e306c74cb81a9b8ef1621f87a39a093c196b1ebe
4
Commits
| Author | SHA1 | Message | Date | |
|---|---|---|---|---|
|
|
e306c74cb8 |
DEV-02: per-instance inverter objects, so nothing is graded against a sibling
checks / unit (pull_request) Successful in 4m15s
Every piece of per-device state in the Controller was a scalar, and several of
them are safety inputs. app/inverter.py introduces an `Inverter` that owns its
entities, its rating, its device range, its SignWatchdog, its last_write and
its last_beat, under store keys namespaced by unit name. The Controller holds a
list of them and keeps only what is genuinely site-level: the P1 reading, the
site integrator, and the tariff quarter.
WHAT THE SCALARS WERE SILENTLY ASSERTING
dev_min/dev_max one pair, read from one setpoint_entity. A second
inverter's rating was NEVER READ AT ALL, so its clamp, its
freeze rail and the peak guard's achievable_w were the
first one's numbers.
soc one reading into the maintenance FSM, SAFETY-24's pack
floor and arbitrage's bounds. An average lets the emptier
pack be driven below its own floor.
sign_wd ONE SignWatchdog, whose own docstring says "one instance
per actuator", latched under FLAT store keys - so a trip
caused by B latched A across restarts and one operator
press cleared both.
last_beat one deadline and one serialised hass.call(), so a hung
write to A ate B's 30 s layer-1 budget.
actual_w BECAME SITE LEVEL WHILE THE READINGS BECAME PER-INSTANCE, and those
are opposite directions on purpose. compute()'s anti-windup test is
`abs(prev_w - actual_w) > saturation_w` with prev_w the SITE target, so feeding
it one inverter's power compares a site number against a unit number, trips the
saturation freeze permanently and leaves a standing grid error. Measured on
admin/goodwe's two-master rig (tools/alloc_sim.py --splits, 2 kW load, 40
cycles), worst |delta| between splits at the meter:
gain one unit's power the site sum
0.2 510 W 0 W
0.4 250 W 0 W
0.6 50 W 0 W
That was ALLOC-01's disclosed finding; test_alloc.py part 8 kept its stimulus
and now grades the other row.
THE STORE MIGRATION IS GRADED, NOT MERELY PERFORMED. sign_tripped/sign_reason
move to unit/<name>/... once, verified by READING BACK what was written, and
the version marker is set only when nothing that carried state was lost. The
flat keys stay in the file so a rollback still finds its latch. And __init__
compares the pre-migration flat latch against what unit A actually came up
with: if the latch did not survive it is RE-ARMED from the legacy value and
shouted about. A latch that silently fails to migrate is a disarmed safety
guard on an install whose state file says it is protected - which is strictly
worse than never persisting it, because now there is evidence saying it is
fine. test_inverter.py part 2 breaks the migration and watches the guard fire.
HEARTBEATS ARE INDEPENDENT AND THE BUDGET IS DERIVED. Each inverter owns its
deadline, the refreshes go out concurrently, and each write is bounded by
WRITE_BUDGET_S = 4 s. The inequality is graded rather than asserted: 4 +
heartbeat_s's schema maximum of 25 < 30, validate.FIRMWARE_INGEST_VETO_S.
Verified by injecting a transport that accepts and never answers.
live_units() ANSWERS HONESTLY. A unit whose every write has been rejected for a
whole layer-1 window is not commandable; the allocator drops it, the survivors
carry its share, the action log names it, and the dropped unit is commanded
0 W rather than left standing on its last share. A roster entry with NO
setpoint_entity is deliberately not handled there - that is a configuration
that cannot be delivered, and it reaches main.py's refusal branch, which is how
that branch keeps a live trigger after this card removed its old one.
AT N=1 NOTHING MOVES. The removed scalars survive as read/write properties of
the sole inverter, so every existing replay runs unmodified - and they REFUSE
at N>=2 rather than answering for the first inverter, which is the tripwire on
a consumer that was never made per-instance.
EVIDENCE. 19 files green. test_inverter.py is new (82 checks). Eighteen
mutations were applied to the shipped modules on a purged tree via
tools/mutation_run.sh and each was observed RED. Two of them SURVIVED first
time and the checks were changed rather than the table: the serialised dispatch
and the shared last_beat both passed while part 6 gathered its own writes and
computed its own `due` list. send_heartbeats() was extracted from run_control()
so the shipped dispatch is reachable by a check at all.
INVERTER B STILL DOES NOT EXIST. build_roster() returns exactly one inverter
from the flat options and is the one function CFG-04 changes; every two-unit
figure here is architecture, and the second rating in the checks is marked a
hypothesis.
Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01BwRLw7eKYj2byVdwB6kbjU
|
||
|
|
cc4e88490b |
SAFETY-02 review: a latch that a restart clears is not a latch
BLOCKER. `auto` was persisted and `sign_wd.tripped` was not, so reconstructing the Controller against the same store - which is what a container restart does - brought it back ARMED, into the same fault, unattended: tripped=False, banner back to NOT READY, and it resumed commanding -1000 then -2000 W before re-tripping 180 s later. "Restart the add-on" is the first thing an operator looking at a FAILSAFE banner and a 0 W inverter will try, and under a supervisor that restarts a crashed add-on it is a loop of three-minute wrong-direction bursts. DOCS.md's "it does not clear itself" was false across a restart. `sign_tripped` and `sign_reason` are Store keys now, beside the maintenance state and for the reason store.py's own docstring gives. Written the moment the trip happens - reason first, flag second, so a crash between the two can never persist a latch with no explanation - restored in Controller.__init__, cleared only by the operator's start. The regression is covered: reverting the restore fails seven checks in test_watchdog.py. Review follow-ups, no behaviour change: - The arming gate is tested against the REAL arbiter. It is the decision the ticket turns on and it was asserted in three comment blocks and verified by nothing - every case passed `following` in as a literal. Twelve claim configurations now derive it from resolve(), including the redirect case `winner == "loop"` alone would have got wrong and the `lo` limit that raises magnitude without flipping sign. - The MQTT `status: "failsafe"` value is tested. The check that claimed to cover it restated the line above it and never touched the payload. - The worked example described a config that does not ship: at the defaults maintenance_charge_w 2500 against max_w 2000 is an arbiter contradiction and 0 W, not a -2500 W charge. Rewritten at 1500 W. The contradiction is a real pre-existing bug - a default cheap-window maintenance charge silently never happens - filed separately and deliberately not fixed here. - Forward hazard recorded at the gate: `winner == "loop"` disarms the watchdog under any higher-priority SET, and a peak-shaving strategy at P_PEAK IS grid-following in sign, so it would blind this for every peak event. - disagrees() is public so the replay harness stops carrying its own copy of the predicate it grades. - held_s takes the clock instead of reading one. - The two limits are now each stated in both places rather than one each. - The no-false-positive argument is tied to control.py's freeze permitting the command to cross zero; under the shrink-only encoding control.py records as rejected, this would false-trip on a load step. - Measured figures corrected: 93.4 % / 4212 of 17280, per-cluster 0.3/0.9/10.5/0.0, and the near-circularity of those figures is now stated rather than leaned on. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_01Du77usMj8XNKNFZGmUiWDa |
||
|
|
594f8f9fc9 |
Six silent failures found by installing this on a live system
Migrated the reference site off the YAML packages and onto the add-on. Every bug below presented identically: the add-on starts, logs "started", serves its UI, and cannot do its job. - run.sh needs #!/usr/bin/with-contenv sh. s6-overlay sanitises the environment for services, so a plain shebang means SUPERVISOR_TOKEN is absent and every Core API call is 401 - while homeassistant_api: true makes permissions look granted. Startup now prints the token length and probes the API. - Supervisor keys the image by config.yaml `version`, so rebuilding without a bump reuses the old image. Two fixes appeared not to work because of it. - Alpine is musl and has no aiohttp wheel on PyPI; deps now come from apk so nothing compiles on a client's Pi. - Alpine ships paho-mqtt 1.x, which has no CallbackAPIVersion. That raised at construction and took the control loop down with it - so MQTT setup is now wrapped too. Observability must never be able to stop the controller. - MQTT discovery is published from on_connect: paho silently drops QoS-0 publishes issued before the CONNACK, so the previous code announced nothing while logging "MQTT connected". - Repeated failures now log once a minute. Six warnings a second rolled the log buffer and destroyed the startup diagnostics needed to find the 401. - auto_start could never fire, because the store's defaults always supplied auto: False for the fallback to find. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_016NckgXecasQb2eSsPYNSW6 |
||
|
|
0a1e61dbc9 |
Packaged as a Home Assistant add-on, with a field guide
Turns the reference RS485 controller into something a technician can install at a client site: a typed config form instead of YAML, an ingress UI that names misconfiguration in words, and persistent state that cannot be broken by a timezone. Why an add-on rather than YAML packages or blueprints: - Blueprints cannot create helpers, and the maintenance cycle is a state machine whose phase and completion date must survive restarts. - YAML packages need filesystem access, a configuration.yaml edit and a restart - none of which belong in a client install. - Add-ons authenticate with SUPERVISOR_TOKEN, so there is no long-lived token to generate, store or leak on someone else's machine. - Requires HA OS/Supervised. Container and Core installs cannot run add-ons at all, which is a market decision, not an oversight. The control law and the maintenance machine are pure functions with no Home Assistant imports, and both ship with runnable checks (22 and 22 assertions). Every assertion corresponds to a rule whose absence caused an observed failure on hardware - the saturation duration term, the clamp-before-slew ordering, the deadband, the sign convention. One behaviour deliberately differs from the implementation it replaces: when its inputs go missing this commands 0 W rather than replaying the last setpoint. The reference version kept replaying, which the hardware watchdog cannot catch - from the ESP32's side, Home Assistant is still talking to it. Includes the ESPHome firmware (now parameterised: node name, inverter rating, watchdog timeout) and the optional RS485 e-stop. FIELD-GUIDE.md carries the commissioning gates, all judged on the wire rather than on how Home Assistant looks, plus the written statement a site without an e-stop needs signed. Co-Authored-By: Claude Opus 5 <noreply@anthropic.com> Claude-Session: https://claude.ai/code/session_016NckgXecasQb2eSsPYNSW6 |