpoint this add-on is emitting and the grid figure it is regulating on point **opposite ways** — charging the battery while the house imports, or discharging it while the house exports — with both over `sign_disagree_w`, for `sign_disagree_s` **continuously**, the add-on commands **0 W** and holds it there. The banner reads `FAILSAFE`, the commissioning list says which two numbers disagreed and for how long, and the `Controller status` entity reports `failsafe`. #### ⚠️ At two or more inverters this is TWO checks, not one (SAFETY-30) The paragraph above describes what a **one-inverter** install does, and it is unchanged: there is one meter, one actuator, and comparing the command against the meter is comparing a thing with a view of itself. With a second inverter that stops being true. The meter answers for **both** units, so a command put on one of them can be opposed to it with nothing wrong (inverter A charging while inverter B discharges more), and - the worse direction - a unit genuinely driving the wrong way can be **hidden**, because its sibling's watts arrive at the meter and the sum looks healthy. So the check splits in two, and they are different faults: - **Per inverter** — that unit's own share against **its own measured power** (the `batt_entity` reading, register 0x0518). This catches *"this inverter is not doing what it was told"*. Only that inverter is parked; the site keeps running on the one that works. Thresholds: `unit_sign_disagree_w` / `unit_sign_disagree_s`. - **Site-wide** — the **sum** of what every inverter has standing, against the meter. This catches *"the site as a whole is pushing the wrong way"*, which no per-inverter check can see because every unit may be faithfully executing its share of a number that is itself wrong. **Every** inverter is parked and the banner names the site rather than an inverter. Thresholds: `site_sign_disagree_w` / `site_sign_disagree_s`, latched under flat `site_sign_tripped` in `/data/state.json`. Both latch, both are cleared by the same *stop, then start*, and both survive a restart. **On a one-inverter install neither pair does anything at all** - the two questions are the same question there, and only the check described above is armed. This is **not** the circulating-power alarm further down: that one compares the inverters *against each other* and catches them pushing power through each other, which nets to zero at the meter and which no command is evidence about. It is also not the saturation freeze, which is a *magnitude* test that shapes the loop rather than a *direction* test that parks an inverter. **It does not clear itself, and restarting the add-on does not clear it either.** Pressing *Start / stop control* twice — stop, then start — is the only thing that does. That is deliberate on both counts: - Commanding 0 W removes the command side of the comparison, so the disagreement always vanishes the instant the trip works. A watchdog that took that as proof the fault was over would hand the inverter straight back to the loop that was driving the wrong way, three minutes later, forever. - The trip is written to `/data/state.json` — under `unit//sign_tripped`, one key per inverter since DEV-02, so a trip caused by one inverter cannot latch another — and restored on startup. The pre-DEV-02 flat `sign_tripped` is written and cleared alongside it as the **rollback view**, so downgrading the add-on past DEV-02 still finds the latch, and a trip taken while the install is rolled back is re-armed by the version that comes back up rather than silently lost. Restarting the add-on is the first thing most people try when they see a red banner, and a latch that a restart clears would bring the controller back **armed, into the same fault, unattended** — and under a Supervisor that restarts a crashed add-on automatically, would do so in a loop. After a restart the banner, the 0 W and the recorded reason are all still there. **What it is for.** This is a loop-integrity check: it asks whether the loop's output direction still matches the input state it was regulating. It catches a polarity error anywhere between the meter and the wire, and an integrator so far wound up that unwinding takes minutes. It is the check that would have caught all four episodes of 2026-08-20, when a commercial controller charged the battery out of the grid, four times, for up to 77 minutes at a time. **What it is not for.** It does not detect an inverter that acts opposite to what it was told — that moves the meter *further* the same way, so command and meter agree while everything runs away. That is the saturation freeze's job (`saturation_w` / `saturation_cycles`), which compares the command against the battery's actual power. The two checks are complementary and neither replaces the other. **Why it will not false-trip on ordinary operation.** A battery that refuses a command (empty, full, standby) leaves the meter where it was, so command and meter agree. A frozen meter drives the loop into agreeing with it. Around the resting point both signals are inside the 300 W gate, so the deadband can never produce one. A load step does flip the meter's sign before the loop catches up — measured on a full captured day, the longest such crossing is 30 s, against a 180 s window. And the watchdog is **disarmed whenever the grid-following loop is not what is driving**: a maintenance grid charge opposes the meter by design and must not be mistaken for a fault. Both numbers are measured rather than chosen, and are exposed only because the ticket requires defaults rather than constants. On the captured healthy day sign agreement is 93.4 %; on the four captured fault clusters it is 0.3 %, 0.9 %, 10.5 % and 0.0 %. There is no reason to move either value without a capture that says so. #### Saturation is counted in cycles, not seconds The specification states the saturation window as **"> 10 s"**. This add-on counts **cycles** instead, and that is a deliberate, accepted deviation rather than an oversight - the acceptance criterion is not met as literally written. A cycle here is one meter update **or `cycle_floor_s` elapsing, whichever comes first**. At the reference P1's ~5 s update rate the default of 3 cycles is usually around 15 s, and the worst case is bounded at `3 x cycle_floor_s` = 45 s. It is still not the 10 s the specification asks for, so the deviation stands - but it is now a bounded number rather than an open one. ⚠️ **This passage used to say something different, and the second half of it was wrong.** Until SAFETY-12 the loop ran only when the meter value *changed*, so a meter that repeated a value stalled the counter for as long as it repeated, with no upper bound at all. That was defended here on the grounds that "a stalled counter is a detection-latency limit and not a runaway risk - the condition that stalls it stops the whole loop, so nothing accumulates while it is stalled". That argument covers **integrator windup and nothing else**. The hazard it misses is **staleness**: while the loop was stopped the heartbeat kept re-emitting the last command and the firmware kept putting it on the wire every 2 s, so a command computed from an old reading went on being executed through a real load change, with every indicator reading healthy. Measured on the rig during TEL-05: 70 s at a literally constant 350.0 W, 14 arrivals, zero control cycles. The half that survives is the first one: the control law is still a pure function with no clock, and the wall-clock window still lives in `Controller`, which has one - see `run_control()`. What changed is that the controller now enforces a floor on the gap between cycles, so `saturation_cycles` finally means a bounded number of seconds. If a tighter window matters on your site, lower `cycle_floor_s` (not below your meter's update interval, or the floor starts firing on a healthy meter) or raise `saturation_cycles` for a fast meter. **This is not a freeze detector, and it deliberately cannot be one.** Nothing here decides whether a repeated reading is true — see `unchanged_s` in the meter section for why no threshold on that is safe at the converged operating point. The floor only stops "the number is the same" from meaning "do not think". The consequence is worth stating plainly: against a meter that is genuinely frozen at a wrong value, the loop will now correct toward that wrong value instead of holding a stale command. It is bounded by `max_w`, the arbiter and the device rating, and it is the same thing that already happened to a lying meter whose value merely jittered — bit-exact repetition was never a safety property. #### Why `target_grid_w` is not zero The deadband is a one-way ratchet: any resting point inside it holds until something disturbs it. Import and export are **separate registers on the meter**, so a rest point of +14 W is billed for every second it holds and no amount of export cancels it - 14 W all day is 0.34 kWh. Biasing the target below zero moves that residue into the export register, which is not billed. The resting band becomes `target ± deadband`, so: | `target_grid_w` | resting band | worst billed leak | export given away | |---|---|---|---| | 0 | -15 … +15 W | ~15 W (0.35 kWh/day) | none | | **-10** | -25 … +5 W | ~5 W (0.12 kWh/day) | ~10 W | | -15 | -30 … 0 W | none | ~15 W (0.36 kWh/day) | Set it to `-deadband_w` if injection is worth nothing to you and you would rather give the energy away than buy it back. Set it to `0` if you are paid properly for export, or if you are debugging and want the loop centred. ⚠️ This is a **billing** knob, not a speed knob. If import is arriving in bursts rather than as a trickle, the cause is tracking lag, and this will not help - see "Why the tuning is what it is". ### Maintenance | option | default | meaning | |---|---|---| | `maintenance_enabled` | false | Enable the monthly cycle | | `maintenance_interval_days` | 28 | Minimum gap between cycles | | `maintenance_start_hour` | 10 | Hour of day a due cycle begins | | `maintenance_discharge_w` | 2000 | Drain rate (exports the surplus). Above `max_w` it is **clamped** to `max_w` — the drain phase SETs the setpoint and the arbiter bounds it, saying so on the status page (`limited by supervised(max_w)`). Warned about, not refused: the cycle still completes, just slower | | `maintenance_charge_w` | 2000 | Charge ceiling, capped again by peak headroom. Must stay **at or below `max_w`** or the cheap-window shaping (`hi = -maintenance_charge_w`) contradicts the supervised limit (`lo = -max_w`), the arbiter resolves it to **0 W**, and maintenance silently never charges in a cheap window — **the add-on refuses to start** | | `maintenance_soc_floor` | 11 | Drain target — stay just above the inverter's own floor. ⚠️ **This is not `peak_soc_floor`.** It is the depth the monthly recalibration deliberately goes to, once, on purpose; `peak_soc_floor` is the depth a money-saving discharge may never reach on any day. The right values differ (11 vs 20 as shipped), which is why they are two keys | | `maintenance_soc_target` | 99 | Charge target | | `maintenance_hold_min` | 120 | Hold at full so the BMS can balance | ### Tariff (all optional) | option | meaning | |---|---| | `peak_forecast_entity` | Quarter-hour demand forecast, for capacity-tariff markets. Empty = no cap | | `peak_cap_w` | The site's capacity-tariff target | | `peak_soc_floor` (20) | **The percent below which the capacity-peak guard will not discharge the battery.** ⚠️ It bounds **the peak guard only** — it is **not a pack-wide reserve**, and ordinary self-consumption discharges straight past it (SAFETY-25, see below). Not optional and not the same thing as `maintenance_soc_floor` | | `bms_soc_floor` (10) | The pack's **own** cut-out percent, the number the BMS enforces whatever you set above. `peak_soc_floor` must be **strictly above** it or the add-on refuses to start | | `price_now_entity`, `price_avg_entity` | Dynamic tariff. Empty = never force a paid grid top-up | On a capacity-tariff site the maintenance charge is capped by the headroom left under `peak_cap_w`, and if the forecast goes over the cap the charge-only clamp is dropped so the battery can shave the peak instead. Money outranks the maintenance schedule. #### Capacity-tariff exposure of the grid-following loop ⚠️ **This section described the exposure BEFORE SAFETY-07. The loop is now capped — see "The capacity-peak guard" below — and what follows is kept because it is still the clearest statement of WHAT is being guarded and why the number is worth what it is.** ⚠️ **`peak_cap_w` caps MAINTENANCE charging. It does not cap the loop.** The grid-following loop is bounded by `max_w` and by the device rating, and by nothing else. That is deliberate — the loop exists to *reduce* what crosses the meter, so under every healthy condition it lowers the peak rather than raising it — but it means one thing is true and worth writing down: **If the meter lies, the loop will happily buy `max_w` from the grid for as long as the lie lasts, and no cap in this add-on stops it.** A meter frozen at a large export reads as "the house is exporting hard", the loop charges the battery to correct it, and the correction is a grid import. At the schema maximum `max_w: 5000` — which is what this house runs, and is also the device rating — that is a 5 kW unattended import. The bill is not the energy. In the Belgian capaciteitstarief the month is billed on its highest quarter-hour average, so **fifteen minutes of this sets the whole month's peak.** A measured case: one 4998 W quarter moved a monthly peak from 4832 W to 5013 W, and every day of that month was billed at the higher figure. What exists today, and what does not: | | | |---|---| | `max_w` bounds the magnitude | ✅ — but the exposure IS the magnitude | | Maintenance charging capped under `peak_cap_w` | ✅ | | **Loop capped under `peak_cap_w`** | ✅ — SAFETY-07, on every `meter_source` but `off` | | Frozen meter detected | ✅ on `homewizard_local` only, **alarm only** | | Frozen meter *stopped* | ✅ — SAFETY-07 forbids importing while the meter is frozen | | SoC guard on the loop | ❌ — the BMS is the only energy backstop | On the legacy `meter_source: off` path there are no P1 telegrams, so there is no quarter-hour average to guard, and the status page says **NOT COVERED**. There the mitigation is still operational: set `max_w` no higher than the loop actually needs (the tuning was measured at 2000 W and a 1.78 kW load step is tracked fine there), fit the e-stop, and watch for the alarm. ### The capacity-peak guard **What it does.** Every cycle the add-on projects the open quarter to its end-of-interval average — from P1 telegrams only, never from the command — and compares it to a ceiling. Over the ceiling it files one claim: a **lower bound on the setpoint**, at `P_PEAK`. That single shape is both behaviours §10.1 asks for: a hard clamp on charging while the bound sits above the standing charge, and pre-emptive discharge while it sits above zero. It can never cap discharge or export, because a floor cannot. **The number.** `excess = 900 × (projected − ceiling) ÷ seconds remaining`, and the floor is the **measured** battery power plus that. The 900/remaining factor is the design rather than an accident: it is 1.0 at the top of the quarter and grows, so the guard is gentlest when its projection rests on the least evidence and becomes aggressive only once the quarter is nearly measured. **The ceiling** is `peak_cap_w`, raised to the month's banked peak when that already stands higher — once a month's bill is set at 5013 W, holding later quarters to 3500 W buys nothing and costs real charging. **That relaxation is granted only by an OBSERVED reading:** a peak store that cannot be read leaves the ceiling at the cap, so a broken instrument makes the guard stricter, never looser. **When it cannot see, it forbids importing.** Three states are not evidence and are checked before the projection is graded: no open quarter (a fresh averager projects a confident 0 W, which is under every ceiling there is), a meter gap longer than `meter_max_age_s`, and SAFETY-18's frozen-meter conjunction. In all three the claim becomes a floor of **0 W**. That is the backstop for the frozen meter: the alarm arrives at `meter_freeze_s` (300 s) of a 900 s billing quarter and commands nothing, and this stops the import. **It trips, where the freeze detector only notifies,** and the captures are why. On the healthy reference day (2026-08-23) it engages on **zero** of 95 quarters. The action is level-triggered and unlatched — re-derived from a fresh projection every cycle, released the instant the projection drops back — so a false engagement costs one cycle of discharge rather than a parked battery. And it is a LIMIT, so every stop in the watchdog table still outranks it. **Replayed on 2026-08-20**, the day the vendor controller failed: the billed quarter measured **5029.8 W**, above the inverter's own 5000 W rating, and the guard brings it to **3485 W** — under the soft limit, without ever asking for more than the inverter can give. Across both committed days the quarters under the limit go from 189/190 to 190/190. Two days is not thirty and does not close AC 3; it is the comparison two days can support. **What it alarms on is saturation, not engagement.** An engagement is an ordinary control action and goes to the action log and the status page. A *saturated* guard — asking for everything the inverter has while the quarter is still projected over — raises one notification (`goodwe_peak_saturated`), because that is the one state where the money will be spent and shedding load is the only thing left that changes the bill. **No new option for the CEILING.** It is `peak_cap_w`, which already shipped. The coverage threshold is `meter_max_age_s`, the freeze predicate is `meter_freeze_s`, and the achievable discharge comes from `max_w` and the device rating — every one of them a key that already exists. #### The energy floor under the forced discharge (`peak_soc_floor`) The guard above can **command a discharge**, and until SAFETY-24 nothing in the add-on bounded how far down it took the pack — the BMS was the only backstop. On the 2026-08-20 replay the guard asks for **878 Wh in a day**. That is not absurd: the BMS floor is real and it works. But it is *the pack's* protection, not *yours*. A month of aggressive quarters can leave the battery repeatedly parked at that cut-out with no record on this side of why, and the first symptom — a battery that is never available when you want it — looks exactly like the SoC drift the monthly maintenance cycle exists to correct. - **`peak_soc_floor` (20 %)** is where the forced discharge stops. Below it the guard files a **0 W** floor instead of a sized one: charging stays blocked (that can only ever lower your offtake), and no further discharge is asked for. - **⚠️ IT BOUNDS THE PEAK GUARD ONLY. IT IS NOT A PACK-WIDE RESERVE, AND THE NAME READS LIKE ONE.** The ordinary self-consumption loop — the grid-following control law that holds your meter at zero — has **no SoC floor of any kind**. It will discharge straight past this number and keep going until the pack's own BMS cut-out stops it. What you are promised by `peak_soc_floor: 20` is *"the capacity-peak guard will not spend the pack for money below 20 %"*, and **nothing more**. See below for what that costs on a real evening. - **When it binds you are told**, once per episode, with notification `goodwe_peak_soc_floor` and a status-page row reading `PEAK GUARD FLOOR-LIMITED`: the quarter **will** go over the ceiling, so shedding load is the only thing left that changes the bill. Failing to shave is never silent — the euro figure is the whole point of the guard. - **An unreadable SoC is treated as floor-limited, not as a full battery.** A full battery is exactly the value that would disarm this floor. - **`bms_soc_floor` (10 %)** is the pack's own cut-out — register `0x0560` on the reference GW5000S-BP, consistent with DoD 90. It exists so the add-on can **refuse to start** when `peak_soc_floor` is at or below it: such a floor can never be the thing that stops the discharge, and a guard that advertises a backstop it does not have is the one thing this project will not ship. Equal is refused too — equal buys zero margin. Why 20 %: the reference pack is 13.8 kWh usable, so 10 points of margin over the BMS cut-out is about 1.6× the guard's worst measured day. If your pack is smaller, or your quarters are worse, raise it. #### ⚠️ What `peak_soc_floor` does **not** protect (SAFETY-25) **On a sustained-load evening this add-on will take your battery to the BMS cut-out, whatever `peak_soc_floor` says.** That is measured, not argued. Replayed on the committed 2026-08-20 capture, 19:00–22:00 UTC — three hours of house load after the sun has gone, 830 W average, not one watt of export in the window — with the 13.8 kWh reference pack started at 21 %, one point above the shipped floor: | | | |---|---| | pack at the start of the evening | **21 %** (one point above `peak_soc_floor`) | | pack three hours later | **10.0 %** — the `bms_soc_floor` cut-out | | energy the loop took out | **1525 Wh** | | control cycles below `peak_soc_floor` | **549 of 587**, and **343** of those still delivering discharge | | cycles on which the peak guard filed *any* floor | **0** | | same replay at `peak_soc_floor` = 5, 11, 20, 60 | **the same 10.0 %, to four decimal places** | That last row is the point: **this is a property of the control law, not a value you can configure.** Raising `peak_soc_floor` to 60 % changes nothing at all, because the guard it bounds is not the thing doing the discharging. **And the two can happen in the same cycle.** On the high-load block of the same day (15:00–17:00 UTC) with the pack below the floor, the guard reports `PEAK GUARD FLOOR-LIMITED` — *"commanding no forced discharge"* — on 49 cycles, and on **all 49 of them** the loop is simultaneously being granted a discharge of up to 2000 W by the arbiter. The status page is telling you the truth about the guard while the battery empties. **Why it is built this way, and why SAFETY-24 could not fix it.** The peak guard files a `lo` limit — a *lower* bound on the setpoint. That asymmetry is exactly what makes the guard safe: it is provably incapable of lowering a target, capping a discharge or contradicting the arbiter. The same property makes it incapable of stopping a discharge the loop itself wants. A floor on the guard cannot become a floor on the pack by being raised. **Is this a runaway?** No. Self-consumption discharge is demand-driven and self-limiting: it stops when the house stops drawing, and every watt of it is serving load you would otherwise have imported. It is not SAFETY-18's frozen-meter rail. What it means is that the *depth* your pack reaches on a heavy evening is set by your house, not by any number in this file, and the BMS is the only thing underneath it. **This is now a recorded decision, not an open question.** On **2026-09-02** the product owner took **Option A**: the BMS cut-out is **deliberately** the only backstop for demand-driven discharge, and a loop-side reserve floor is **deferred** rather than rejected. The options, their costs, the measured replay and the reasoning are in [`DECISIONS/SAFETY-25-loop-soc-floor.md`](DECISIONS/SAFETY-25-loop-soc-floor.md), together with the revisit trigger (`ALLOC-01`, the host-side share allocator) under which a reserve becomes safe to build. **Nothing about the behaviour above changed** — Option A is what has always shipped. What changed is that this section now describes a choice somebody made, and you can read why. ### The winding-loop alarm (the output clamp) Every setpoint this add-on writes is clamped to `max_w` before it leaves the process, and **when that clamp actually engages, it alarms.** The clamp on its own is not the feature - this project already clipped, and the clipping is what hid the defect the guard exists for: with the inverter switched off entirely an unclamped integrator climbed ~130 W per 4 s past 10 kW and, pinned at the 5 kW rail, reported **14 768 W**. Clipped silently, that is a flat, legal-looking 5000 W hold on every dashboard, and nothing anywhere says the loop asked for three times it. **What "the rating" is.** The bound is `max_w`, and only `max_w`. It is already validated against the setpoint device's own range at startup - the add-on *refuses to start* if `max_w` exceeds what the device accepts (and again once ESPHome is up and the real rating is known), so by the time the loop runs the two numbers agree. The device range is applied a second time inside the write as defence in depth; after a successful validation it cannot bite, and if it ever does, that engagement alarms too and names the bound. **Clamping is not saturation, and the two never share a channel.** | | what it means | what happens | |---|---|---| | **clamp** | the *computed* value exceeded the rating | a software bug signal - something upstream is winding. **Alarm.** | | **saturation** | the inverter is not following a perfectly *legal* command | a hardware condition - freeze the integrator. **No alarm.** | A loop can be legally saturated all day: a cold pack, a curtailed inverter, an export limit. Routing the clamp through a saturation-shaped alarm puts the bug signal inside the noise, which is the same silence as clipping quietly. They share no reason code, no notification id, no status row and no counter. **It is an alarm, not a trip.** The clamped value is written and the loop keeps running - this is not the sign-disagreement failsafe, which commands 0 W. You get a persistent notification (`goodwe_output_clamp`, replaced rather than stacked), an `ERROR` in the log with the reason code `OUTPUT_CLAMP`, a row in the event list, and a red status banner while it is engaged. Once it clears, a warning row keeps the engagement count so the evidence does not vanish with the condition. Consecutive engagements share one event row carrying the exact count, because the event list keeps only 40 rows and a row per cycle would flush every other guard's entries out of it. **There is nothing to configure**, deliberately. The bound is `max_w`, which you already set; giving the guard a limit of its own would be a second number that can disagree with the first, which is exactly the failure the startup validation exists to prevent. The alarm's cadence - first engagement, then re-asserted every 30 s while it persists, cleared after 3 clean cycles - is fixed for the same reason `RAIL_FRAC` is: it describes the notification bus, not the plant. WARNING: **on a default install the engagement you will see is the integrator's, not the output's.** The control law bounds the integrator to `max_w` and *then* derives the command from it, so the command itself can never come out over the rating unless `integrator_max_w` has been deliberately raised above `max_w`. Both are watched. A guard that watched only the emitted value would be silent on every standard configuration. ### The frozen-meter alarm A meter that has died is easy — it stops answering, the sample age climbs past `meter_max_age_s`, the reading becomes missing, and the add-on and the ESP32 both command 0 W. A meter that keeps answering `200 OK` with a document that never changes is the hard one: **every freshness mechanism in the stack reads it as healthy**, because it really is arriving on every poll. The loop then integrates a constant error and winds to the rail, in 75–360 s at `max_w: 5000`. The add-on alarms when **both** of these are true at once: - the meter's own document (power figure *and* both kWh registers) has not changed for `meter_freeze_s` — 300 s by default; **and** - the command standing on the wire is at the rail, within 5 % of the ceiling the command can actually reach. **That ceiling is `min(max_w, the setpoint device's own rating)`, not `max_w`.** The emitted command is clipped to the device's reported range as well as to `max_w`, so on a 4700 W inverter configured with `max_w: 5000` a rail measured at 4750 W is one the command can never stand at — the guard could not fire, and the status page said `armed` anyway. It now measures the rail against the smaller number and the page names it, saying *"below max_w because …"* when the device is what capped it. (On an install that started, the two are equal: a `max_w` above the device rating is refused at startup. This matters when the rating could not be read at boot — see below.) Neither half is usable alone. A bare "unchanged for N seconds" rule false-trips at the exact operating point this controller aims for — at a converged −10 W a 1 Wh register legitimately takes about six minutes to move — and a bare "at the rail" rule fires on any genuinely large load. Together they are safe in both directions, because a real railed condition means kilowatts still crossing the meter, and a kilowatt advances a 1 Wh register every 3.6 s. **It is an alarm and nothing else.** It does not command 0 W, does not latch, and does not claim the actuator. A false trip here parks the battery; a false notification costs an alert. Turning it into a trip is a separate decision that needs data from a real install — and an answer to "what should the loop do instead", given that 0 W is itself an import of whatever the house is drawing. When it fires you get a Home Assistant persistent notification (`goodwe_meter_frozen`, replaced rather than stacked on a repeat), an `ERROR` in the add-on log, an entry in the UI's event list, and a red banner on the status page. **The loop keeps running.** If the meter really is stuck, stop control from the add-on UI. ⚠️ **Only `meter_source: homewizard_local` is covered.** It is the only transport that reads the meter's own document; on `ha_dsmr`, `mqtt_p1`, `ha_signed` and `off` there is no signal to threshold and the status page says **NOT COVERED** rather than pretending the guard is armed. The same row appears for a second reason: a setpoint device that reports a range from which no command magnitude is available in both directions leaves no rail to measure at all, and a 0 W rail would be satisfied by *every* command. That is reported as **NOT COVERED** too, and the detector stays silent rather than degenerating into the bare "unchanged for N seconds" rule this design exists to avoid. | option | default | meaning | |---|---|---| | `meter_freeze_s` | 300 | Seconds of an unchanged measurement, *while the command is at the rail*, before the alarm | Why 300 s: over 2399 s of this house at the converged operating point (mean grid −14.2 W, 1194 polls, 735 of them repeating the previous reading) the largest `unchanged_s` any sample sees is **8.0 s**, and the longest interval serving no distinct reading at all is **15.4 s**. There is also a structural reason not to lower it much: at 300 s the slowest a *healthy* register can tick and still look unchanged is 12 W, which is inside the 15 W deadband — so the command there is parked at 0 W and the two halves of the rule cannot both be true. At the schema floor of 60 s that figure is 60 W and only the margin is left. ### The circulating-power alarm (SAFETY-31) > **Only at two or more inverters.** At the shipped roster of one this quantity > is identically zero for every reading, no claim is ever filed, and the status > page says *n/a* rather than pretending to watch it. Two inverters can move a great deal of energy while the meter reads almost nothing. Inverter A charging at 3 kW while inverter B discharges at 3 kW nets **~0 W at P1**: the site looks idle, and in reality the packs are being cycled through two round-trip conversion losses continuously, for no benefit. **Nothing else in this add-on can see it, and that is structural rather than an oversight.** Every other guard is a consumer of the *net* figure at the grid connection — the sign-disagreement failsafe gates on `abs(grid_w) > 300 W` and that gate never opens at a netted zero; the capacity-peak guard and the tariff both bill grid exchange. Circulating power is precisely the component of per-inverter power that the sum destroys. So the add-on computes a quantity none of them were computing: ``` circulating_w = Σ|Bᵢ| − |ΣBᵢ| ``` Zero when the units pull the same way. `2 × min(|B_a|, |B_b|)` when they oppose — twice the power going round the loop, which is what both conversion stages are processing between them. It is published as `sensor.goodwe_circulating_power`, deliberately **beside** the grid figure: *"grid 0 W, circulating 6000 W"* is the whole fault in two dashboard rows, and no arithmetic on the grid figure alone can produce the second one. **It is derived from each inverter's own measured power, not from what the controller believed it commanded.** That matters because the allocator already *refuses* to command opposite directions (ALLOC-01's sign-coherence gate), so a figure computed from the allocation record would read zero by construction and detect nothing. What this catches is circulation **nobody commanded** — a unit ignoring or lagging its share, a stale share still being executed, or an inverter doing something of its own accord. | option | default | meaning | |---|---|---| | `circulation_w` | 700 | Watts of measured opposition below which nothing is reported | | `circulation_hold_s` | 75 | Seconds it must stand there continuously before the trip | **Why 700 W and 75 s, and why neither is a round number.** Both were read off 924 closed-loop runs on the two-master test rig in which *nothing* was faulty, swept across the whole range the schema accepts for `gain` and `slew_w`. A momentary opposition is **legitimate**: writes to the inverters are serialised, so on a reversing cycle one unit gets its new number up to a control cycle before its sibling, both slew through zero, and between the two crossings they genuinely oppose. The worst *continuous* legitimate opposition, by threshold, was **505 s at 100 W, 40 s at 250 W, 10 s at 300 W and 5.0 s — one control cycle — at 400 W and above**. The knee is 400 W and it is the schema floor; below it, ordinary operation would hold the sensor over the line for minutes and no usable window could tell that from a fault. 700 W carries margin above the knee because the second inverter's ramp and lag are not yet measured. 75 s is 15× the worst legitimate episode, 2.5× the firmware's own 30 s link-veto window, and comfortably inside the 900 s quarter that bills the capacity tariff. **What happens when it trips, and what it honestly cannot do.** The site is commanded **0 W on every inverter** and latched there until you press start. That is not aimed at making a misbehaving inverter stop — if a unit has stopped listening, no command will reach it. It does two things that do not need its cooperation: it removes *this controller* as one of the two participants in the loop, and it makes anything still happening **visible at the meter** instead of cancelled at it, where the ordinary guards can see it. **If the grid reading does not move after the trip, one inverter is no longer listening and the remaining actuator is a human at the isolator.** **The alarm survives a Home Assistant restart.** The latch is written to `/data` and the notification is re-raised on the first cycle after every start — `persistent_notification` lives only in memory, and an alarm that vanishes with a restart is how a real outage on this system went unseen for over six hours. Restarting does **not** clear the trip; starting control from the add-on UI does, and only after you have read why. ### Energy price providers > **A fetched price moves energy only when you switch arbitrage on.** This > release ships the five provider plugins, the canonical all-in format they > emit, the config that selects one, and — new in OPT-04 — a price-arbitrage > strategy that trades on them. With `arbitrage_enabled: false`, which is the > shipped default, turning a provider on still fetches, validates and publishes > prices and changes no charging decision. > > `static_profile` below needs no network at all, so its cheap window is > computed on every cycle and reaches the maintenance cycle's grid top-up > whether or not arbitrage is armed. | option | meaning | |---|---| | `price_provider` | `off` (default) or one of the five plugins below | | `price_markup_eur_kwh` | Your supplier's margin, EUR/kWh. **Added only when the chosen plugin's feed does not already contain it** | | `price_taxes_eur_kwh` | Levies and VAT, EUR/kWh. Same rule | | `export_price_eur_kwh` | The **injection** price. A separate scalar, not a series — see below | | `price_csv_path` | Where `manual_csv` reads its file | | `price_feed_url` | Override the plugin's default feed. Only a host the plugin itself declares is accepted | | `price_horizon_h` | How far ahead to ask for, hours | | `price_timeout_s` | Per-request timeout | | `static_profile` | A static day/night or fully-fixed tariff. Empty by default — see below | **Which plugin sources what.** This is the one thing to get right, because adding your markup to a price that already contains it makes every future arbitrage decision wrong by that amount, in a direction nothing reports. | plugin | product | the published figure contains | the add-on adds | |---|---|---|---| | `generic_dayahead` | day-ahead | energy only (wholesale EPEX BE) | markup **and** taxes | | `engie_dynamic` | day-ahead | energy + Engie's markup | taxes | | `totalenergies_dynamic` | day-ahead | energy + TotalEnergies' markup | taxes | | `eneco_eddy` | **real-time / imbalance** | everything, all-in | nothing | | `manual_csv` | day-ahead | everything, all-in | nothing | You cannot get this wrong by editing the markup: each plugin *declares* what its feed contains and the add-on adds only the rest. Set a markup under a plugin that already carries one and it is **ignored, with a line in the log saying so** — never applied twice. That holds **given a correct declaration**, and it is worth knowing where the line is. What the add-on enforces mechanically is that a plugin cannot obtain the markup or apply it: the numbers are not reachable from plugin code, and a plugin whose code mentions them fails to load at all. What it cannot check is whether a plugin described its supplier's feed truthfully — that is a claim about somebody else's tariff, and no code can verify it. If you write a plugin, the `sources` declaration is the part a reviewer has to read. `eneco_eddy` is a real-time/imbalance product rather than a day-ahead one. It is flagged as high-volatility, which widens arbitrage thresholds once the optimiser lands. That comes from the plugin's own declaration, not from its name. **`manual_csv` — the offline fallback.** It needs no internet, no supplier account and no HTTP stack at all, and it is the supported way to run this add-on price-aware on a site with no outbound connectivity. Write a file and point `price_csv_path` at it: ```csv start,eur_per_kwh,provisional 2026-01-15T00:00:00+01:00,0.1834,false 2026-01-15T01:00:00+01:00,-0.0210,true 2026-01-15T02:00:00+01:00,0.3115,false ``` - `start` **must carry its UTC offset** (`+01:00` in winter, `+02:00` in summer). A bare `2026-01-15 00:00` is refused, because for one hour every October a local wall clock names two different moments. - `eur_per_kwh` is **all-in** — energy *plus* markup *plus* taxes. This plugin has no way to know what your numbers already include, so it assumes everything and adds nothing. - Negative prices are valid and are kept. They are the best charging hours of the year. - `provisional` is optional; omit the column and every hour is treated as settled. **When there are no prices at all** — provider off, feed unreachable, CSV missing — the add-on does not guess. It reports *no price data*, which is a distinct state from "prices, all of them zero": the plan is marked provisional and arbitrage is disabled, per the degradation matrix. It never falls back to a price of zero, which would read as free electricity. **Injection is priced separately** (`export_price_eur_kwh`). In Belgium it is often near zero, which by itself strongly favours self-consumption over export. It is a single number rather than a curve because no supported supplier publishes a dynamic injection tariff; negative values are accepted. **The old Home Assistant price sensors.** `price_now_entity` and `price_avg_entity` still work and are unchanged: the add-on compares them and uses the result as a cheap-window hint for the maintenance charge. They are **not compatible with `price_provider`, and not with `static_profile` either** — configure two of them and the add-on refuses to start, naming the conflict, because the add-on reads exactly one and the loser is silent. Use one. ### Static day/night and fully-fixed tariffs (`static_profile`) Most Belgian households are **not** on a dynamic contract, and an EMS that only works under hourly pricing is an EMS for a minority. `static_profile` is how a two-period day/night tariff or a single fixed price becomes a first-class configuration rather than "turn the price feature off and hope". It is one option, holding a JSON object, on one line: ```json {"periods": [ {"name":"day", "from":"07:00","to":"22:00","days":"mon-fri","eur_per_kwh":0.34}, {"name":"night", "from":"22:00","to":"07:00","days":"mon-fri","eur_per_kwh":0.26}, {"name":"night", "from":"00:00","to":"24:00","days":"sat,sun", "eur_per_kwh":0.26}]} ``` A **fully fixed** tariff is one period covering the whole week: ```json {"periods": [ {"name":"fixed","from":"00:00","to":"24:00","days":"all","eur_per_kwh":0.31}]} ``` - `eur_per_kwh` is **all-in** — energy *plus* your supplier's markup *plus* taxes — exactly like `manual_csv`. `price_markup_eur_kwh` and `price_taxes_eur_kwh` are **not** added to it. - `days` takes `mon`…`sun`, ranges (`mon-fri`, `fri-mon`), comma lists (`sat,sun`) and the words `weekday`, `weekend`, `all`. - Times are **local Belgian time** and windows are half-open: `07:00`–`22:00` includes 07:00 and excludes 22:00. A window may cross midnight. - The clock changes twice a year and the add-on handles it. It generates prices against absolute instants, so a spring-forward day is 23 hours and an autumn-back day is 25. > ⚠️ **A window belongs to the day the clock reads, not the day it started.** > `22:00`–`07:00` on `mon-fri` covers Friday 23:00 but **not** Saturday 03:00 — > Saturday 03:00 is Saturday's. That is why the example above has a third row > for the weekend. Leave it out and the add-on **refuses to start**, naming the > uncovered hours. **Every day type must be covered exactly once.** The periods have to tile all seven days with no gap and no overlap, and the add-on checks that at startup. A gap is refused rather than filled in, because a made-up price is one the optimiser would trade on; an overlap is refused because otherwise one of the two prices silently wins on the order you typed them in. **What it changes today.** The add-on works out which window you are in and whether that window is *cheap* — strictly below the tariff's seven-day average. The Web UI shows both on a new **Tariff** row, and the maintenance cycle's cheap-window grid top-up uses it, which is exactly the "shift load into the cheap window" behaviour a day/night tariff asks for. Nothing else moves energy on a price yet. Under a **fully fixed** tariff every hour equals the average, so there is *no* cheap window by construction and the add-on runs self-consumption only — which is the correct behaviour for that product, not a limitation. Peak shaving, the capacity-tariff tracker, the reserve floor and the maintenance schedule are all unaffected: the capacity tariff is a network cost charged whatever your energy contract is. **Recommended even on a dynamic contract.** When a price feed is unreachable the add-on falls back to your static profile, marks the plan provisional and disables arbitrage. With `static_profile` empty there is nothing to fall back to, and the site simply has no tariff until the feed returns. It is not required — the add-on warns rather than refusing — but filling it in is what makes that fallback work. ### Price arbitrage (`arbitrage_enabled`) §10.1 priority 3: charge in the cheapest published hour, discharge in the dearest, **and only when the spread covers what the round trip costs.** Off by default — this is the first strategy in the add-on that commands the battery *against* the meter on purpose, so it is armed deliberately or not at all. | option | meaning | |---|---| | `arbitrage_enabled` | `false` by default. Arms the strategy | | `cycle_cost_threshold_eur` | What one full round trip costs per kWh — pack wear plus conversion losses. A spread below this is not traded | | `arbitrage_soc_floor` | The reserve arbitrage may not spend, % | | `arbitrage_soc_ceiling` | The headroom it may not overfill, % | **What it needs, and what the add-on refuses.** Arbitrage requires a price source (`price_provider` or `static_profile`) and a P1 meter (`meter_source`). Without a price source there is nothing to tell cheap from expensive; without P1 the capacity-tariff peak guard never runs, and §9.1 puts peak shaving above arbitrage — a charge that nothing measures is exactly what that guard exists to prevent. Both combinations are **refused at startup** rather than left looking armed. **Peak shaving always wins.** The strategy cannot obtain a spread at all without first answering whether the peak guard is holding, and even if it could, the guard's floor is filed at a higher arbiter priority and clamps an arbitrage charge. Discharging is never capped by it — only offtake is billed. **It never exports into a negative price** (§17). A negative hour is the best possible hour to *charge* in and that is still allowed; selling into one gives energy away and pays for the privilege. **At the shipped threshold a static day/night site does not trade.** The realistic Belgian day/night spread is about 0.08 EUR/kWh and the default threshold is 0.10, so the honest answer on such a site is "no opportunity", and the status page says so with the numbers. Whether 0.10 is the right default is a product decision, not a bug: lower it only if you know what a cycle costs your pack. **The prices are fetched in the background**, never on the control tick — a supplier's TLS timeout on that path would be a supplier able to push the add-on towards the firmware's 30 s failsafe. The plan refreshes every 30 minutes and retires itself if the refresh stops answering, at which point arbitrage stops with it. ### Site | option | meaning | |---|---| | `estop_fitted` | Whether the RS485 e-stop is installed. Drives the warning banner | | `log_level` | `trace`/`debug`/`info`/`warning`/`error` | ## The Web UI The ingress panel shows live values, why the controller is commanding what it is, and a **Commissioning** checklist that names any problem in words. It also carries the three buttons: start/stop control, force a maintenance cycle, and abort one. ## Status entities If an MQTT broker is available the add-on publishes setpoint, grid power, battery power, circulating power, state of charge, maintenance phase and controller status by MQTT discovery. This is observability only — the controller works fine without a broker, and MQTT problems can never affect control.